SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems EM-A-CMP Centralized Lighting Control System
369-507a 1 10.26.11
eLumenTM Manager: Servers
The server-based eLumenTM Manager is a dedicated
server for a Lutron® GRAFIK 5000TM, through GRAFIK
7000TM centralized lighting control systems (CLCS). It is
used to support system operation 24/7. This eLumenTM
Manager is required for storage of data, for lighting
zone controller (LZC) systems, and to run PictureITTM
software. This eLumenTM Manager allows the following
operations:
•Centralized,real-timesetupandcontrol
•Interfacingtoremoteclients(upto50additionalper
server; see the Specification Submittal for eLumen
TM
Manager: Desktop and Laptop Models)
•Upto3concurrentclientusers
•Upto10concurrentPictureIT
TM users
•ConnectiontoaLANfromitsRJ-45networkjackand
to the rest of the system through one of its network
connections
Note: The server must run at all times for proper
operation of the system
Available Models
•EM-A-CMP-S-O: Standard server
•EM-A-CMP-S-T: Standard server with telephone interface
•EM-A-CMP-R-O:Server with RAID
•EM-A-CMP-R-T: Server with RAID and telephone interface
• EM-A-CMP-R-T-K: RAID Rack mount with telephone interface
• EM-A-CMP-R-0-K:RAID Rack mount
• EM-A-CMP-S-T-K: SCSI Rack mount with telephone interface
• EM-A-CMP-S-0-K:SCSI Rack mount
•EM-A-CMP-R-T-C: RAID Rack mount with telephone
interface and console
• EM-A-CMP-R-0-C RAID Rack mount with console
•EM-A-CMP-S-T-C: SCSI Rack mount with telephone
interface and console
• EM-A-CMP-S-0-C:SCSI Rack mount with console
•Serverswithtelephoneinterface(-T-models)allow
control of some functions via an analog phone line
•ServerswithRAID(-R-models)useanarrayofthreeor
more hard drives to prevent loss of data
Capability
This eLumen
TM Manager can control the largest
GRAFIK 5000
TM, through GRAFIK 7000TM centralized
lighting control systems, including those with more than
16,000lightingzonesandmultipleconcurrentusers.
Power
•Operatingvoltage:115V~at60Hz
•Serverrequiresatleastfourpowerreceptacles
•PowershouldbethroughaLutron-supplied
uninterruptiblepowersource(UPS)ratedforat
least1500VA
Hardware
•CPU:Intel
®
1
Xeon®
1
Processor
—ServerswithRAID:3.0GHzmin.
—ServerswithoutRAID:2.8GHzmin.
•Memory:1GBRAM.
•Monitor:Color17inchwith1024x768resolution
•Diskspace:36GBmin.with10XRPMSCSI
•Motherboard:integrated10/100Ethernetcard
•48xCDRW/DVD-ROMdrive
•RS232serialport
•US-101keyboard
•PCIEthernet
2
dual-port100Base-TNIC
•2-buttonmousewithscrollwheel
•Phonelineportwithinterfacecard
(telephone interface models only)
Software
•USWindows
®
3
32-bitserveroperatingsystem
Windows®
3
2003orWindows®
3
2008,withSP1
•Microsoft.NETFramework2.0
•LutronDesignITTM (also available separately for use
with a customer-supplied server; consult Lutron
factory representative)
•SecureITTM
•ScheduleITTM
•CongureITTM
•ControlITTM(Optional)
•PictureITTM(Optional)
1 IntelandXeonareregisteredtrademarksofIntelCorporationin
theUnitedStatesandothercountries
2 TheLutrondedicatedEthernetportmustbeconnectedonlyto
the GRAFIK
TM Centralized Lighting Control System
3 WindowsisaregisteredtrademarkofMicrosoftCorporationin
theUnitedStatesandothercountries
NOTICE: The warranty will be voided if unapproved
software additions or upgrades are made to this server.
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems EM-A-CMP Centralized Lighting Control System
369-507a 2 10.26.11
System Communications
•Networkconnectionprovidesdualspeedcapabilityat
10Mbit/secor100Mbit/secaccessedbyamultiple
redundantRJ45connector
•ConnectstotheGRAFIKCentralizedLightingControl
System through one of its network connectors through
anetworkinterface(EM-A-NWK-E-D-x)ordirectly
Environment
•Operatingtemperature:50°Fto75°F(10°Cto24°C)
•Storagetemperature:0°Fto120°F(-17°Cto48°C)
•Relativehumidity:8%to80%noncondensing
•Mustbeinstalledinalockable,temperature-controlled
environmenttomaintainthe1-yearwarranty
Dimensions
•HxWxD:17.3x8.58x20.5in(440x218x521mm)
•Weight:51.8lbs(23.5kg)
Monitor Specifications
•17inchLCD
•1024x768minimumresolution
•HxWxD:16.2x14.3x16.4in(409x363x417mm)
•Weight:34.17lbs(15.5kg)
Delivery
•Shipsin4-6weeksfromtimeofrelease
UPS Specifications
•Capacity:1500VA
•OutputWaveform:Sinewave
•Features:Hot-swappable(user-replaceable)batteries,
IntelligentBatteryManagement,OverloadandReplace
BatteryIndicator,SmartSlot,Sitewiringfaultindicator,
AutomaticVoltageRegulation(AVR)
•HxWxD:6.2x5.4x14.1in(158x137x358mm)
•Weight:29lbs(13kg)
•AverageRunTime:18.6minutes(22W,halfload);
5.8minutes(450W,fullload)
•CompliantStandards:CSA,FCCA,UL1778
•DeviceType:UPS
•EnclosureColor:Black
•EnergyRating:320joules(surgeenergyrating)
•PowerProvided:450W
•Voltage:120V~
•InputConnector(s):1xNEMA5-15P
•CircuitProtection:Surgeprotectionandltering
•ClampingLevel:Zeroclampingresponsetime
•PowerOutputConnectorsDetails:4xNEMA5-15R
RAID Details (EM-A-CMP-R model only)
•UsesaRAID5arrayofthreeormoreharddrivesto
achieve transparent data redundancy. Drives are hot
swappable and easily removable in the event of a
single drive failure
Telephone Interface Details
(Telephone interference model only)
•Theintegratedtelephoneinterfaceallows:
Input from one analog phone line; must support
caller ID
— Voice-promptedremotetouch-toneoperation
Select intensity
Select scenes
— Enable/disablecontrolstationdevices
— Enable/disabletimeclocks
Select the state of system variables
Select the state of walls
Access restrictions by:
UserID
Passcode
Caller ID
•ThetelephoneinterfaceisdesignedforusewithPSTN
systemsandrequiresananalogPSTNlinetofunction
properly;itisnotdesignedforusewithPBXsystems
Network
connection to
GRAFIK centralized
lighting control
system
Telephone Line In
(where applicable)
To client network
Line voltage in
UPS
2