SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Cable Low-Voltage Cables
369385c 1 01.22.2018
EcoSystem Cable
Custom designed cable, for use with EcoSystem
components, improves system performance and
decreases installation time. Cable is available for sensor
connections and EcoSystem bus connections. Both
types are available in plenum versions.
Features
Internal conductors match EcoSystem device terminal
and lead color scheme.
Each conductor sized for direct connection to
EcoSystem ballast and module terminals.
Three types of EcoSystem bus cable:
- Non-plenum bus cable (CL3R), for Class 2 applications
- Non-plenum bus cable (TC), for Class 1 applications
-
Plenum bus cable (CL3P) for plenum Class 2 applications
Two types of EcoSystem Class 2 sensor cable:
- Non-plenum sensor cable (CL3)
- Plenum sensor cable (CL3P)
All plenum cable is rated to a maximum of 300V.
Non-plenum cable is rated to a maximum of 300V or
600V dependant upon application.
Each offering is spooled to 1000 ft (305 m) and based
upon industry standards of ±10% on all shipments.
EcoSystem Class 2 Sensor Cable
C-CBL-522S-WH-1 (non plenum)
C-PCBL-522S-CL-1 (plenum)
EcoSystem Bus Cable
C-CBL-216-GR-1 (non-plenum, Class 2)
C-CBL-216-WH-C1 (non-plenum, Class 1)
C-PCBL-216-CL-1 (plenum, Class 2)
Lutron, )Lutron, and EcoSystem are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries.
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Cable Low-Voltage Cables
369385c 2 01.22.2018
EcoSystem Bus Cable Specifications
C-PCBL-216-CL-1
General Description
Two conductor EcoSystem bus cable for plenum spaces
16 AWG (1.5 mm
2
) solid bare copper, FEP insulated conductors
2 single conductors cabled
Clear 0.017 in (0.43 mm) thick FEP jacket — sheathed
All external markings use white ink
Electrical
Maximum operating voltage 300 V RMS CL3P
Maximum continuous current per conductor 10 A at 77 °F (25 °C)
Nominal conductor DC resistance 4 Ω/1000 ft (304.8 m) at 68 °F (20 °C)
Physical
Temperature Rating -94 °F to 392 °F (-70 °C to 200 °C)
Nominal Diameter 0.173 in (4.39 mm)
Maximum Pull Tension 45 lb (20.41 kg)
Minimum Bend Radius 1.75 in (44.5 mm)
Insulation Material FEP
Jacket Material FEP
Listings
UL listed as Type CL3P or CMP c(UL)us, FT-6
NFPA 262
UL444 and UL13
CSA-C22.2 No. 214
RoHS Compliant
Colors
Jacket — Clear (CL)
Conductor Color Ballast Terminal
Purple (PL) E1
Purple + white stripe (PL/WH) E2
Jacket Markings
LUTRON C-PCBL-216-CL-1 2/16 AWG (UL File #) (UL) CL3P or
CMP c(UL)us 200 °C FT-6 RoHS COMPLIANT
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Cable Low-Voltage Cables
369385c 3 01.22.2018
EcoSystem Bus Cable Specifications (continued)
C-CBL-216-GR-1
General Description
For running EcoSystem link with other Class 2 wires in non-plenum applications
16 AWG (1.5 mm
2
) solid bare copper, PVC insulated conductors
2 single conductors cabled
Gray 0.03 in (0.76 mm) thick PVC jacket — sheathed, UV stabilized
All external markings use black ink
Electrical
Maximum operating voltage 300 V RMS CL3R/CMG
600 V RMS AWM Style 20811
Maximum continuous current per conductor 13 A at 77 °F (25 °C)
Nominal conductor DC resistance 4 Ω/1000 ft (304.8 m) at 68 °F (20 °C)
Physical
Temperature Rating -4 °F to 221 °F (-20 °C to 105 °C)
Nominal Diameter 0.300 in (7.62 mm)
Maximum Pull Tension 62.5 lb (28.35 kg)
Minimum Bend Radius 1.75 in (44.5 mm)
Insulation Material PVC
Jacket Material PVC
Listings
UL Type CL3R
CMG (C)UL
FT-4 Flame Rating
AWM Style 20811
UL 1666 Vertical Shaft
RoHS Compliant
Colors
Jacket — Gray (GR)
Conductor Color Ballast Terminal
Purple (PL) E1
Purple + white stripe (PL/WH) E2
Jacket Markings
C-CBL-216-GR-1 LUTRON 2/16 AWG CL3R 90 °C (UL) E171202
or CMG c(UL)
or AWM STYLE 20811 105 °C 600 V DATE CODE FT-4 RoHS COMPLIANT
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Cable Low-Voltage Cables
369385c 4 01.22.2018
EcoSystem Bus Cable Specifications (continued)
C-CBL-216-WH-C1
General Description
For running EcoSystem link with other line-voltage wires (Class 1) in non-plenum applications
16 AWG (1.5 mm
2
) solid bare copper, PVC/Nylon insulated conductors
2 single conductors cabled
White 0.045 in (1.1 mm) thick PVC jacket — sheathed, UV stabilized
All external markings use black ink
Electrical
Maximum operating voltage 600 V RMS TC
600 V RMS UL STANDARD 62, TYPE TFN
Maximum continuous current per conductor 20 A at 77 °F (25 °C)
Nominal conductor DC resistance 4 Ω/1000 ft (304.8 m) at 68 °F (20 °C)
Physical
Temperature Rating -4 °F to 194 °F (-20 °C to 90 °C)
Nominal Diameter 0.299 in (7.59 mm)
Maximum Pull Tension 41 lb (18.6 kg)
Minimum Bend Radius 1.75 in (44.5 mm)
Insulation Material PVC and Nylon
Jacket Material PVC
Listings
UL Type TC Per UL Standard 1277 for tray cables
CSA Listed CIC C22.2 No. 239-09
UL Approved for Sunlight Resistance
Individual Conductors are rated TFN
Cable meets IEEE 383 & UL 1581 70,000 BTU/h Flame Test Requirements
Cable meets ICEA S-95-658, where applicable
FT-4 Flame Rating
RoHS Compliant
Colors
Jacket — White (WH)
Conductor Color Ballast Terminal
Purple (PL) E1
Purple + white stripe (PL/WH) E2
Jacket Markings
C-CBL-216-WH-C1 LUTRON (UL File #) 2/16 AWG 2C TFN (UL) TYPE C 600 V 90 °C DRY PVC JACKET SUN RES
or CSA LL226471 CIC (TC) FT-4 RoHS COMPLIANT
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Cable Low-Voltage Cables
369385c 5 01.22.2018
EcoSystem Class 2 Sensor Cable Specifications
C-PCBL-522S-CL-1
General Description
5 conductor EcoSystem sensor cable for plenum spaces
22 AWG (0.34 mm
2
) solid bare copper, FEP insulated conductors
Overall aluminum-polymer foil shield, plus 24 AWG (0.25 mm
2
) copper drain wire
Clear 0.012 in (0.3 mm) thick FEP jacket — sheathed
All external markings use white ink
Electrical
Maximum operating voltage 300V RMS CL3P
Maximum continuous current per conductor 4 A at 77 °F (25 °C)
Nominal conductor DC resistance 16.5 Ω/1000 ft (304.8 m) at 68 °F (20 °C)
Physical
Temperature Rating -94 °F to 392 °F (-70 °C to 200 °C)
Nominal Diameter 0.140 in (3.56 mm)
Maximum Pull Tension 36.0 lb (16.33 kg)
Minimum Bend Radius 1.50 in (38.1 mm)
Insulation Material FEP
Jacket Material FEP
Listings
UL listed as Type CL3P or CMP c(UL)us, FT-6
NFPA 262
UL444 and UL13
CSA-C22.2 No. 214
RoHS Compliant
Colors
Jacket — Clear (CL)
Conductor Color Ballast Terminal
Red +20 V-
Black Common
White IR
Blue Occupancy
Yellow Daylight
Jacket Markings
LUTRON C-PCBL-522S-CL-1 (UL File #) 22 AWG 5C SHIELDED (UL) CL3P or
CMP c(UL)us FT-6 200 °C RoHS COMPLIANT
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Cable Low-Voltage Cables
369385c 6 01.22.2018
EcoSystem Class 2 Sensor Cable Specifications (continued)
C-CBL-522S-WH-1
General Description
5 conductor EcoSystem sensor cable for non-plenum applications
22 AWG (0.34 mm
2
) solid bare copper, PVC insulated conductors
Overall aluminum-polymer foil shield, plus 24 AWG (0.25 mm
2
) copper drain wire
White 0.047 in (1.2 mm) thick PVC jacket — sheathed, UV Stabilized
All external markings use indented print
Electrical
Maximum operating voltage 300 V RMS CL3
600 V RMS AWM 20811
Maximum continuous current per conductor 4 A at 77 °F (25 °C)
Nominal conductor DC resistance 16.5 Ω/1000 ft (304.8 m) at 68 °F (20 °C)
Physical
Temperature Rating -4 °F to 221 °F (-20 °C to 105 °C)
Nominal Diameter 0.297 in (7.54 mm)
Maximum Pull Tension 36.0 lb (16.33 kg)
Minimum Bend Radius 3 in (76.2 mm)
Insulation Material PVC
Jacket Material PVC
Listings
UL Type CL3 and CM
UL recognized AWM Style 20811
UL444, UL13 and UL758
CSA-C22.2 No. 214
CPR Classification: E
CA
ROHS Compliant
Colors
Jacket - White (WH)
Conductor Color Ballast Terminal
Red +20 V-
Black Common
White IR
Blue Occupancy
Yellow Daylight
Jacket Markings
LUTRON C-CBL-522S-WH-1 PELV/SELV (UL File #) 22 AWG 5C SHIELDED (UL) CL3 or
CM c(UL)us 75 °C OR
AWM 20811 105 °C 600V RoHS COMPLIANT
6