Wireless Receptacle
The Wireless Receptacle is a radio-frequency (RF)
receptacle switching solution that is capable of
controlling 15 A or 20 A split or duplex style
receptacles when paired with Pico wireless controls
and Radio Powr Savr occupancy/vacancy sensors.
Communication with RF input devices, such as Pico
wireless controls and / or Radio Powr Savr
occupancy / vacancy sensors, is accomplished using
Lutron Clear Connect RF Technology.
These products are compatible with the Vive wireless
hub which enables a simple setup process using a
standard web browser on any Wi-Fi enabled phone,
tablet, or computer. The hub enables control and
monitoring of all Vive devices. The Vive wireless hub
can be added at any time. For a complete list of
features supported with the Vive wireless hub, see
specification submittal 369902.
NOTE: Not intended for control of permanently
installed lighting fixtures.
Features
•UtilizesLutronClearConnectRFTechnology
•Receiveswirelessinputsfromupto10Picowireless
controls and 10 Radio Powr Savr occupancy / vacancy
sensors
•Capableofswitchinggeneral-purposeloads
•Capableofswitchingdownstreamreceptacles
•AdaptiveSwitching:maximizesrelaylifebyswitching
at the point of minimum energy on the AC power
curve
•Tamperresistant
•RoHSCompliant
•Includesrequiredcontrolledoutletlabelsforcode
compliance
•Includesplasticscrewterminalcovers
15 A Split
Receptacle *
20 A Split
Receptacle *
Colors and Finishes
Gloss Finishes
Add color / finish code to model number
Example: CAR2S-15-DTR-WH
White
WH
Light Almond
LA
Black
BL
Description Model Number Region Operating Voltage Frequency Band
15 A Split (half switching;
single pole / downstream)
CAR2S-15-STR USA,Canada,Mexico
(TA A /NAF TA approved)
120 V~
431.0437.0MHz
15 A Duplex (dual switching;
single pole / downstream)
CAR2S-15-DTR USA,Canada,Mexico
(TA A /NAF TA approved)
120 V~
431.0437.0MHz
20 A Split (half switching;
single pole / downstream)
CAR2S-20-STR USA,Canada,Mexico
(TA A /NAF TA approved)
120 V~
431.0437.0MHz
20 A Duplex (dual switching;
single pole / downstream)
CAR2S-20-DTR USA,Canada,Mexico
(TA A /NAF TA approved)
120 V~
431.0437.0MHz
Model Numbers
15 A Duplex
Receptacle *
20 A Duplex
Receptacle *
* Note: RequiresaU.S.Wallbox2in(51mm)deep
minimum
1
SPECIFICATION SUBMITTAL Page:
Job Name:
Job Number:
Model Numbers:
Vive Wireless Receptacle With Clear Connect Technology Wireless Receptacle Control
3691034d 2 11.29.18
Specifications
Regulatory Approvals
•cULus498B-SA;ListedwithFederalSpecicationWC596
•FCCapproved.ComplieswiththelimitsforaClassB
device, pursuant to Part 15 of the FCC
•IndustryCanada
•NOMandIFT(Mexico)
•ASHRAE90.1compliantwhenusedwithwireless
transmitters or the Vive wireless hub
• CECTitle24compliantwhen used with wireless
transmitters or the Vive wireless hub
• NEMA
® WD-6 compliant
Power
•Operatingvoltage:
120 V ~
50 / 60Hz
System Communication
•OperatesusingClearConnectRFTechnologyforreliable
wireless communication.
•RFrangeis60ft(18m)lineofsight,or30ft(9m),
through walls. For maximum RF range do not place large
office furniture in front of wireless receptacles.
Environment
•Ambientoperatingtemperature:32˚Fto122˚F
(0˚Cto50˚C)
•0%to90%humidity,non-condensing
•Forindooruseonly
Terminals
•Eachterminalacceptsuptotwo14AWGto12AWG
(1.5mm
2
to4.0mm
2
) wires
•Sideorbackwireinstallationcapable
•Solidorstrandedwires
•Copperwiresonly
Switching
•Adaptivezerocrossmaximizesrelaylifebyactively
adapting to variations in relay timing to switch at the
point of minimum energy on the AC power curve.
Load
•Availablein15Aor20Avarieties.Seechartbelow
for maximum load ratings.
•Nominimumloadrequirements.
The Wireless Receptacle may be used with, but is
notlimitedto,thefollowing:
–Monitors –Fans –Humidiers
Note: Refer to the manufacturer’s guidelines for
acceptable switching methods.
TheWirelessReceptacleisNOTsuitableforuse
withdevicesthatrequireanyofthefollowing:
Shut-down process before power is interrupted,
such as computers.
Cool-down process before power is interrupted,
such as projectors.
Programming, such as clocks or DVRs.
Long warm-up cycle.
Ensure that the equipment being controlled
is visible from every control location and that
only suitable equipment is connected to these
controls.
Not for use with loads that present a hazard if
automatically energized. For example, heaters.
Any receptacles that are controlled by an
automatic control device must be marked with
u located on the controlled receptacle outlet
where visible after installation as stated in 2014
NECR Article 406.3(E).
NOTE: Labels with this marking u
are included
with the product.
Mounting
•TypicalU.S.stylewallboxdimensions:
3.0in(76mm)Hx2.0in(51mm)Wx
2.5 in (64 mm) D
Load Type
Relay Ratings
120 V~ 15 A single phase only
CAR2S-15-STR, CAR2S-15-DTR
120 V~ 20 A single phase only
CAR2S-20-STR, CAR2S-20-DTR
Tungsten 1000 W 1500 W
L E D / C F L 3.75 A 5 A
ACGeneralUse 15 A 20 A
Resistive 15 A 20 A
Inductive 15 A 20 A
Motor
0.5HP120V~ 1.0HP120V~
2
SPECIFICATION SUBMITTAL Page:
Job Name:
Job Number:
Model Numbers:
Vive Wireless Receptacle With Clear Connect Technology Wireless Receptacle Control
3691034d 3 11.29.18
Dimensions
U.S. Style (faceplate sold separately)
Measurementsshownas:in(mm)
Side View
2.9
(75)
1.4
(36)
0.4
(9)
4.7
(119)
2.7
(69)
1-Gang
Range Diagrams
1
All Wireless Transmitters must be installed within 60 ft
(18 m) line of sight, or 30 ft (9 m), through walls of the
Wireless Receptacle.
2
For maximum RF range do not place large office
furniture in front of wireless receptacles.
30 ft (9 m)
Maximum
1
Pico
wireless
control
Radio Powr Savr
Occupancy Sensor
Wireless
Receptacle
2
Note: RequiresaU.S.Wallbox
2 in (51 mm) deep minimum.
Top View
1.75
(45)
3
SPECIFICATION SUBMITTAL Page:
Job Name:
Job Number:
Model Numbers:
Vive Wireless Receptacle With Clear Connect Technology Wireless Receptacle Control
3691034d 4 11.29.18
System Diagram
Radio Powr Savr occupancy/vacancy sensor
(up to 10)
Pico wireless control (up to 10)
To power source
and load
Radio Powr Savr
occupancy/
vacancy sensor
Vive Wireless
Receptacle
QSM(Connected
to Quantum,
GRAFIKEyeQS,
orEnergiSavr
Node standalone)
A single Radio Powr
Savr occupancy/vacancy
sensor can communicate
to multiple systems
Multi-system
Application Example
Default Operation
Transmitting Device Transmitted Command
Relay Default Action
Pico wireless control
(a 2 button Pico wireless control
[PJ2-2B-XX] is recommended).
On Close
Off Open
Raise Close
Lower No Action
Preset Close
Radio Powr Savr
occupancy sensor
Occupied Close
Unoccupied Open
Radio Powr Savr
vacancy sensor
Occupied Close
Unoccupied Open
4
SPECIFICATION SUBMITTAL Page:
Job Name:
Job Number:
Model Numbers:
Vive Wireless Receptacle With Clear Connect Technology Wireless Receptacle Control
3691034d 5 11.29.18
ATTENTION INSTALLER
Any receptacles that are
controlled by an automatic
control device must be
marked with “u” located on
the controlled receptacle
outlet where visible after
installation as stated in 2014
NECRArticle406.3(E).
NOTE: Labels with the u
marking are included with the
product.
u
u
u
u
LineIn/Hot(Black)
Load/SwitchedLine/Hot(Red)
Wireless Receptacle
(Split)
1,4
Optional
Downstream-Controlled
Split Receptacle
1,2,3
Neutral (White)
120 V~
50/60Hz
*
*
Before After
1
20 A version shown in above diagram.
2
Downstream receptacles are optional.
3
Whenusingsplitdownstreamreceptacle,ensuretheconnectinglinkisbrokentoenableindependentLine/HotandSwitchedLine/Hotconnections.
4
Snap the plastic screw terminal covers (3 included) onto the metal terminals before placing unit into wallbox.
Split Wireless Receptacle with a Downstream-Controlled Split Receptacle
3
Wiring Diagrams
Duplex Wireless Receptacle with a Downstream-Controlled Duplex Receptacle
Load/SwitchedLine/Hot(Red)
u
u
u
u
LineIn/Hot(Black)
Wireless Receptacle
(Duplex)
1,4
Optional
Downstream-Controlled
Duplex Receptacle
1,2
Neutral (White)
120 V~
50/60Hz
ATTENTION INSTALLER
Any receptacles that are
controlled by an automatic
control device must be
marked with “u” located on
the controlled receptacle
outlet where visible after
installation as stated in 2014
NECRArticle406.3(E).
NOTE: Labels with the u
marking are included with the
product.
Important Note
WARNING: Entrapment Hazard. To avoid the risk of entrapment, serious injury, or death, these controls must not be used to control equipment which
isnotvisiblefromeverycontrollocationorwhichcouldcreatehazardoussituationssuchasentrapmentifoperatedaccidentally.
WARNING: Fire Hazard. To avoid the risk of fire, serious injury, or death, these controls must not be used to control equipment which is not visible
fromeverycontrollocationorwhichcouldcreatehazardoussituationssuchasfireifoperatedaccidentally.
Examplesofsuchequipmentwhichmustnotbeoperatedbythesecontrolsinclude(butarenotlimitedto)motorizedgates,industrialdoors,space
heaters,etc.Itistheinstaller’sresponsibilitytoensurethattheequipmentbeingcontrolledisvisiblefromeverycontrollocationandthatonlysuitable
equipment is connected to these controls. Failure to do so could result in serious injury or death.
)Lutron,Lutron,ClearConnect,Quantum,GRAFIKEye,andPicoaretrademarksofLutronElectronicsCo.,Inc.,registeredintheU.S.andothercountries.
Vive,EnergiSavrNode,andRadioPowrSavraretrademarksofLutronElectronicsCo.,Inc.
NECisaregisteredtrademarkofNationalFireProtectionAssociation,Quincy,Massachusetts.
ULisatrademarkofULLLC.
u
u
5