SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive PowPak Relay Module with Softswitch Wireless Lighting Control
3691046-04g 2 04.24.19
Specifications
Power
• Operating voltage: 220–240 V~ 50/60 Hz
• Standby Power Consumption < 1.0 W
System Communication
• Operates using Clear Connect RF Technology for
reliable wireless communication; refer to the model
number chart on page 1 for band frequency details
• Wireless sensors and controls must be located within
9 m of the associated control module.
Mounting
• This device can be installed on a junction box through
a 20 mm knockout or with mounting screws. The
device must NOT be mounted inside a metallic
enclosure. Improper installation can result in degraded
wireless communications and intermittent or sustained
communications failures and will not be covered under
warranty. Refer to the installation instructions and
consult local and national electric codes for proper
installation.
• The PowPak should be installed in an accessible
location and in a way that avoids exposure to high
voltage, particularly in those installations where button
programming is used. Record where it is mounted so
that it can be easily located later.
Metal Ceiling Mounting
• Metal ceiling grids must have a > 3 mm gap of
non-metal material which extends the entire length of
the tile on at least one edge. This is often achieved
by foam spacers that are used to prevent tile-to-tile
rattling.
• Metal ceiling grids which are continuous (with no
gap) or those that are interlocked, must have a total
surface area that is less than 81 m
2
for each section.
The overall space can be larger as long as there are
non-metal sections bordering or intersecting the metal
sections.
Environment
• Ambient operating temperature: 0 °C to 55 °C
• 0% to 90% humidity, non-condensing
• For indoor use only
• All drivers and ballasts used with Vive wireless controls
must comply with EN 55015 / CISPR 15
Output Ratings
• 16 A
• No minimum load requirements.
• Load types include (but are not limited to):
Incandescent, MLV, ELV, Resistive, Inductive,
Magnetic fluorescent, Electronic fluorescent
• Motor rating: 6 A 220 –240 V~
Softswitch
• Patented Softswitch circuit eliminates relay arcing at
mechanical contacts
• Extends relay life to an average of 1 million cycles
• Output is non-latching
Key Design Features
• LED status indicator shows current load status and
provides programming feedback
• Power failure memory: If power is interrupted,
connected loads will return to the previous level prior
to interruption
NOTICE: Improper installation can result in
degraded wireless communication and/or
intermittent or sustained communication failures,
and will not be covered under warranty.