If several generators are to serve primary distribution systems, they should generate the
same voltage to avoid the need for voltage transformation. The number of phases
required by the load may differ from that produced by the generator. As loads usually
can be divided and balanced between phases, most generators of appreciable size are
wound for three phase operation.
3.1.1 Power and Voltage Requirements
The selection of voltage is affected by the size, character, and distribution of the load;
length, capacity, and type of transmission and distribution circuits; and size, location,
and connection of generators. Practically all general-purpose lighting in the United
States and at United States overseas bases is 120 volts. The lighting voltage may be
obtained from a three-wire, 120/240-volt, single-phase circuit or a 120/208-volt, three-
phase, four-wire circuit.
Small motors can be supplied by single-phase AC at normally 120 volts. Large three-
phase, AC motors above 5 horsepower (hp) generally operate satisfactorily at any
voltage between 200 and 240. The use of combined light and power circuits will be
accomplished by the use of 240- or 208-volt systems.
3.1.2 Computation of the Load
As mentioned earlier, you must take various factors into consideration in selecting the
required generating equipment. The following technical data will help you compute the
load.
Before designing any part of the system, you must determine the amount of power to be
transmitted, or the electrical load. Electrical loads are generally measured in terms of
amperes, kilowatts, or kilovoltamperes. In general, electrical loads are seldom constant
for any appreciable time, but fluctuate constantly. To calculate the electrical load,
determine the connected load first. The connected load is the sum of the rated
capacities of all electrical appliances, lamps, motors, and so on, connected to the wiring
of the system. The maximum demand load is the greatest value of all connected loads
that are in operation over a specified period of time. Knowledge of the maximum
demand of groups of loads is of great importance because the group maximum demand
determines the size of generators, conductors, and apparatuses throughout the
electrical system.
The ratio between the actual maximum demand and the connected load is called the
DEMAND FACTOR. If a group of loads were all connected to the supply source and
drew their rated loads at the same time, the demand factor would be 1.00. There are
two main reasons why the demand factor is usually less than 1.00. First, all load
devices are seldom in use at the same time and, even if they are, they will seldom reach
maximum demand at the same time. Second, some load devices are usually slightly
larger than the minimum size needed and normally draw less than their rated load.
Since maximum demand is one of the factors determining the size of conductors, it is
important to establish the demand factor as closely as possible.
The demand factor varies considerably for different types of loads, services, and
structures. The National Electrical Code®. Article 220 provides the requirements for
determining demand factors. Demand factors for some military structures are given in
Table 6-2.