QSNE-4S5-230-D
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Quantum Switching Power Module
3691079d 2 01.20.20
Specifications
Power
• 220–240V~ 50/60Hz
• Single input feed
• 16 A maximum input current
• Lightning strike protection meets ANSI/IEEE standard
C62.41 and IEC 61000-4-5. Can withstand voltage
surges up to 6000V~ and current surges up to
3000A
• ESD-protection exceeds agency requirements per
IEC-61000-4-2
• For ungrounded delta feed applications, contact Lutron
Regulatory Approvals
• Complies with IEC/EN 60669
• Lutron Quality Systems registered to ISO9001.2015
• CE Marked
• RoHS Compliant
Environment
• For thermal specifications, see Mounting section
• Relative humidity: less than 90% non-condensing
• For indoor use only
Terminals
• Mains wiring: 1.0 mm² to 2.5 mm² (18 AWG to 12 AWG)
(single wire, solid or stranded)
• CCI / CCO
wiring: 0.5 mm² to 2.5 mm² (22 AWG to 12 AWG)
(single wire, solid or stranded)
0.5 mm² to 1.5 mm² (20 AWG to 16 AWG)
(two wires, solid or stranded)
• Zone wiring: 1.0 mm² to 2.5 mm² (18 AWG to 12 AWG)
(single wire, solid or stranded)
• QS Link: 0.5 mm² to 2.5 mm² (22 AWG to 12 AWG)
(single wire, solid or stranded)
0.5 mm² to 1.0 mm² (20 AWG to 18 AWG)
(two wires, solid or stranded)
Programming and Compatibility Requirements
• Setup and programming of the Switching Module is
done through the Quantum programming software
• Quantum software version 3.4 or higher is required
QS Link Limits
• A QS link in a Quantum system can have up to
512zones (outputs) and 100devices (required
Quantum processor counts as 1 device on the
QS link)
• Each Switching Module counts as one device toward
the 100device limit, and 4 zones toward the
512 zone limit
• For more information, see the Lutron Residential
and Commercial Systems Rules specification
submittal (P/N 369821) at
www.lutron.com
Output Zone Ratings
• Each zone is rated at 5A for switching. Rated for
resistive, inductive, or capacitive lighting loads as
defined by IEC/EN 60669
• Air gap off per output
• No minimum load per output
• This module is designed to control loads with ratings
as noted in the table below
• Outputs cannot be used to control general purpose
receptacles
Load Type
Relay Ratings
220-240 V~
Tungsten 5 A/zone, 16 A max/module
AC General Use 5 A/zone, 16 A max/module
Electric Discharge Lamp 5 A/zone, 16 A max/module
Electronic Ballast 5 A/zone, 16 A max/module
Resistive 5 A/zone, 16 A max/module
Inductive 5 A/zone, 16 A max/module
Motor
5 A (1/2 HP)/zone,
16 A max/module