SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Compact Fluorescent Ballasts Digital Dimming Ballasts
369339h 1 03.06.18
EcoSystem Digital Ballasts
EcoSystem compact ballasts provide high-performance
dimming for any compact fluorescent application,
including within an EcoSystem Lighting Control System.
EcoSystem compact ballasts offer 100%
to 5% dimming, providing both energy savings and
lighting flexibility.
Features
•Continuous,icker-freedimmingfrom100%to5%
•CompatiblewithEnergi Savr Node with EcoSystem
devices, GRAFIK Eye QS with EcoSystem connection,
PowPakdimmingmodulewithEcoSystem connection,
and Quantum systems, allowing for integration into an
existing/planned EcoSystem lighting control system
•Supportsstandard3-wireline-voltagephasecontrol
technology.
•Programmedrapidstartdesignensuresfull-ratedlamp
life while dimming and cycling.
•Lampsturnontoanydimmedlevelwithoutashingto
full brightness.
•Lowharmonicdistortionthroughouttheentire
dimming range.
•Frequencyofoperationensuresthatballastdoesnot
interfere with infrared devices.
•Inrushcurrentlimitingcircuitryeliminatescircuitbreaker
tripping, switch arcing, and relay failure.
•Ultra-quietoperation.
•Protectedfrommiswiresofanyinputpowertocontrol
lead, or from lamp leads to each other and/or ground.
•End-of-lamp-lifeprotectioncircuitryensuressafe
operation throughout entire lamp life
•Nonvolatilememoryrestoresallballastsettingsafter
power failure
•100%compatiblewithallLutron3-wireuorescent
controls and EcoSystem digital controls.
•100%performancetestedatfactory.
•Customballastfactorsavailable.
Design tool and specifications can be found at
www.lutron.com/ballasttool
•BAA-compliant(BuyAmericanAct)modelnumbers
available.Adda"U"prextothemodelnumber.
EcoSystem ballast, case type K
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Compact Fluorescent Ballasts Digital Dimming Ballasts
369339h 2 03.06.18
Specifications
Regulatory Approvals
•ULListed(evaluatedtotherequirementsofUL935)
•ULType1Outdoorfordamplocations
•CSACertied(evaluatedtotherequirementsofC22.2
No.74)
•ClassPthermallyprotected
•MeetsANSIC82.11HighFrequencyBallastStandard
•ThisdevicecomplieswithPart18(Non-Consumer
Limits)oftheFCCRules.Operationissubjecttothe
following conditions:
(1)Thisdevicemaycauseinterferencetoradio
equipment.
(2)Thisdeviceshouldnotbeinstallednearmaritime
safetycommunicationsequipmentorothercritical
navigationorcommunicationequipmentoperating
between0.45–30MHz.
ModicationnotexpresslyapprovedbyLutron
Electronics Co., Inc. could void the users authority to
operatethisequipment.
ThisNon-ConsumerRFLDcomplieswiththeCanadian
standard ICES-005.
•MeetsANSIC62.41CategoryAsurgeprotection
standardsuptoandincluding4kV
•ManufacturingfacilitiesemployESDreduction
practicesthatcomplywiththerequirementsof
ANSI/ESDS20.20
•LutronQualitySystemsregisteredto
ISO9001.2008
Environment
•Minimumlampstartingtemperature:50°F(10°C)
•Relativehumidity:lessthan90%non-condensing
•SoundRating:ClassA
•Maximumballastcasetemperature:167°F(75°C)
Lamp Seasoning
Refer to lamp manufacturer for lamp seasoning
requirementspriortodimming
Performance
•OperatingVoltage:120V~,220/240V~,277V~
at50or60Hz
•Grounding:ballastandxturemustbegroundedfor
proper dimming
•DimmingRange:100%to5%measuredrelative
light output
•LampStarting:programmedrapidstart
•LampCurrentCrestFactor:lessthan1.7
•LightOutputVariation:Constant±2%lightoutput
forlinevoltagevariationsof±10%
•LampLife:Averagelamplifemeetsorexceeds
specified lamp ratings
•PowerFactor:0.95minimum
•TotalHarmonicDistortion(THD):Lessthan10%
•Inaudibleina27dBAambient
•MaximumInrushCurrent:3Aperballastat277V~,
7Aperballastat120V~
•Standbypower:Lessthan1W
Ballast Wiring & Mounting
•Ballastisgroundedbythespeciedterminalorbya
mounting screw to the fixture
•Terminalblocksontheballastacceptthefollowing
wire gauges:
–PowerWiringandEcoSystemBus:one18AWGor
16AWG(0.75mm
2
or 1.5 mm
2
)solidperterminal
–LampWiring:one18AWGor16AWG(0.75mm
2
or 1.5 mm
2
)solidperterminal
•Ballastmountsusingtwomountingtabsorstuds
within a fluorescent fixture
•Wiringfromtheballasttolampsocketsshallnot
exceed3ft(0.9m)forT4compactlamps
•Ballastdoesnothavesensorterminals
Warranty
5-year limited warranty with Lutron field service
commissioning(3-yearstandardwarranty)fromdate
ofpurchase.ForadditionalWarrantyinformation,
please visit
www.lutron.com/TechnicalDocumentLibrary/
Ballast%20and%20Driver%20Warranty.pdf
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Compact Fluorescent Ballasts Digital Dimming Ballasts
369339h 3 03.06.18
EcoSystem Compact Fluorescent Ballast Models
Lamp
Type
Lamp
Watts
No. of
Lamps
Model Case
Size
Input
Voltage
(V~)
Input
Current
(A)
Input
Power
(W)
Ballast
Factor
(BF)
System
Lumens
(lm)
System
Efficacy
(lm/W)
Ballast
Efficacy
Factor
Relative
Efficacy
(RSE)
T44-Pin
Quad-
Tubeor
Triple-
Tube
18W 1 EC3DT418KU1S
(Studded)
EC3DT418KU1
(Non-studded)
K 120 0.18 21.3 0.95 1140 53.5 4.46 0.80
K 220 0.10 21.1 0.95 114 0 54.0 4.50 0.81
K 240 0.09 21.4 0.95 114 0 53.3 4.44 0.80
K 277 0.08 20.8 0.95 114 0 54.8 4.57 0.82
2 EC3DT418KU2S
(Studded)
EC3DT418KU2
(Non-studded)
K 120 0.34 41.1 0.95 2280 55.5 2.31 0.83
K 220 0.18 39.6 0.95 2280 57. 6 2.40 0.86
K 240 0.17 39.4 0.95 2280 57.9 2.41 0.87
K 277 0 .15 39.9 0.95
2280 57.1 2.38 0.86
26W 1 EC3DT4MWKU1S
(Studded)
EC3DT4MWKU1
(Non-studded)
K 120 0.22 26.4 0.95 1710 64.8 3.60 0.94
K 220 0.12 26.8 0.95 1710 63.9 3.55 0.92
K 240 0.11 26.9 0.95 1710 63.7 3.54 0.92
K 277 0 .10 27.0 0.95 1710 63.4 3.52 0.92
2
EC3DT4MWKU2S
(Studded)
EC3DT4MWKU2
(Non-studded)
K 120 0.43 51.6 0.95 3420 66.3 1.84 0.96
K 220 0.23 49.9 0.95 3420 68.5 1.90 0.99
K 240 0.21 50.6 0.95 3420 6 7. 5 1.88 0.98
K 277 0 .19 51.4 0.95 3420 66.6 1.85 0.96
T44-Pin
Triple-
Tube
32W 1 EC3DT4MWKU1S
(Studded)
EC3DT4MWKU1
(Non-studded)
K 120 0.29 34.8 0.95 2280 65.5 2.73 0.87
K 220 0.15 33.0 0.95 2280 6 9.1 2.88 0.92
K 240 0.14 33.6 0.95 2280 6 7. 9 2.83 0.90
K 277 0 .12 33.2 0.95 2280 68.6 2.86 0.91
2
EC3DT4MWKU2S
(Studded)
EC3DT4MWKU2
(Non-studded)
K 120 0.55 66.0 0.95 4560 69.1 1.44 0.92
K 220 0.29 64.5 0.95 4560 70.7 1.47 0.94
K 240 0.26 63.0 0.95 4560 72.3 1.51 0.96
K 277 0.24 65.5 0.95 4560 69.7 1.45 0.93
42W 1 EC3DT4 42KU1S
(Studded)
EC 3DT442KU1
(Non-studded)
K 120 0.36 43.2 0.95 3040 70.4 2.20 0.92
K 220 0.20 42.9 0.95 3040 70.8 2.21 0.93
K 240 0.18 42.7 0.95 3040 71.2 2.23 0.93
K 277 0 .15 42.6 0.95 3040 71.3 2.23 0.94
2
EC 3DT442KU2S
(Studded)
EC 3DT442KU2
(Non-studded)
K 120 0.73 8 7.6 0.95 6080 69.4 1.08 0.91
K 220 0.39 85.9 0.95 6080 70.8 1.11 0.93
K 240 0.35 8 5.1 0.95 6080 71.5 1.12 0.94
K 277 0.31 85.4 0.95 6080 71.2 1.11 0.93
NOTE:The"S"attheendoftheballastmodelnumberindicatesastuddedoption.Removethe"S"foranon-studdedballast.
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Compact Fluorescent Ballasts Digital Dimming Ballasts
369339h 4 03.06.18
EcoSystem Compact Fluorescent Ballast Case Dimensions
A 4.20in(107mm)
B 1.00in(25mm)
C 3.00in(76mm)
D 4.90in(124mm)
E 4.60in(117mm)
(mountingcenters)
F 1.42in(36mm)
G 1.99in(51mm)
H 1.09in(28mm)
I 2.00in(51mm)
J 1.60in(41mm)
A
C
E
D
B
F
G
H
I
J
A
C
E
D
B
F
G
Studded
Non-studded
A 4.20in(107mm)
B 1.00in(25mm)
C 3.00in(76mm)
D 4.90in(124mm)
E 4.60in(117mm)
(mountingcenters)
F 1.42in(36mm)
G 1.99in(51mm)
NOTE: Studded version does not have side connectors.
8-32ThreadedStud
0.29in(0.736mm)
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Compact Fluorescent Ballasts Digital Dimming Ballasts
369339h 5 03.06.18
Lamp Wiring Diagrams
EcoSystem Power Wiring Diagrams
1
Ballastisgroundedviathecaseorterminal.
2
WirecolorsshownareforLutroncontrolsandballastsonly.Dimmingcontrolwiresmaynotmatchballastwirecolors.
3
TheConstantHotmustnotbewiredtoaswitchingdevice.
Note: ForT4compactlamps,maximumlamp-to-ballastwirelengthis3ft(0.9m)toguaranteeproperperformance.
One Compact Fluorescent Lamp
Two Compact Fluorescent Lamps
EcoSystem
Compact
Ballast
EcoSystem
Compact
Ballast
EcoSystem
®
Compact
Ballast
4-pin
Lamp
Holder
Red
Blue
Red
Blue
Red
Blue
Yellow
Yellow
Red
Blue
Ground
1
Ground
1
Ground
1
Ground
1
Neutral
Black(ConstantHot)
2,3
E1
E2
4-pin
Lamp
Holder
4-pin
Lamp
Holder
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Compact Fluorescent Ballasts Digital Dimming Ballasts
369339h 6 03.06.18
EcoSystem Bus Wiring Diagrams
EcoSystem Digital Link Overview
•TheEcoSystemDigitalLinkwiring(E1andE2)connects
the digital ballasts and drivers together to form a lighting
control system.
•EachEcoSystemDigitalLinksupportsupto64digital
ballastsorLEDdrivers,64occupantsensors,
16daylightsensors,and64wallstationsorIRreceivers.*
•SensorsdonotdirectlyconnecttoEcoSystemH-Series
ballasts.
•No3-wirephasecontrolwithEcoSystemH-Series
ballasts.
•E1andE2(EcoSystemdigitallinkwires)arepolarity
insensitive and can be wired in any topology.
•AnEnergiSavrNodewithEcoSystemunit,GRAFIKEye
QS control unit with EcoSystem, or Quantum system
providespowerfortheEcoSystemDigitalLinkand
supports system programming.
•AllEcoSystemDigitalLinkprogrammingiscompletedby
using the Energi Savr App for an Apple iPad or iPhone
mobile digital devices, GRAFIK Eye QS with EcoSystem,
PowPak dimming module with
EcoSystem, or Quantum System.
•Forcompleteinformation,seetheEcoSystem Design
& Application Guide
(P/N367-1533)at
www.lutron.com.
EcoSystem Digital Link Wiring
•BallastEcoSystemDigitalLinkterminalsonlyacceptone
18AWGor16AWG(0.75mm
2
or 1.5 mm
2
)solidcopper
wire per terminal.
•MakesurethatthesupplybreakertotheDigitalBallast
andEcoSystemDigitalLinkSupplyisOFFwhenwiring.
•ConnectthetwoconductorstothetwoDigitalBallast
terminalsE1andE2asshown.
•UsingtwodifferentcolorsforE1andE2willreduce
confusion when wiring several ballasts together.
•TheEcoSystemDigitalLinkmaybewiredClass1or
Class2.Consultapplicableelectricalcodesforproper
wiring practices.
* PowPakdimmingmodulewithEcoSystemcansupport32ballasts
or LED drivers.
TotheEcoSystem DigitalLink Supply
Notes
•TheEcoSystemDigitalLinkSupplydoesnothaveto
belocatedattheendoftheDigitalLink.
•EcoSystemDigitalLinklengthislimitedbythewire
gaugeusedforE1andE2asfollows:
Wire Gauge Digital Link Length
(max)
12AWG 2200ft
14AWG 1400 ft
16AWG 900ft
18AWG 550 ft
Wire Size Digital Link Length
(max)
4.0 mm
2
828m
2.5mm
2
517 m
1.5 mm
2
310m
1.0 mm
2
207m
0.75 mm
2
155 m
BallastTerminals
BallastTerminals
GRD
NEU
DH
SH
E1
E2
LINE
Class 2
Bus
GRD
NEU
DH
SH
E1
E2
LINE
Class 2
Bus
Apple,iPad,andiPhoneareregisteredtrademarksofAppleInc.
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Compact Fluorescent Ballasts Digital Dimming Ballasts
369339h 7 03.06.18
EcoSystem Ballast Wiring:
Line Voltage Dimmers
EcoSystem Ballasts and 3-wire dimmers
•Lutron3-wiredimmersonlycontroltheballaststhey
are wired to; EcoSystem ballasts do not support
groupingof3-wirecontrolinput.
3-Wire Control Wiring
•MakesurethatthesupplybreakertotheDigital
BallastisOFFwhenwiring.
•Wireasshown
Line input Connects to
Hot DimmerBlackWire
Neutral DimmerWhiteWire
Dimmer wire Connects to
Yellow BallastOrange(DH)
Red BallastBlack(SH)
White BallastWhite(NEU)
Green EarthGround(GND)
•EcoSystemballastlinevoltageand3-wireinput
terminalsonlyacceptone18AWG(0.75mm
2
)or
16AWG(1.5mm
2
)solidwire.
Emergency and 3-wire
•EcoSystemballastscontrolledbyawallboxdimmer
should not be used for emergency/egress lighting
unless an external emergency ballast is used in the
fixture. See Lutron App Note #50 at
www.lutron.com.
•EcoSystemballastsmaybeusedforemergency/
egress lighting when controlled by a Lutron dimming
panel(GP);wherethepanelisadedicated
emergency panel.
Notice
3-Wirecontrolturnsoffdigitalballastswhenthe
control is in the off position.
LUTRON
GRD
NEU
DH
SH
E1
E2
LINE
Cla ss 2
Bus
GRD
NEU
DH
SH
E1
E2
LINE
Cla ss 2
Bus
3-WireDimmer
Black
White
Ground
1
Ground
1
1
Ballastisgroundedviathecaseorterminal
Ground
1
Green
1
White
Orange
Black
Green
1
Yellow
Hot
Neutral
Red
7
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Compact Fluorescent Ballasts Digital Dimming Ballasts
369339h 8 03.06.18
ATTENTION ELECTRICIANS
AND CONTRACTORS
Ballast/Socket Leads
Leadlengthsfromballasttosocketmustnotexceed
7ft(2m)forT8,T5,andT5HOlinearlamps.
Lamp Sockets
LampsocketsasperIEC60400arerequiredto
ensurepositivelamp-pintosocketcontact.
Lamp Mounting
Manyuorescentlampsocketsareavailablewith
mounting slots to vary the height of the lamp away
fromthegroundedmetalsurface.Havinga
fluorescent lamp too close to the grounded metal will
reducelamplife.Havingauorescentlamptoofar
awayfromthegroundedmetalwillmakethelamp
ickerornotturnonatall.Pleasenotethatallofthe
lamp heights are measured between the grounded
metal surface and the glass wall of the lamp.
Mounting for T4 Lamps
Do not allow lamp glass to come in direct contact with
any grounded metal surface.
Ballast Operating Temperature
Ballastcasetemperaturemustnotexceed167°F
(75°C) at any point on ballast.
Cold Air Flow
Ensurethatnocoldair(fromHVACsystem,etc)is
blowing across the lamps. Cooling the lamp will cause
performanceissuesasnotedinNEMALSD-34.
Wiring and Grounding
Ballastandlightingxturemustbeeffectively
grounded.Ballastsmustbeinstalledpernationaland
local electrical codes.
IMPOR
TANT: Lamps must never touch ground
plane and should be placed without obstruction.
Lamp
Lamp Socket
(side view)
Mounting height
Grounded
metal
Ballast
ATTENTION
FACILITIES MANAGERS
PERFORMANCE
Lamp Seasoning
Consult lamp manufacturer’s recommendations on
lamp seasoning prior to dimming.
SERVICE
Replacement Parts
UsereplacementpartswithexactLutronmodel
numbers.ConsultLutronifyouhaveanyquestions.
Further Information
For further information, please visit us at
www.lutron.com/ballasts or contact Lutron Customer
Assistanceat1-844.LUTRON1.
)Lutron,Lutron,Quantum,GRAFIKEye,PowPak,andEcoSystemare
trademarksofLutronElectronicsCo.,Inc.,registeredintheU.S.and
other countries.
EnergiSavrNodeisatrademarkofLutronElectronicsCo.,Inc.
Apple,iPad,andiPhoneareregisteredtrademarksofAppleInc.
8