369912a 1 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
ViveTM Basic Packages
The ViveTM Basic Package incorporates Maestro®
load controls and wireless sensors which provides
a system that delivers energy savings, convenience,
and ease of installation.
Maestro Wireless
® switches use Lutron® patented
Clear Connect
® RF Technology, which enables
wireless communication with Radio Powr Savr
TM
sensors for light control.
These products are also compatible with the Vive
TM
hub which enables a simple setup process using a
standard web browser on any Wi-Fi enabled phone,
tablet or computer. It also enables control and
monitoring of all Vive
TM devices. The ViveTM hub can
be added at any time and preserves existing system
setup by extracting local programming from each
device. For a complete list of features supported with
the Vive
TM hub, see specification submittal 369902.
Note for Replacement: MRF2S - the “S” model can
replace the non-S” model.
Features
• The Vive
TM Basic package provides switching and
occupancy / vacancy sensing of multiple load types.
• Lutron
® patented Clear Connect® RF Technology
works through walls and floors.
• Controls include Front Accessible Service Switch
(FASS
TM) for safe lamp replacement.
• Two-wire installation for any retrofit application.
• Power failure memory: If power is interrupted, the
control will return to its previously set level prior to
interruption.
Receiving Devices
Maestro Wireless
® Control
Transmitting Devices
Radio Powr Savr
TM Sensors
RF Switch
Ceiling-Mounted Occupancy
and Vacancy Sensor
Wall, Corner, or
Hall Mounted
Occupancy and
Vacancy Sensor
1
369912a 2 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
ViveTM Basic Packages
Model Numbers
MRF2S-1S8A-1OC (1) 8 A Switch, (1) Radio Powr Savr
TM ceiling sensor
MRF2S-1S8A-1OH (1) 8 A Switch, (1) Radio Powr Savr
TM hallway senso
MRF2S-1S8A-1OK (1) 8 A Switch, (1) Radio Powr Savr
TM corner sensor
MRF2S-1S8A-1OW (1) 8 A Switch, (1) Radio Powr Savr
TM wall sensor
MRF2S-1S8A-1VC (1) 8 A Switch, (1) Radio Powr Savr
TM ceiling vacancy sensor
MRF2S-2S8A-1OW (2) 8 A Switches, (1) Radio Powr Savr
TM wall sensor
2
369912a 3 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Maestro WirelessR Switch
Model Number
Switch
Lighting and motor loads
MRF2S-8S-DV-XX
1
8 A Lighting, 3 A Fan (1/10 HP
motor, 120 V~ only), Spec
Grade Electronic Switch
120–277 V~, NO NEUTRAL
WIRE REQUIRED
Companion Controls
ClaroR Gloss Finishes
MA-AS-XX
1
Companion Switch 120 V~
MA-AS-277-XX
1
Companion Switch 277 V~
Satin ColorsR Satin Finishes
MSC-AS-XX
1
Companion Switch 120 V~
MSC-AS-277-XX
1
Companion Switch 277 V~
Switch
Companion Switch
Switch Load Type and Capacity
No Neutral Required
Control Voltage Load Type Minimum
Load
Maximum Load
Not
Ganged
End of
Gang
Middle of
Gang
MRF2S-8S-DV
1,2
120–277 V~
Incandescent /
Halogen
25 W 8 A 8 A / 7 A
3
7 A
120–277 V~
Fluorescent /
LED/CFL
40 W
(LUT-MLC)
4
8 A 8 A / 7 A
3
7 A
120 V~
Fan
Motor
0.4 A
1/10 HP
3 A
1/10 HP
3 A
1/10 HP
3 A
1
Switch Load Type: MRF2S-8S-DV is designed for use with permanently installed lighting loads and with fan motor loads up to 1/10 HP (3 A, 120 V~ only).
2
Switch Load Type: MRF2S-8S-DV are designed for use with permanently installed lighting loads.
3
Maximum load for double gang application is 8 A. Triple gang application derates maximum load to 7 A.
4
The LUT-MLC (included) ensures proper function with certain fluorescent, CFL, and LED load types.
MRF2S-8S-DV-XX MA-AS-XX
1
XX in the model number represents Color / Finish code. See Page 7 for Colors and Finishes.
3
369912a 4 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Specifications
Regulatory Approvals
• UL
® Listed.
• CSA Certified.
• FCC Approved. Complies with the limits for a
Class B digital device, pursuant to Part 15 of the
FCC Rules.
• Industry Canada Certified.
Power
Operating voltage:
120–277 V~ 50 / 60 Hz
Key Design Features
Switch
• On a single-tap, lights turn ON or OFF.
All RF Local Controls
• Tested to withstand electrostatic discharge without
damage or memory loss, in accordance with IEC
61000-4-2.
• Tested to withstand surge voltages without damage
or loss of operation, in accordance with IEEE
C62.41-1991 Recommended Practice on Surge
Voltages in Low-Voltage AC Power Circuits.
• Controls always operate locally and do not require
system control.
• Power failure memory: should power be interrupted,
the control will return to its previously set level prior
to the interruption when power is restored.
• Uses conventional Single-pole, 3-way and 4-way
wiring.
• Multiple location control from Switch and up to
9 Companion Switches.
• Use Lutron
® Designer (Claro® and Satin Colors®)
wallplates or designer-style wallplates from other
manufacturers. Wallplates are sold separately.
• Lutron Claro
® and Satin Colors® wallplates snap on
with no visible means of attachment.
• Requires a 1-gang U.S. wallbox. 3
1
2 in (89 mm) deep
recommended, 2
1
4 in (57 mm) deep minimum.
• Green indicator light.
System Communications and Capacity
• Maestro Wireless
® controls communicate with the
Pico
® remote controls and Radio Power SavrTM
sensors through radio frequency (RF).
Receives wireless inputs from up to 10
Pico
® remote controls, 10 Radio Powr SavrTM
occupancy / vacancy sensors, and 1 Radio Powr
Savr
TM daylight sensor
• Maestro Wireless
® local controls must be located
within 60 ft (18 m) line of sight or 30 ft (9 m)
through walls, of Radio Power Savr
TM sensors.
• Maestro Wireless
® local controls must be located
within 60 ft (18 m) line of sight or 30 ft (9 m)
through walls, of a Pico
® remote control.
Up to 10 Maestro Wireless
® controls can be
configured to work together.
• Sensors can be assigned to multiple switches.
Environment
• Ambient operating temperature: 32 °F to 104 °F
(0 °C to 40 °C)
• 0%-90% relative humidity, non-condensing.
• Indoor use only.
4
369912a 5 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Mounting
Wallbox
Control
Adapter
Mounting
Screws
Control
Mounting
Screws
Wallplate / Adapter purchased
separately.
Operation
IMPORTANT NOTICE:
FASSTM - Front Accessible Service Switch - to service load, remove power by pulling the FASSTM switch out
completely on either the Switch or Companion Switch. After servicing load, push the FASSTM switch back in fully to
restore power to the control.
Tapswitch
Tap ON / OFF
FASSTM
Front
Accessible
Service
Switch
Switch
Status LED
Indicates load status; glows softly as
night light when light is off
Dimensions
Front View
Side View
5/16 in
(8 mm)
1
1
8 in
(30 mm)
4
11
16 in
(119 mm)
2
15
16 in
(75 mm)
5
369912a 6 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Single Location Installation
MRF2S-8S-DV
Brass
Black
Blue - unused, tighten
1
Optional
Green
Ground
Line / Hot
Neutral
Switch
Switch
Wiring Diagrams
Multi-Location Installation
2
MRF2S-8S-DV
3
with MA-AS / MA-AS-277 or MSC-AS / MSC-AS-277
Brass
Black
Blue
Green
Ground
Brass
Black
Blue
Green
Ground
Brass
Black
Blue
Green
Ground
Line / Hot
Neutral
Companion Switch Companion Switch
Load
Load
120 V277 V~
50 / 60 Hz
120 V277 V~
50 / 60 Hz
LUT-MLC*
1
When using controls in single location installations, tighten the blue terminal without any wires attached. DO NOT connect the blue terminal to any other wiring or
to ground.
2
Up to 9 Maestro® Companion Switches may be connected to the Maestro Wireless® Switch. Total blue terminal wire length may be up to 250 ft (76 m).
3
Requires MA-AS / MSC-AS for 120 V~ applications, and MA-AS-277 / MSC-AS-277 for 277 V~ applications.
Optional
*
A LUT-MLC ensures proper function when fluorescent, CFL, or LED
loads are used. Install the LUT-MLC inside a load fixture or in a
separate J-box of the circuit.
LUT-MLC*
6
369912a 7 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Colors and Finishes
Gloss Finishes Satin Finishes
Metal Finish
(wallplate only)
Stainless Steel
SS
Taupe
TP
Turquoise
TQ
Plum
PL
Merlot
MR
Terracotta
TC
Sienna
SI
Midnight
MN
Hot
HT
Desert Stone
DS
Due to printing limitations, colors
and finishes shown cannot be
guaranteed to perfectly match
actual product colors.
Eggshell
ES
Biscuit
BI
Snow
SW
Palladium
PD
Greenbriar
GB
Bluestone
BG
Mocha
Stone
MS
Goldstone
GS
Stone
ST
Limestone
LS
White
WH
Ivory
IV
Almond
AL
Light
Almond
LA
Gray
GR
Brown
BR
Black
BL
When using Stainless Steel wallplates, it
is recommended to order the controls in
Black (BL) or Midnight (MN).
7
369912a 8 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Radio Powr SavrTM Wireless
Occupancy / Vacancy Ceiling Sensor
Lutron® Radio Powr SavrTM occupancy / vacancy
sensors are wireless, battery-powered passive
infrared (PIR) sensors that automatically control lights
via RF communication to compatible dimming and
switching devices. These sensors detect the heat
from people moving within an area to determine
when the space is occupied. The sensors then
wirelessly transmit the appropriate commands to the
associated dimming and switching devices to turn
the lights on or off automatically. They combine both
convenience and exceptional energy savings
potential along with ease of installation.
Features
Wireless occupancy sensor has 3 settings available:
Auto-ON / Auto-OFF, Auto-ON Low-Light / Auto-OFF,
and Manual-ON / Auto-OFF
Auto-ON Low-Light feature will only turn lights on
automatically if there is less than approximately 10
Lux
(1 fc) of ambient light
Vacancy only model available to meet California (U.S.A.)
Title 24 requirements
Uses Clear Connect
® technology
Passive infrared motion detection with exclusive
Lutron
® XCTTM Technology for fine motion detection
360˚ coverage ranges from 324 ft
2
(30.2 m
2
) to 676
ft
2
(62.4 m
2
), depending on mounting height. See
range diagrams for more details.
Simple and intuitive adjustments available for
Timeout, Auto-ON, and Activity settings
Supports advanced occupancy features, such as
dependent occupancy groups and customizable
occupied / unoccupied presets in some systems
Multiple sensors can be added for extended
coveragerefer to product specification submittal of
receiving device to determine system limits
Lens illuminates during test mode to verify ideal
locations
Multiple ceiling-mount methods available for different
ceiling materials
Front accessible test buttons make programming easy
10-year battery life design
• RoHS compliant
8
369912a 9 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Specifications
Regulatory Approvals
• FCC certified
• IC certified
Meets CA (U.S.A.) Energy Commission Title 24
requirements
• COFETEL
• ANATEL
• SUTEL
• Lutron
® Quality Systems Registered to ISO
9001:2008
Power/Performance
Operating voltage: 3 V -
Operating current: 14 μA nominal
Requires one CR 123 lithium battery
10-year battery life
Non-volatile memory (saved changes are stored
during power loss)
Environment
Temperature: 32 ˚F to 104 ˚F (0 ˚C to 40 ˚C)
For indoor use only
Range
Local load controls must be located within 60 ft (18
m) line of sight, or 30 ft (9 m), through walls, of a
sensor.
Sensor Coverage Test
Front accessible test button
Lens illuminates orange in response to motion
during test mode and is visible from 60 ft (18 m)
Wireless Communication Test
Front accessible test button
Turn associated loads on and off
Timeout Options
1 minute *
• 5 minutes
15 minutes – default setting
• 30 minutes
Auto-On Options (Occupancy Versions Only)
“Enabled” – Sensor turns lights ON and OFF
automatically – default setting.
“Low Light” – Sensor turns lights ON automatically
only in low ambient light conditions. Sensor turns
lights OFF automatically.
“Disabled” ** – Lights must be turned ON manually
from dimming or switching device. Sensor turns
lights OFF automatically.
Activity Options
Low Activity (
) – default setting
Medium Activity (
)
High Activity (
)
* Intended for use in high-activity, briefly occupied areas only
** There is a 15-second grace period that begins when the lights are
automatically turned off, during which the lights will automatically turn
back on in response to motion. This grace period is provided as a safety
and convenience feature in the event the lights turn off while the room is
still occupied, so that the user does not need to manually turn the lights
back on. After 15 seconds, the grace period expires and the lights must
be manually turned on.
9
369912a 10 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Installation Overview
Sensor Setup
Sensor setup is available as a service by Lutron. For more information see the Sensor Layout and Tuning service
document (Lutron
® P/N 3601235).
Sensor Placement
The ability of the sensor to detect motion requires line of sight of room occupants. The sensor must have an
unobstructed view of the room. DO NOT mount behind or near tall cabinets, shelves, hanging fixtures, ceiling fans,
etc. The sensor cannot see through glass objects such as patio or shower doors.
Hot objects and moving air currents can affect the performance of the sensor. To ensure proper operation, the
sensor should be mounted at least 4 ft (1.2 m) away from HVAC vents and light bulbs that are below the ceiling line.
The performance of the sensor depends on a temperature differential between the ambient room temperature and
that of room occupants. Warmer rooms may reduce the ability of the sensor to detect occupants.
Mounting
Temporary mounting is optional to test sensor coverage and wireless communication before permanently installing
the sensor.
Drop Ceiling (Compressed Fiber Ceiling Tile)
The mounting wire is provided for both temporary and permanent mounting of the sensor to ceiling tiles. It is
designed to allow temporary mounting, testing, and repositioning (if necessary) of the sensor without damaging a
ceiling tile. Once the final position of the sensor has been chosen, the mounting wire should be twisted together to
permanently secure the
sensor in place.
Solid Ceiling (Drywall, Plaster, Concrete, or Wood)
Temporary mounting: Ten (10) temporary mounting strips can be purchased in the kit L-CMDPIRKIT for temporarily
mounting and testing the sensor.
Permanent mounting: Screws and anchors (for drywall or plaster) provided to mount the sensor.
Recess Mount
• Do not recess mount sensor in a metal surface.
• Recess mounting ring requires an opening of 3 in (76 mm) in
diameter.
• Recess mounting ring secures internally to ceiling. Sensor
twists into the recess mounting ring and sits flush with ceiling
(see image to right).
• Recess mounting ring purchased as a separate kit: L-CRMK-WH.
10
369912a 11 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimensions
3.57 in
(90.7 mm)
2.85 in
(72.4 mm)
1.13 in
(28.7 mm)
0.40 in *
(10.2 mm)
0.60 in
(15.2 mm)
1.00 in
(25.4 mm)
* With the recess mounting kit 0.46 (11.7 mm) is below the plane of the ceiling.
11
369912a 12 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
* 12 ft (3.7 m) is the recommended maximum mounting height
Range Diagrams
8 ft
(2.4 m)
Ceiling
height
9 ft
(2.7 m)
9 ft
(2.7 m)
0 ft
(0 m)
12 ft
(3.7 m)
6 ft
(1.8 m)
3 ft
(0.9 m)
15 ft
(4.6 m)
15 ft
(4.6 m)
3 ft
(0.9 m)
6 ft
(1.8 m)
12 ft
(3.7 m)
Radius of Coverage at Floor
Sensor
Floor
Ceiling
Occupant
18 ft x 18 ft (5.5 m x 5.5 m) Maximum
room dimensions for complete coverage
when mounted on an 8 ft (2.4 m) ceiling
13 ft (4.0 m) Radius of coverage at floor
when mounted on an 8 ft (2.4 m) ceiling
Sensor Coverage Chart (for sensor mounted in center of room)
Ceiling Height Maximum Room Dimensions for Complete Floor
Coverage*
8 ft (2.4 m) 18 ft x 18 ft (5.5 m × 5.5 m) 324 ft
2
(30.2 m
2
)
9 ft (2.7 m) 20 ft x 20 ft (6.1 m × 6.1 m) 400 ft
2
(37.2 m
2
)
10 ft (3.0 m) 22 ft x 22 ft (6.7 m × 6.7 m) 484 ft
2
(44.9 m
2
)
12 ft (3.7 m) 26 ft x 26 ft (7.9 m × 7.9 m) 676 ft
2
(62.4 m
2
)
12
369912a 13 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lens Masking
Whenever possible, the sensor should be installed in a location where it cannot view areas outside the intended
space, such as hallways or adjacent rooms. If this situation cannot be avoided, portions of the lens may be
masked to block the view of the sensor into undesired areas. Ten (10) PIR Lens Masks can be purchased in the
kit L-CMDPIRKIT.
Lens sections
shown in white are
masked with labels
Lens sections
shown in gray
have not been
masked
PIR Lens Mask
sold separately
(L-CMDPIRKIT)
Hallway falls
within Sensor’s
coverage area.
13
369912a 14 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wireless Wall-Mount Sensor
Lutron® wall-mounted occupancy and vacancy sensors
are wireless battery-powered passive infrared (PIR)
sensors that automatically control lights via RF
communication to compatible dimming or switching
devices. These sensors detect the heat from people
moving within an area to determine when the space is
occupied. The sensors then wirelessly transmit the
appropriate commands to the associated dimming or
switching devices to turn the lights on or off automatically.
They combine both convenience and exceptional energy
savings along with ease of installation.
Features
Wireless occupancy / vacancy sensor has 2 settings
available: Auto-ON / Auto-OFF, and Manual-ON / Auto-OFF
Vacancy model meets California Title 24 requirements
Passive infrared motion detection with exclusive Lutron
®
XCT
TM Technology for fine motion detection
180˚ field of view model:
Minor motion = 1500 ft
2
(139.4 m
2
)
Major motion = 3000 ft
2
(278.7 m
2
)
90˚ field of view model:
Minor motion = 1225 ft
2
(113.8 m
2
)
Major motion = 2500 ft
2
(232.3 m
2
)
Hallway model with long, narrow field of view:
Major motion = coverage of up to 150 ft (45.7 m)
Simple and intuitive adjustments available for Timeout,
Activity, and Auto-ON settings
Accessible test buttons make setup easy
Lens illuminates during test mode to verify ideal locations
Multiple sensors can be added for extended coverage
refer to product specification submittal of receiving device
to determine system limits
10-year battery life design
• RoHS compliant
Compatible RF Devices
For use with Lutron® products only
Communicates to various wireless Lutron
® Clear ConnectR
systems*
* Contact Lutron Customer Service at www.lutron.com for
frequency / channel code compatibility with your particular
geographic region, and for integrating with other Lutron
®
lighting and shading products.
14
369912a 15 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Specifications
Regulatory Approvals
• cULus Listed
• FCC certified
• IC certified
• COFETEL certified
• ANATEL certified
• SUTEL certified
Meets CA (U.S.A.) Energy Commission Title 24
requirements
• Lutron
® Quality Systems Registered to
ISO 9001:2008
Power/Performance
Operating voltage: 3 V -
Operating current: 14 μA nominal
Requires one CR 123 lithium battery
10-year battery life design
Non-volatile memory (saved changes are stored
during power loss)
Environment
Temperature: 32 ˚F to 104 ˚F (0 ˚C to 40 ˚C)
For indoor use only
RF Range
Distance between local load controls and sensor
should not exceed 60 ft (18 m) line of sight or 30 ft
(9 m) through walls.
Sensor Coverage Test
Dedicated test button
Lens illuminates orange in response to motion
during test mode
Wireless Communication Test
Dedicated test button
Turn associated loads on and off
Timeout Options
1 minute *
• 5 minutes
15 minutes – default setting
• 30 minutes
Auto-On Options (Occupancy Versions Only)
“Enabled” – Sensor turns lights ON and OFF
automatically – default setting.
“Disabled” ** – Lights must be turned ON manually
from dimming or switching device. Sensor turns
lights OFF automatically.
Sensitivity Options
Low Activity (
) – default setting
Medium Activity (
)
High Activity (
)
* Intended for use in high-activity, briefly occupied areas only
** There is a 15-second grace period that begins when the lights are
automatically turned off, during which the lights will automatically turn
back on in response to motion. This grace period is provided as a safety
and convenience feature in the event the lights turn off while the room is
still occupied, so that the user does not need to manually turn the lights
back on. After 15 seconds, the grace period expires and the lights must
be manually turned on.
15
369912a 16 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimensions
4.35 in
(110 mm)
1.35 in
(34 mm)
1.8 in
(46 mm)
16
369912a 17 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Coverage Diagrams
180° Wall-Mount Sensors
(Models: LRFX-OWLB-P-WH and LRFX-VWLB-P-WH)
* Sensor mounting shown at 7 ft (2.1 m). Mounting height should be between 6 ft and 8 ft (1.6 m and 2.4 m).
Horizontal Beam Diagram
Vertical Beam Diagram *
0 ft
(0 m)
7 ft
(2.1 m)
0 ft
(0 m)
60 ft
(18.3 m)
20 ft
(6.1 m)
10 ft
(3.0 m)
30 ft
(9.1 m)
40 ft
(12.2 m)
50 ft
(15.2 m)
0 ft
(0 m)
20 ft
(6.1 m)
10 ft
(3.0 m)
25 ft
(7.6 m)
20 ft
(6.1 m)
10 ft
(3.0 m)
25 ft
(7.6 m)
0 ft
(0 m)
60 ft
(18.3 m)
20 ft
(6.1 m)
10 ft
(3.0 m)
30 ft
(9.1 m)
40 ft
(12.2 m)
50 ft
(15.2 m)
Compliant to NEMA WD7 test grid shown below
Tested Coverage Area
Major Motion 3000 ft
2
(278.7 m
2
) coverage
Minor Motion 1500 ft
2
(139.4 m
2
) coverage
25 ft
(7.6 m)
15 ft
(4.6 m)
50 ft
(15.2 m)
60 ft
(18.3 m)
17
369912a 18 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Coverage Diagrams
90° Corner-Mount Sensors
(Models: LRFX-OKLB-P-WH and LRFX-VKLB-P-WH)
* Sensor mounting shown at 7 ft (2.1 m). Mounting height should be between 6 ft and 8 ft (1.6 m and 2.4 m).
50 ft (15.2 m)
35 ft (10.7 m)
0 ft
(0 m)
7 ft
(2.1 m)
0 ft
(0 m)
20 ft
(6.1 m)
10 ft
(3.0 m)
30 ft
(9.1 m)
40 ft
(12.2 m)
56 ft
(17.1 m)
Horizontal Beam Diagram
Vertical Beam Diagram *
Compliant to NEMA WD7 test grid shown below
Tested Coverage Area
Major Motion 2500 ft
2
(232.3 m
2
) coverage
Minor Motion 1225 ft
2
(113.8 m
2
) coverage
50 ft
(15.2 m)
35 ft
(10.7 m)
35 ft
(10.7 m)
50 ft
(15.2 m)
18
369912a 19 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Coverage Diagrams
Hallway Sensors
(Models: LRFX-OHLB-P-WH and LRFX-VHLB-P-WH)
• Designed to mount at the end of a hallway with a clear view down the length of a hall.
• Detection at longer distances is best when motion occurs at right angles to the sensor.
• Multiple sensors can be used to extend coverage.
* Sensor mounting shown at 7 ft (2.1 m). Mounting height should be between 6 ft and 8 ft (1.8 m and 2.4 m) and centered within hallway.
Width of Hall Length of Hall
6 ft (1.8 m) or less 50 ft (15.2 m)
8 ft (2.4 m) 100 ft (30.5 m)
10 ft (3.0 m) or more 150 ft (45.7 m)
Maximum Recommended Hallway Length
5 ft
(1.5 m)
0 ft
(0 m)
5 ft
(1.5 m)
0 ft
(0 m)
25 ft
(7.6 m)
50 ft
(15.2 m)
75 ft
(22.9 m)
100 ft
(30.5 m)
150 ft
(45.7 m)
125 ft
(38.1 m)
0 ft
(0 m)
25 ft
(7.6 m)
50 ft
(15.2 m)
75 ft
(22.9 m)
100 ft
(30.5 m)
150 ft
(45.7 m)
125 ft
(38.1 m)
0 ft
(0 m)
7 ft
(2.1 m)
Top View
Side View
19
369912a 20 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Installation Overview
Sensor Placement
The mounting height of the sensor should be between 6 ft and 8 ft (1.6 m and 2.4 m)
For smaller rooms less than 12 ft x 12 ft (3.7 m x 3.7 m), detection may be improved by mounting the sensor at
6 ft (1.8 m) from the floor.
The ability to detect motion requires that the sensor have line-of-sight of all room occupants. The sensor must
have an unobstructed view of the room. DO NOT mount behind or near tall cabinets, shelves, hanging fixtures,
etc. The sensor cannot detect occupants through glass objects such as patio or shower doors.
Hot objects and moving air currents can affect the performance of the sensor. To ensure proper operation, the
sensor should be mounted at least 4 ft (1.2 m) away from light bulbs and HVAC vents.
The performance of the sensor depends on a temperature differential between the ambient room temperature
and that of room occupants. Warmer rooms may reduce the sensor’s ability to detect occupants.
Distance between local load controls and sensor should not exceed 60 ft (18 m) line of sight or 30 ft (9 m)
through walls.
20
369912a 21 11.10.15
ViveTM Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Mounting
180˚ and hallway sensors mount directly to wall with mounting bracket (included). See figure below.
90˚ sensors mount directly in corner or on wall offset away from corner with mounting bracket (included).
See figure below.
Temporary mounting is recommended to test sensor coverage and wireless communication before permanently
installing the sensor.
Temporary mounting: A 3M
TM CommandTM adhesive strip is provided for temporarily mounting and testing
the sensor. This strip is designed for easy, damage-free removal and is not reusable.
Permanent mounting: Mounting bracket, screws and anchors are provided to mount sensor.
• Flexible Armature Mounting Kit - P/N LRF2-MTG-KIT-CPN5991 (sold separately): A flexible sensor mounting
bracket which allows sensor to be mounted at right angles and at greater heights to increase coverage
area.
3M and Command are trademarks of 3M Company.
180˚ Wall-Mount Sensor & Hallway Sensor
90˚ Corner-Mount Sensor
21