R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
ntgrxwstns-1 12.12.03
Wallstations
Architectural Style
®
Turns lights off.
Selects scene 10.
Selects scene 14.
Restores previous scene.
Disables lockout.
Temporarily dims selected zones.
Control Units act independently: movable
wall closed to make two spaces.
Disables zone lockout.
Turns sequencing off.
Selects scene 1.
Selects scene 9.
Selects scene 13.
Selects scene 16 (all lighting full on).
Locks all other system controls.
Temporarily brightens selected zones.
Control Units act in combination; movable
wall open to make one large space.
Allows only temporary zone adjustment.
Preset scene settings are not affected.
Loops continuously through scenes 5 to
16 using fade times entered at Control
Units.
Entrance Wallstation
Scene Selection
Panic Wallstation
Fine Tuning
Single-Partition
Status Wallstation
Zone Lockout
Sequencing
NTGRX-2B-SL-__-_
2-Button with Status Light Wallstation
Description
• Often used in entryways to turn lights on
and off.
• Functionality can be selected in the field.
• Status lights indicate which button was
pushed last.
• Works with GRAFIK Eye 3000 and 4000
Series Control Units.
• Invokes functions in just one Control Unit or
group of up to eight Control Units.
Finish and Engraving Options
Available with engraving to meet specific
project needs.
Status Light
Status Light
Color and Finish Codes
Field Selected Functionality
DIP Switch Settings
5 6 7
Top button:
Bottom button:
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
ntgrxwstns-2 12.12.03
Wallstations
Architectural Style
®
NTGRX-KS-__-_
Keyswitch Wallstation
Description
• Ideal for public spaces.
• Limits access to GRAFIK Eye Control Units.
Authorized personnel must use a key to adjust
lighting.
• Functionality can be selected in the field.
• Works with GRAFIK Eye 3000 and 4000 Series
Control Units.
• Invokes functions in just one Control Unit or a
group of up to eight Control Units.
Finish and Engraving Options
Available with engraving to meet specific
project needs.
Color and Finish Codes
Turns lights off.
Selects scene 10.
Selects scene 14.
Restores previous scene.
Disables lockout.
Temporarily dims selected zones.
Control Units act independently: movable
wall closed to make two spaces.
Disables zone lockout.
Turns sequencing off.
Selects scene 1.
Selects scene 9.
Selects scene 13.
Selects scene 16 (all lighting full on).
Locks all other system controls.
Temporarily brightens selected zones.
Control Units act in combination; movable
wall open to make one large space.
Allows only temporary zone adjustment.
Preset scene settings are not affected.
Loops continuously through scenes 5 to
16 using fade times entered at Control
Units.
Entrance Wallstation
Scene Selection
Panic Wallstation
Fine Tuning
Single-Partition
Status Wallstation
Zone Lockout
Sequencing
Field Selected Functionality
DIP Switch Settings
5 6 7
Turning key clockwise:
Turning key counter-clockwise:
2
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
ntgrxwstns-3 12.12.03
Wallstations
Architectural Style
®
NTGRX-4B-__-__
4-Button Wallstation
Description
• Used to select scenes in GRAFIK Eye Control
Units.
• Scene selection functionality can be selected in
the field.
• Status LEDs indicate which scene is selected.
• Works with GRAFIK Eye 3000 and 4000 Series
Control Units.
• Selects scenes in just one Control Unit or a group
of up to eight Control Units.
• Can be ganged with the NTGRX-4S Wallstation to
give occupants access to 8, 12, or 16 scenes.
Finish and Engraving Options
• Available with engraving to meet specific project
needs.
• Available in a “no-insert” version for a sleeker look.
LEDs
Insert
Scene
selection
buttons
Color and Finish Codes
Field Selected Functionality
Scene selection
buttons activate:
Scenes 1 to 4
Scenes 5 to 8
Scenes 9 to 12
Scenes 13 to 16
DIP Switch Settings
5 6
3
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
ntgrxwstns-4 12.12.03
Wallstations
Architectural Style
®
NTGRX-4S-__-_
4-Scene with Off and Raise/Lower
Wallstation
Description
• Used to select and adjust scenes in GRAFIK Eye
Control Units.
• Scene selection functionality can be selected in
the field.
• Status LEDs indicate which scene is selected.
• Off button turns all lights off.
• Master raise/lower button brightens or dims all
lighting in the selected scene.
• Works with GRAFIK Eye 3000 and 4000 Series
Control Units.
• Selects scenes in just one Control Unit or a group
of up to eight Control Units.
Finish and Engraving Options
• Available with engraving to meet specific project
needs.
• Available in a “no-insert” version for a sleeker look.
LEDs
Off
Master raise/lower
Scene
selection
buttons
Insert
Color and Finish Codes
Field Selected Functionality
Scene selection
buttons activate:
Scenes 1 to 4
Scenes 5 to 8
Scenes 9 to 12
Scenes 13 to 16
DIP Switch Settings
5 6
4
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
ntgrxwstns-5 12.12.03
Wallstations
Architectural Style
®
NTGRX-4S-IR-__-__
4-Scene with Off and IR Receiver
Wallstation
Description
• Allows user to select scenes at the Wallstation
or by Wireless Remote Control.
• Scene selection functionality can be selected in
the field.
• Status LEDs indicate which scene is selected.
• Off button turns all lights off.
• Infrared receiver allows infrared transmitters to
select scenes and raise/lower lighting zones.
• Raise/lower button on GRX-IT and GRX-8IT
Wireless Remote Controls brightens or dims
all lighting in the selected scene.
• Works with GRAFIK Eye 3000 and 4000 Series
Control Units.
• Selects scenes in just one Control Unit or a
group of up to eight Control Units.
Finish and Engraving Options
• Available with engraving to meet specific project
needs.
• Available in a “no-insert” version for a sleeker
look.
LEDs
Off
Infrared
receiver
Scene
selection
buttons
Insert
Color and Finish Codes
Field Selected Functionality
Scene selection buttons and
GRX-IT 4-Scene Wireless
Remote Control activates:
Scenes 1 to 4
Scenes 5 to 8
Scenes 9 to 12
Scenes 13 to 16
GRX-IT 8-Scene Wireless
Remote Control activates:
Scenes 1 to 8
Scenes 5 to 12
Scenes 9 to 16
Scenes 13 to 16/1 to 4
DIP Switch Settings
5 6
5
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
ntgrxwstns-6 12.12.03
Wallstations
Architectural Style
®
NTGRX-SI4S-IR-__-__
Switch Interface, 4-Scene with Off,
and IR Receiver Wallstation
Description
• Ideal for partitionable spaces. Allows user to
access different sets of scenes depending on
whether partition wall is open or closed.
• Terminals on the back of the Wallstation
connect to a contact closure such as a
switch on a movable wall.
• Scene selection functionality can be selected
in the field.
• Occupants can also select scenes using a
GRX-IT Wireless Remote Control.
• Status LEDs indicate which scene is selected.
• Off button turns all lights off.
• Raise/lower button on GRX-IT Wireless
Remote Control brightens or dims all
lighting in the selected scene.
• Works with GRAFIK Eye 3000 and 4000
Series Control Units.
• Selects scenes in just one Control Unit or a
group of up to eight Control Units. (Locate the
Control Units away from the usable space so
occupants must control lighting from the
Wallstation.)
Contact Closure Specifications
• Maintained dry contact closure only - 15mA
minimum.
• Terminals accept one #18 AWG (1.0mm
2
)
standard wire.
Finish and Engraving Options
• Available with engraving to meet specific
project needs.
• Available in a “no-insert” version for a sleeker
look.
LEDs
Off
Infrared receiver
Scene
selection
buttons
Insert
1234567
4
3
2
1
Com
N/O
Color and Finish Codes
DIP Switches
Terminals to contact
closure:
Com: Common
N/O: Normally Open
To low-voltage
contact closures
by Lutron (NT-PS,
IR-PS) or others
Field Selected Functionality
DIP Switch
Settings
5 6
When contact is OPEN,
scene selection buttons
and GRX-IT select:
When contact is CLOSED,
scene selection buttons and
GRX-IT select:
Scenes 1 to 4
Scenes 9 to 12
Scenes 5 to 8
Scenes 1 to 4
Scenes 13 to 16
Scenes 9 to 12
Scenes 1 to 4
Scenes 9 to 12
6
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
ntgrxwstns-7 12.12.03
Wallstations
Architectural Style
®
NTGRX-4PS-__-__
4-Partition Status Wallstation
LEDs
For wall open,
Control Units work
in combination.
For wall closed,
Control Units work
independently.
Toggle buttons
Reset
Description
• Coordinates lighting for up to four movable walls
(five rooms). Each toggle button is set up to
operate the Control Units associated with a
movable wall.
• When the wall is open to make one large space,
the user presses the wall’s toggle button to
make the LED light up. The GRAFIK Eye Control
Units assigned to the buttons now work “in
combination.” Scene changes at one Control
Unit occur on all of these Control Units.
• When the wall is closed to make several smaller
spaces, the user presses the wall’s toggle
button to turn off the LED. The Control Units
now work independently.
• The bottom button resets all Control Units to
independent operation.
• The example shows how to use the Wallstation
for a space with four movable walls.
Color and Finish Codes
1
ABCDE
Movable Wall
Movable Wall
23
Movable Wall
Movable Wall
4
Example
Button:
Button 1
Button 2
Button 3
Button 4
Wall:
Wall 1
Wall 2
Wall 3
Wall 4
Combine
Control Units:
A and B
B and C
C and D
D and E
7
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
ntgrxwstns-8 12.12.03
Wallstations
Architectural Style
®
NTGRX-4M-__-___
4-Button Master Wallstation
Description
• Allows user to control several different areas of
GRAFIK Eye lighting from one master location.
• Each button can operate a different GRAFIK Eye
Control Unit or group of Control Units.
• Four buttons toggle their associated Control Units
on (to Scene 1) and off.
• Status LEDs indicate which Control Units are on.
• The bottom button either turns all associated
Control Units on (to scene 1) or off, depending on
settings of DIP switches 5 and 6.
• In a home, a Master Wallstation might be placed
inside the main entry. The first button would turn
on foyer lights, the second button would light a
path to the kitchen, etc.
• The Master Wallstation can work with a total of
eight GRAFIK Eye 3000 or 4000 Series Control
Units. The Control Units may be assigned to
buttons in any combination.
Finish and Engraving Options
• Available with engraving to meet specific project
needs.
• Available in a “no-insert” version for a sleeker look.
LEDs
On (to scene1)
or off
Insert
Toggle buttons
Color and Finish Codes
Field Selected Functionality
Bottom button:
DIP Switch Settings
5 6
Turns all associated
Control Units on to
Scene 1.
Turns all associated
Control Units off.
8
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
ntgrxwstns-9 12.12.03
Wallstations
Architectural Style
®
2 3/4"
(70mm)
5/16"
(8mm)
1 3/8"
(35mm)
4 9/16"
(116mm)
1234567
4
3
2
1
Color and Finish Codes
Matte Finishes
Standard – Ship in 48 hours
White WH
Ivory IV
Beige BE
Gray GR
Brown BR
Black BL
Metal Finishes
Ship in 4 to 6 weeks
Bright Brass BB
Bright Chrome BC
Bright Nickel BN
Satin Brass SB
Satin Chrome SC
Satin Nickel SN
Antique Brass QB
Antique Bronze QZ
Anodized Aluminum Finishes
Ship in 4 to 6 weeks
Clear CLA
Black BLA
Brass BRA
Engraving E
No Insert NI
Also available:
-Custom Controls
-Color Matching
Ship in 4 to 6 weeks. Pricing
may vary depending on finishes.
Dimensions
Front View
Mounting
Power
Low-voltage type Class 2 (PELV).
Operating voltage: 12/24 V Direct Current.
Key Design Features
• Meets IEC 801-2. Tested to withstand 15kV
electro-static discharge without damage or
memory loss.
• Faceplate snaps on with no visible means of
attachment.
• Can be ganged to share a common faceplate
with NovaT*
® and Vareo® Dimmers. Counts as
a “small control” for ganging.
System Communications and Capacity
• Low-voltage type Class 2 (PELV) wiring
connects Wallstations to Control Units
and other components.
• Up to 8 Control Units and up to 16 total
Wallstations and/or Control Interfaces may
be linked for a total of 24 control points.
Terminals
Accept up to two #18 AWG (1.0mm
2
) typical.
Environment
32-104°F (0-40°C). Relative humidity less
than 90% non-condensing.
Side View
Back View
DIP Switches
1-4 used to set
address
5-7 used to
select function
Terminals for
Class 2
(PELV) wiring
Class 2 (PELV)
wiring
1-Gang U.S.
Wallbox
Faceplate
Specifications
9
DIP Switch Settings
Address
1234
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Reserved for GRX-PRG, if present on link.
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
ntgrxwstns-10 12.12.03
Wallstations
Architectural Style
®
DIP Switches
• Set DIP switches 1-4 to give the
Wallstation a unique system address
from 1 to 16.
• Set additional DIP switches (if any) to
specify function as shown on the first
page of the Wallstation’s Specification
Submittal.
123456
4
3
2
1
Wallstation Rear View
D: Drain/Shield
(2) #12 AWG
(2.5mm
2
)
(1) #18 AWG
(1.0mm
2
)
(2) #12 AWG
(2.5mm
2
)
Class 2/PELV
Control Wiring
1: Common
2: 24VFW
Wallstation Installation
Low-Voltage Class 2 (PELV) Wiring
• Use low-voltage Class 2 (PELV) wiring to daisy-chain
Wallstations to Control Units and other components.
• Make connections inside the wallbox or in a switch/junction
box with a maximum wire length of 8 feet (2.5m) from the link
to the Wallstation.
Note: EGRX Wallstations have a “D” terminal for Drain.
Connect the Drain/Shield at this terminal.
When used with GRAFIK Eye 3000 Control Units:
• Two #18 AWG (1.0mm
2
) conductors for common (terminal 1)
and 12 V Direct Current (terminal 2). Ensure that the terminal 2
connection is wired correctly. Refer to GRX-3000 Specification
Submittal.
• One shielded, twisted pair #18 AWG (1.0mm
2
) for data link
(terminals 3 and 4).
When used with GRAFIK Eye 4000 Control Units:
• Two #12 AWG (2.5mm
2
) conductors for common (terminal 1)
and 24 V Direct Current (terminal 2). These won’t fit in
terminals. Connect as shown.
• One shielded, twisted pair #18 AWG (1.0mm
2
) for data link
(terminals 3 and 4).
• Connect Drain/Shield as shown. Do not connect to Ground
(Earth) or Wallstation. Connect the bare drain wires and cut off
the outside shield.
Data Link
(1) Shielded, twisted
pair #18 AWG (1.0mm
2
)
3: MUX
4: MUX
10