SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems BMS InterfaceEM-A-BAC-ET-120
369-510a 6 10.26.11
BACnet® Protocol Implementation Conformance Statement (PICS)
Date: 31 May 2011
Vendor Name: Lutron Electronics Co., Inc.
Product Name: Centralized Lighting Control System BACnet® Integrator
Product Model Number: EM-A-BAC-IP-120, EM-A-BAC-ET-120
Applications Software Version: V6.06p (E) Firmware Revision: V5.22fA (K) BACnet® Protocol Revision: V2.01 bL
Product Description:
Both the EM-A-BAC-IP-120 and EM-A-BAC-ET-120 are gateway interfaces between a BACnet® Building Automation System
and the Lutron® GRAFIK Centralized Lighting Control System. The BACnet® gatateway exports a single BACnet® device with
objects that retrieve the status and perform actions through the Centralized Lighting Control System. The BACnet® gatateway
can interface with either the zones or the spaces dened in a GRAFIK Centralized Lighting Control System. Both zone control
and space control are not possible through the same device. If congured to interface with zones on the GRAFIK Centralized
Lighting Control System, the interface is able to retrieve the relay status and current intensity and set a desired intensity for
each zone in the system. If congured to interface with spaces on the GRAFIK Centralized Lighting Control System, the
interface is able to retrieve the last scene set in the space. The space is controlled by selecting a desired scene. A processor
can only move one EM-A-BAC-IP-120 or EM-A-BAC-ET-120 gateway interface.
BACnet® Interoperability Building Blocks Supported (Annex K):
K.1.1 BIBB - Data Sharing - ReadProperty-B (DS-RP-B)
K.1.3 BIBB - Data Sharing - ReadPropertyMultiple-A (DS-RPM-A)
K.1.4 BIBB - Data Sharing - ReadPropertyMultiple-B (DS-RPM-B)
K.1.8 BIBB - Data Sharing - WriteProperty-B (DS-WP-B)
K.1.9 BIBB - Data Sharing - ReadPropertyMultiple-A (DS-WPM-A)
K.1.10 BIBB - Data Sharing - ReadPropertyMultiple-B (DS-WPM-B)
K.5.2 BIBB - Device Management - Dynamic Device Binding-B (DM-DDB-B)
BACnet® Standardized Device Profile (Annex L):
BACnet® Smart Sensor (B-SS)
BACnet® Smart Actuator (B-SA)
Segmentation Capability:
Segmented requests supported? No Window Size n/a
Segmented responses suppored? No Window Size n/a
Non-Standard Application Services:
The EM-A-BAC-IP-120 does not support non-standard application services.
Standard Object Types Supported:
Device
Analog Input/Output
Binary Input/Output
Multistate Output
Binary Variable
Analog Variable
Data Link Layer Options:
BACnet® Ethernet, (Annex J)
Device Address Binding:
Is static device binding supported? No
If this product is a communication gateway, describe the types of non-BACnet® equipment/network(s) that the
gateway supports:
Both the EM-A-BAC-IP-120 and EM-A-BAC-ET-120 are gateway interfaces between a BACnet® protocol and the Lutron
Centralized Lighting Control System communication protocol.