R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
egrx-9 12.9.03
Wallstations
European Style
®
EGRX-4M-__-___
4-Unit Master Wallstation
Description
• Allows user to control several different
areas of GRAFIK Eye lighting from one
master location.
• Each button can operate a different
GRAFIK Eye Control Unit or group of
Control Units.
• Four buttons toggle their associated
Control Units on (to Scene 1) and off.
• Status LEDs indicate which Control
Units are on.
• The bottom button turns all associated
Control Units on (to scene 1) or off,
depending on settings of DIP switches
5 and 6.
• In a home, a Master Control might be
placed inside the main entry. The first
button would turn on foyer lights, the
second button would light a path to the
kitchen, etc.
• Works with a total of eight GRAFIK Eye
3000 or 4000 Series Control Units.
Control Units may be assigned to
buttons in any combination.
• Mounts in UK/German wallbox. In the
U.S., Lutron supplies a UK wallbox
(P/N 241-683) with the Wallstation.
Finish and Engraving Options
Available with engraving to meet
specific project needs.
Color and Finish Codes
Status LEDs
Toggle
Buttons
On (to Scene 1)
or Off
DIP Switches 7-10 are set at the factory.
Do not change these switches.
Field Selected Functionality
DIP Switch Settings
5 6
Bottom button:
Turns all associated Control
Units on to Scene 1.
Turns all associated Control
Units off.
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
egrx-10 12.9.03
Wallstations
European Style
®
1
234
5
6
1.4" (35mm)
2.4"
(60mm)
6mm
(1/4”)
25mm
(1”)
86mm
(3 3/8”)
86mm (3.38”)
Color and Finish Codes
Standard Finishes
Ship in 48 hours*
Black BL
White WH
Bright Brass BB
Bright Chrome BC
Satin Brass SB
Satin Chrome SC
Matte Finishes
Ship in 3 to 4 weeks
Ivory IV
Beige BE
Gray GR
Brown BR
Metal Finishes
Ship in 4 to 6 weeks
Bright Nickel BN
Satin Nickel SN
Antique Brass QB
Antique Bronze QZ
Anodized Aluminum Finishes
Ship in 4 to 6 weeks
Clear CLA
Black BLA
Brass BRA
Engraving E
Wallbox Included NA
Also available:
-Custom Controls
-Color matching
Ship in 4 to 6 weeks. Pricing
may vary depending on finish.
* 48 hours for 4S, 2B-SL, 4SIR-
8S, 8S-IR. All others – 2 weeks.
Dimensions
Front View
Mounting
Power
Low-voltage Type Class 2 (PELV).
Operating voltage: 12/24 V Direct Current
Key Design Features
• Meets IEC 801-2. Tested to withstand 15kV
electro-static discharge without damage or
memory loss.
• Faceplate snaps on with no visible means of
attachment.
System Communications and Capacity
• Low-voltage Type Class 2 (PELV) wiring
connects Wallstations to Control Units and
Control Interfaces.
• Up to 8 Control Units and up to 16 total
Wallstations and/or Control Interfaces may
be linked for a total of 24 control points.
Terminals
Accept up to two 1.0mm
2
(#18 AWG) wires
typical.
Environment
0-40°C (32-104°F). Relative humidity less
than 90% non-condensing.
Side View
Back View
Terminals for PELV
(Class 2) Wiring
UK or German wallbox.
Shipped with Wallstation in US (P/N 241-683)
DIP
Switches
Faceplate
Specifications
2
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
egrx-11 12.9.03
Wallstations
European Style
®
D3
4
21
2 # 18 AWG (1.0 mm
2
)
twisted, shielded pair
from terminals 3 to 3
and 4 to 4
#18 AWG (1.0 mm
2
)
2 #12 AWG (2.5 mm
2
)
Drain/Shield
DIP Switches
• Set DIP switches 1-4 to give the Wallstation
a unique system address from 1 to 16.
• Set additional DIP switches (if any) to specify
function as shown on the first page of the
Wallstation’s Specification Submittal.
DIP Switch Settings
Address
1234
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Reserved for GRX-PRG, if present on link.
Low-Voltage Class 2 (PELV) Wiring
• Use low-voltage Class 2 (PELV) wiring to daisy-chain
Wallstations to Control Units and other components.
• Make connections inside the wallbox or in a
switch/junction box with a maximum wire length of 8
feet (2.5m) from the link to the Wallstation.
Note: EGRX Wallstations have a “D” terminal for Drain.
Connect the Drain/Shield at this terminal.
When used with GRAFIK Eye 3000 Control Units:
• Two #18 AWG (1.0mm
2
) conductors for common
(terminal 1) and 12 V Direct Current (terminal 2). Ensure
that the terminal 2 connection is wired correctly. Refer
to GRAFIK Eye 3000 Series Specification Submittal.
• One shielded, twisted pair #18 AWG (1.0mm
2
) for data
link (terminals 3 and 4).
When used with GRAFIK Eye 4000 Control Units:
• Two #12 AWG (2.5mm
2
) conductors for common
(terminal 1) and 24 V Direct Current (terminal 2). These
won’t fit in terminals. Connect as shown.
• One shielded, twisted pair #18 AWG (1.0mm
2
) for data
link (terminals 3 and 4).
• Connect Drain/Shield as shown. Do not connect to
Ground (Earth). Connect the bare drain wires and cut
off the outside shield.
Wallstation Installation
3