SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom LMR-EO Network
369872c 2 05.21.18
System Start-Up
When the network is supplied by others, the
network must be operational before the certified
Lutron service engineer arrives on-site for system
start-up. The system start-up cannot be completed
without reliable connectivity between the myRoom
processors and the myRoom server.
The customer may be required to schedule an
additional field service visit at an additional charge if
start-up cannot be completed. This may occur if the
network is not installed or if any networking
equipment required to ensure connectivity between
myRoom components is not operational and
properly configured.
Site and Network Access
Certified Lutron service engineers and supporting
personnel must have access to network equipment
required to ensure communication between Lutron
components on the network.
If access to network equipment and/or use of
network analysis tools is not permitted, the
customer must ensure that qualified network
support personnel are on-site and available to
support the certified Lutron service engineer during
the commissioning process. Lack of support may
require scheduling additional field service visits at an
additional charge.
Network Documentation
The network configuration settings of the Lutron
equipment connected to the network; such as, IP
addresses, subnet masks, and gateway addresses,
must be supplied to Lutron prior to the certified
Lutron service engineer’s arrival on site to
commission the system.
Note: The server and each processor will need its
own unique IP address for the system VLAN.
Network Support Disclaimer
When the network is supplied by the customer’s IT
department, Lutron cannot be held responsible for
myRoom system downtime that results from network
downtime.
The network that is used to communicate between
Lutron myRoom equipment is utilized as a control and
a data network. Control networks require more
predictable and consistent response times. Increased
traffic from corporate intranet data can greatly affect
these response times.
Network reliability impacts the collection of data from
the myRoom system. This data is used to generate
reports and to assess system performance. Network
reliability also impacts control functions.
Lutron recommends that the customer employ
qualified network support personnel that will maintain
the reliability and performance of the network post-
occupancy.
Network Equipment Requirements
All network equipment ports connected to the Lutron
myRoom processor are configured to
10 / 100 Mbps data speeds.
Network communications between the myRoom
processor and the Lutron server must not rely on
wireless technology. A wired IEEE 802.3 Ethernet
network is required for the myRoom system to
function.
The myRoom management software uses a browser
based user interface that can be used with wireless
technology, IEEE 802.11 in communications to the
myRoom server.
Physical and administrative access to network
equipment should be limited to authorized personnel
only.