Vive PowPak Relay Module with Softswitch Wireless Lighting Control
369908f 4 03.12.18
Specifications (continued)
Emergency Model Sequence of Operation
With a Vive hub:
• Normal mode: The RMJS-16R-DV-B-EM can switch
loads as normal and respond to local button presses,
Pico wireless controls, and occupancy / daylight sensors.
• If the emergency PowPak loses power for greater than
250 mS, it will automatically go into emergency mode (full
output, relay closed), when emergency power is restored
to the PowPak, for as long as the Vive hub has no power.
All local buttons, Pico wireless controls and occupancy /
daylight sensors will not respond. The emergency light
level of the emergency PowPak can be configured using
the Vive hub.
• When normal power is restored to the Vive hub and
emergency PowPak, the emergency PowPak will return
to the previous light level in most cases within 3 minutes,
but guaranteed within 10 minutes of normal power being
restored. It will again accept local button control, input
from Pico wireless controls, and occupancy / daylight
sensors.
Without a Vive hub:
• Normal mode: The RMJS-16R-DV-B-EM can switch
loads as normal and respond to local button presses,
Pico wireless controls, and occupancy / daylight sensors.
• If the emergency PowPak loses power for greater than
250 mS, it will automatically go into emergency mode (full
output, relay closed) for 90 minutes, when emergency
power is restored to the PowPak. All local buttons, Pico
wireless controls and occupancy /daylight sensors will
not respond for 90 minutes.
• When normal power is restored, the emergency PowPak
will remain in emergency mode for 90 minutes (full
output, relay closed). It will then return to the previous
light level and accept local button control, inputs from
Pico wireless controls, and occupancy/daylight sensors.
Contact Closure Output (CCO version only)
• Provides occupancy status to 3rd-party equipment
such as building management systems, HVAC, and
VAV controllers
• Provides both normally open (NO) and normally
closed (NC) dry contacts
• Maintained output type
• CCO terminals accept
20 AWG to 16 AWG
(0.5 mm
2
to 1.5 mm
2
)
solid or stranded wire
•
Output is latching
• Not for voltages greater than 24 V-
• The CCO is not rated to control unclamped, inductive
loads. Inductive loads include, but are not limited
to: relays, solenoids, and motors. To control these
types of equipment, a flyback diode must be used
(DC voltages only). See diagram below. For more
information, please see Application Note #434
(P/N 048434 at www.lutron.com).
24 V-
max.
Inductive
Load
CCO
Output
NO
NC
COM
Flyback
Diode
(required for
inductive
loads)
+
-
Switching
Voltage
0-24 V-
0-24 V~
Resistive
Load
1.0 A
0.5 A
R