R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
eomx-3 7.28.04
Wallstations
European Style
GRAFIK Systems
EOMX-4S-__-__
6-Button Wallstation
Description
• Used to select and adjust scenes.
• Scene selection buttons activate scenes.
• Status LEDs indicate which scene is
selected.
• Off button turns all lights off.
• Master raise/lower button brightens or
dims all lighting in the selected scene.
• May be custom-configured for other
functions.
• Works with GRAFIK 5000/6000/7000
Systems.
• Mounts in UK/German wallbox. In the
U.S., Lutron supplies a UK wallbox
(P/N 241-683) with the Wallstation.
Finish and Engraving Options
• Available with custom engraving to meet
specific project needs.
• Green LEDs are standard. Amber LEDs
are optional.
Status LEDs
Scene
Selection
Buttons
Off
Master
Raise/Lower
Color and Finish Codes
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
eomx-7 7.28.04
Wallstations
European Style
GRAFIK Systems
1
234
5
6
1.4" (35mm)
2.4"
(60mm)
6mm
(1/4”)
25mm
(1”)
86mm
(3 3/8”)
86mm (3.38”)
Color and Finish Codes
Standard Finishes
Ship in 48 hours*
Black BL
White WH
Bright Brass BB
Bright Chrome BC
Satin Brass SB
Satin Chrome SC
Matte Finishes
Ship in 3 to 4 weeks
Ivory IV
Beige BE
Gray GR
Brown BR
Metal Finishes
Ship in 4 to 6 weeks
Bright Nickel BN
Satin Nickel SN
Antique Brass QB
Antique Bronze QZ
Anodized Aluminum Finishes
Ship in 4 to 6 weeks
Clear CLA
Black BLA
Brass BRA
Engraving E
Wallbox Included NA
Also available:
-Custom Controls
-Color matching
Ship in 4 to 6 weeks. Pricing
may vary depending on finish.
* 48 hours for 4S, 2B-SL, 4SIR-
8S, 8S-IR. All others – 2 weeks.
Dimensions
Front View
Mounting
Power
Low-voltage PELV (Class 2).
Operating voltage: 32 V Direct Current
Key Design Features
• Meets IEC 801-2. Tested to withstand 15kV
electro-static discharge without damage or
memory loss.
• Faceplate snaps on with no visible means of
attachment.
System Communications and Capacity
• Low-voltage type Class 2 (PELV) wiring
connects Wallstations to Processor Panel.
• Up to 32 Wallstations, Control Units, and/or
Control Interfaces may be connected per
Class 2 (PELV) wiring link.
Terminals
Accept up to two 1.0mm
2
(#18 AWG) wires
typical.
Environment
0-40°C (32-104°F). Relative humidity less
than 90% non-condensing.
Side View
Back View
Terminals for PELV
(Class 2) Wiring
UK or German wallbox.
Shipped with Wallstation in US (P/N 241-683)
DIP
Switches
Faceplate
Specifications
2
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
eomx-8 7.28.04
Wallstations
European Style
GRAFIK Systems
D3
4
21
2 # 18 AWG (1.0 mm
2
)
twisted, shielded pair
from terminals 3 to 3
and 4 to 4
#18 AWG (1.0 mm
2
)
2 #12 AWG (2.5 mm
2
)
Drain/Shield
Wallstation Installation
Low-voltage PELV (Class 2) Wiring
• Use low-voltage PELV (Class 2) wiring to daisy-chain Wallstations
to the Processor Panel.
• Make connections inside the wallbox or in a switch/junction box
with a maximum wire length of 8 feet (2.5m) from the link to the
Wallstation.
• Two #12 AWG (2.5mm
2
) conductors for common (terminal 1)
and 32VDC (terminal 2). These will not fit in terminals. Connect
as shown.
• One shielded, twisted pair #18 AWG (1.0mm
2
) for data link
(terminals 3 and 4).
• Connect Drain/Shield as shown. Do not connect to Ground
(Earth) or Wallstation. Connect the bare drain wires and cut off
the outside shield.
Note: Some Wallstations have a “D” terminal for Drain. The
Drain/Shield wire may be connected to this terminal.
Note: Use appropriate wire connecting
devices as specified by local codes.
3