SPECIFICATION SUBMITTAL
egrx-8 12.9.03
Wallstations
European Style
®
LEDs
For wall open,
Control Units
work in
combinition.
For wall closed,
Control Units work
independently
Toggle
Buttons
1
2
3
4
EGRX-4PS-__-__
4-Partition Status Wallstation
Description
• Coordinates lighting for up to four movable
walls (five rooms). Each toggle button is
setup to operate the Control Units
associated with a movable wall.
• When the wall is open to make one large
space, the user presses the wall’s toggle
button to make the LED light up. The
GRAFIK Eye Control Units assigned to the
buttons now work “in combination.” Scene
changes at one Control Unit occur on all of
these Control Units.
• When the wall is closed to make several
smaller spaces, the user presses the wall’s
toggle button to turn off the LED - the
Control Units now work independently.
• The example shows how to use the
Wallstation for a space with four
movable walls.
• Mounts in UK/German wallbox. In the U.S.,
Lutron supplies a UK wallbox (P/N 241-683)
with the Wallstation.
Finish and Engraving Options
Available with engraving to meet specific
project needs.
1
ABCDE
Movable Wall
Movable Wall
23
Movable Wall
Movable Wall
4
Color and Finish Codes
DIP Switches 7-10 are set at the factory.
Do not change these switches.
Button:
Button 1
Button 2
Button 3
Button 4
Wall:
Wall 1
Wall 2
Wall 3
Wall 4
Combine
Control Units:
A and B
B and C
C and D
D and E
Example
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
egrx-10 12.9.03
Wallstations
European Style
®
1
234
5
6
1.4" (35mm)
2.4"
(60mm)
6mm
(1/4”)
25mm
(1”)
86mm
(3 3/8”)
86mm (3.38”)
Color and Finish Codes
Standard Finishes
Ship in 48 hours*
Black BL
White WH
Bright Brass BB
Bright Chrome BC
Satin Brass SB
Satin Chrome SC
Matte Finishes
Ship in 3 to 4 weeks
Ivory IV
Beige BE
Gray GR
Brown BR
Metal Finishes
Ship in 4 to 6 weeks
Bright Nickel BN
Satin Nickel SN
Antique Brass QB
Antique Bronze QZ
Anodized Aluminum Finishes
Ship in 4 to 6 weeks
Clear CLA
Black BLA
Brass BRA
Engraving E
Wallbox Included NA
Also available:
-Custom Controls
-Color matching
Ship in 4 to 6 weeks. Pricing
may vary depending on finish.
* 48 hours for 4S, 2B-SL, 4SIR-
8S, 8S-IR. All others – 2 weeks.
Dimensions
Front View
Mounting
Power
Low-voltage Type Class 2 (PELV).
Operating voltage: 12/24 V Direct Current
Key Design Features
• Meets IEC 801-2. Tested to withstand 15kV
electro-static discharge without damage or
memory loss.
• Faceplate snaps on with no visible means of
attachment.
System Communications and Capacity
• Low-voltage Type Class 2 (PELV) wiring
connects Wallstations to Control Units and
Control Interfaces.
• Up to 8 Control Units and up to 16 total
Wallstations and/or Control Interfaces may
be linked for a total of 24 control points.
Terminals
Accept up to two 1.0mm
2
(#18 AWG) wires
typical.
Environment
0-40°C (32-104°F). Relative humidity less
than 90% non-condensing.
Side View
Back View
Terminals for PELV
(Class 2) Wiring
UK or German wallbox.
Shipped with Wallstation in US (P/N 241-683)
DIP
Switches
Faceplate
Specifications
2
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
egrx-11 12.9.03
Wallstations
European Style
®
D3
4
21
2 # 18 AWG (1.0 mm
2
)
twisted, shielded pair
from terminals 3 to 3
and 4 to 4
#18 AWG (1.0 mm
2
)
2 #12 AWG (2.5 mm
2
)
Drain/Shield
DIP Switches
• Set DIP switches 1-4 to give the Wallstation
a unique system address from 1 to 16.
• Set additional DIP switches (if any) to specify
function as shown on the first page of the
Wallstation’s Specification Submittal.
DIP Switch Settings
Address
1234
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Reserved for GRX-PRG, if present on link.
Low-Voltage Class 2 (PELV) Wiring
• Use low-voltage Class 2 (PELV) wiring to daisy-chain
Wallstations to Control Units and other components.
• Make connections inside the wallbox or in a
switch/junction box with a maximum wire length of 8
feet (2.5m) from the link to the Wallstation.
Note: EGRX Wallstations have a “D” terminal for Drain.
Connect the Drain/Shield at this terminal.
When used with GRAFIK Eye 3000 Control Units:
• Two #18 AWG (1.0mm
2
) conductors for common
(terminal 1) and 12 V Direct Current (terminal 2). Ensure
that the terminal 2 connection is wired correctly. Refer
to GRAFIK Eye 3000 Series Specification Submittal.
• One shielded, twisted pair #18 AWG (1.0mm
2
) for data
link (terminals 3 and 4).
When used with GRAFIK Eye 4000 Control Units:
• Two #12 AWG (2.5mm
2
) conductors for common
(terminal 1) and 24 V Direct Current (terminal 2). These
won’t fit in terminals. Connect as shown.
• One shielded, twisted pair #18 AWG (1.0mm
2
) for data
link (terminals 3 and 4).
• Connect Drain/Shield as shown. Do not connect to
Ground (Earth). Connect the bare drain wires and cut
off the outside shield.
Wallstation Installation
3