Vive PowPak CCO Module Wireless Lighting Control
369909e 3 08.15.17
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Environment
•Ambientoperatingtemperature:32°Fto131°F
(0°Cto55°C)
•0%to90humidity,non-condensing
•Forindooruseonly
•AlldriversandballastsusedwithVivewireless
controls must comply with the limits for a Class A
devicepursuanttoPart15oftheFCCRules
Contact Closure Output
•Acceptsinputvoltagesof0–24V~/0–24V-; see
chart below for load switching capacities
•Providesbothnormallyopen(NO)andnormally
closed (NC) dry contacts
•Maintainedoutputtype
•CCOterminalsaccept20AWGto16AWG
(0.5mm
2
to1.5mm
2
) solid or stranded wire
•Outputislatching
•TheCCOisnotratedtocontrolunclamped,inductive
loads. Inductive loads include, but are not limited
to, relays, solenoids, and motors. To control these
types of equipment, a flyback diode must be used
(DC voltages only). See diagram below. For more
information, please see Application Note #434 (p/n
048434).
Specifications
Regulatory Approvals
RMJS- / URMJS- models
•UL® Listed (U.S.A.)
•FCCapproved.ComplieswiththelimitsforaClass
Bdevice,pursuanttoPart15oftheFCCrules.
(U.S.A.)
• Complieswithrequirementsforuseinotherspaces
used for environmental air (plenums) per
NEC
®2014300.22(C)(3)
• ListedinaccordancetoCAN/ULCS102.2-2010
with a Flame Spread Rating of 0 and a Smoke
Developed Classification of 40, with a minimum
spacingof6ft(1.83m)offcenter
•CSAandIC(Canada)(RMJS-only)
•COFETEL(Mexico)(RMJS-only)
Power
•IECPELV/NEC® Class 2
•Operatingvoltage:24V~ / 24 V-
•Operatingcurrent,nominal:45mA(24V~)
35mA(24V-)
•StandbyPowerConsumption(allmodels):<1.0W
System Communication
•OperatesusingClearConnectRFTechnologyfor
reliable wireless communication; refer to model
numberchartonpage1forfrequencybanddetails
•RFrangeis30ft(9m)forRMJS-andURMJS-
models
•Wirelesssensorsandcontrolsmustbelocated
within60ft(18m)lineofsight,or30ft(9m),
through walls, of the associated control module.
The60ft(18m)rangeisnotreducedbyaceilingtile
obstruction.
•ContactLutronrstforapplicationsusing
foil-backed or metallic ceiling tiles.
Switching
Voltage
0-24 V-
0-24 V~
24 V-
max.
Inductive
Load
CCO
Output
NO
NC
COM
Flyback
Diode
(required for
inductive
loads)
Resistive
Load
1.0 A
0.5 A
R
Switching
Voltage
0-24 V-
0-24 V~
24 V-
max.
Inductive
Load
CCO
Output
NO
NC
COM
Flyback
Diode
(required for
inductive
loads)
Resistive
Load
1.0 A
0.5 A
R
+
-