SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive
PowPak Dimming Module Wireless Lighting Control
3691045-04f 2 04.26.19
Specifications
Power
• Operating voltage
220 –240V~ 50 / 60Hz
Output Ratings
• Switch rating of 8 A. Rated for resistive or capacitive
loads as defined by IEC/EN 60669-2-1
• 0 –10V- control link for 60 mA maximum output,
source or sink automatically configures
Other Power Specifications
• Standby power:
220–240 V~ <1.0 W
• BTU / hour when fully loaded: 9
• Works with all drivers and ballasts that provide
a current source that is compliant to IEC 60629
AnnexE.2, and whose inrush current does not
exceed NEMA410 standards for electronic
driver / ballast
System Communication
• Operates using Clear Connect RF Technology for
reliable wireless communication; refer to model
number chart on page 1 for frequency band details
• Wireless sensors and controls must be located within
9 m of the associated control module.
Mounting
• This device can be installed on a junction box
through a 20 mm knockout or with mounting
screws. The device must NOT be mounted inside a
metallic enclosure. Improper installation can result in
degraded wireless communications and intermittent
or sustained communications failures and will not
be covered under warranty. Refer to the installation
instructions and consult local and national electric
codes for proper installation.
• The PowPak should be installed in an accessible
location and in a way that avoids exposure to high
voltage, particularly in those installations where
button programming is used. Record where it is
mounted so that it can be easily located later.
Metal Ceiling Mounting
• Metal ceiling grids must have a > 3 mm gap of
non-metal material which extends the entire length of
the tile on at least one edge. This is often achieved
by foam spacers that are used to prevent tile-to-tile
rattling.
• Metal ceiling grids which are continuous (with no
gap) or those that are interlocked, must have a total
surface area that is less than 81 m
2
for each section.
The overall space can be larger as long as there are
non-metal sections bordering or intersecting the
metal sections.
Environment
• Ambient operating temperature: 0°C to 40°C
• 0% to 90% humidity, non-condensing
• For indoor use only
• All drivers and ballasts used with Vive wireless
controls must comply with EN 55015 / CISPR 15
NOTICE: Improper installation can result in
degraded wireless communication and/or
intermittent or sustained communication failures,
and will not be covered under warranty.