SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem® Cable Low Voltage Cables
369-385 Rev B 1 02.02.11
EcoSystem Cable
Custom designed cable, for use with EcoSystem
components, improves system performance and
decreases installation time. Cable is available for
sensor connections and EcoSystem bus connections.
Both types are available in plenum versions.
Features
•InternalconductorsmatchEcoSystem device
terminal and lead color scheme.
•Eachconductorsizedfordirectconnectionto
EcoSystem ballast and module terminals.
•ThreetypesofEcoSystem Bus Cable:
Non-plenum bus cable (CL3R), for Class 2 applications
Non-plenumbuscable(TC),forClass1applications
Plenum bus cable (CL3P) for plenum Class 2 applications
•TwotypesofEcoSystem Class 2 Sensor Cable:
Non-plenum sensor cable (CL3)
Plenum sensor cable (CL3P)
•Allplenumcableisratedtoamaximumof300V
•Non-plenumcableisratedtoamaximumof300Vor
600Vdependantuponapplication
•Eachofferingisspooledto1000ft(305m)andbased
upon industry standards of plus 10%, minus 10% on
all shipments
EcoSystem Class 2 Sensor Cable
C-CBL-522S-WH-1 (non plenum)
C-PCBL-522S-CL-1 (plenum)
EcoSystem Bus Cable
C-CBL-216-GR-1 (non-plenum, Class 2)
C-CBL-216-WH-C1 (non-plenum, Class 1)
C-PCBL-216-CL-1 (plenum, Class 2)
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem® Cable Low Voltage Cables
369-385 Rev B 2 02.02.11
EcoSystem Bus Cable Specifications
C-PCBL-216-CL-1
General Description
TwoconductorEcoSystem Bus Cable for Plenum Spaces
16AWG(1.5mm
2
)solidbarecopper,FEPinsulatedconductors
2 single conductors cabled
Clear0.017in(0.43mm)thickFEPjacket—sheathed
Allexternalmarkingsusewhiteink
Electrical
Maxoperatingvoltage 300VRMS CL3P
Maxcontinuouscurrentperconductor 10A at77°F(25°C)
NominalconductorDCresistance 4Ohm/1000ft(304.8m) at68°F(20°C)
Physical
TempRating -94°Fto392°F(-70°Cto200°C)
Nominal Diameter 0.173 in (4.39 mm)
MaxPullTension 45lb(20.41kg)
Min Bend Radius 1.75 in (44.5 mm)
InsulationMaterial FEP
JacketMaterial FEP
Listings
ULlistedasTypeCL3PorCMPc(UL)us,FT-6
NFPA262
UL444 and UL13
CSA-C22.2No.214
RoHS Compliant
Colors
Jacket—Clear(CL)
Conductor Color Ballast Terminal
Purple(PL) E1
Purple+whitestripe(PL/WH) E2
Jacket Markings
LUTRONC-PCBL-216-CL-12/16AWG(ULFile#)(UL)CL3P
orCMPc(UL)us200°CFT-6RoHSCOMPLIANT
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem® Cable Low Voltage Cables
369-385 Rev B 3 02.02.11
EcoSystem Bus Cable Specifications (continued)
C-CBL-216-GR-1
General Description
For running EcoSystem link with other Class 2 wires in non-plenum applications
16AWG(1.5mm
2
)solidbarecopper,PVCinsulatedconductors
2 single conductors cabled
Gray0.03in(0.76mm)thickPVCjacket—sheathed,UVstabilized
Allexternalmarkingsuseblackink
Electrical
Maxoperatingvoltage 300VRMS CL3R/CMG
600VRMS AWMStyle20811
Maxcontinuouscurrentperconductor 13A at77°F(25°C)
NominalconductorDCresistance 4Ohm/1000ft(304.8m) at68°F(20°C)
Physical
TempRating -4°Fto221°F(-20°Cto105°C)
Nominal Diameter 0.300 in (7.62 mm)
MaxPullTension 62.5lb(28.35kg)
Min Bend Radius 1.75 in (44.5 mm)
InsulationMaterial PVC
JacketMaterial PVC
Listings
ULTypeCL3R
CMG (C)UL
FT-4FlameRating
AWMStyle20811
UL1666VerticalShaft
RoHS Compliant
Colors
Jacket—Gray(GR)
Conductor Color Ballast Terminal
Purple(PL) E1
Purple+whitestripe(PL/WH) E2
Jacket Markings
C-CBL-216-GR-1LUTRON2/16AWGCL3R90°C(UL)E171202
or CMG c(UL)
orAWMSTYLE20811105°C600VDATECODEFT-4RoHSCOMPLIANT
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem® Cable Low Voltage Cables
369-385 Rev B 4 02.02.11
EcoSystem Bus Cable Specifications (continued)
C-CBL-216-WH-C1
General Description
For running EcoSystem link with other line-voltage wires (Class 1) in non-plenum applications
16AWG(1.5mm
2
)solidbarecopper,PVC/Nyloninsulatedconductors
2 single conductors cabled
White0.045in(1.1mm)thickPVCjacket—sheathed,UVstabilized
Allexternalmarkingsuseblackink
Electrical
Maxoperatingvoltage 600VRMS TC
600VRMS ULSTANDARD62,TYPETFN
Maxcontinuouscurrentperconductor 20A at77°F(25°C)
NominalconductorDCresistance 4Ohm/1000ft(304.8m) at68°F(20°C)
Physical
TempRating -4°Fto194°F(-20°Cto90°C)
Nominal Diameter 0.299 in (7.59 mm)
MaxPullTension 41lb(18.6kg)
Min Bend Radius 1.75 in (44.5 mm)
InsulationMaterial PVCandNylon
JacketMaterial PVC
Listings
ULTypeTCPerULStandard1277fortraycables
CSAListedCICC22.2No.239-09
ULApprovedforSunlightResistance
IndividualConductorsareratedTFN
CablemeetsIEEE383&UL158170,000BTU/HRFlameTestRequirements
CablemeetsICEAS-95-658,whereapplicable
FT-4FlameRating
RoHS Compliant
Colors
Jacket—White(WH)
Conductor Color Ballast Terminal
Purple(PL) E1
Purple+whitestripe(PL/WH) E2
Jacket Markings
C-CBL-216-WH-C1LUTRON(ULFile#)2/16AWG2CTFN(UL)TYPEC600V90°CDRYPVCJACK-
ETSUNRES
orCSALL226471CIC(TC)FT-4RoHSCOMPLIANT
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem® Cable Low Voltage Cables
369-385 Rev B 5 02.02.11
EcoSystem Class 2 Sensor Cable Specifications
C-PCBL-522S-CL-1
General Description
5 conductor EcoSystem sensor cable for plenum spaces
22AWG(0.34mm
2
)solidbarecopper,FEPinsulatedconductors
Overallaluminum-polymerfoilshield,plus24AWG(0.25mm
2
) copper drain wire
Clear0.012in(0.3mm)thickFEPjacket—sheathed
Allexternalmarkingsusewhiteink
Electrical
Maxoperatingvoltage 300VRMS CL3P
Maxcontinuouscurrentperconductor 4A at77°F(25°C)
NominalconductorDCresistance 16.5Ohm/1000ft(304.8m) at68°F(20°C)
Physical
TempRating -94°Fto392°F(-70°Cto200°C)
Nominal Diameter 0.140 in (3.56 mm)
MaxPullTension 36.0lb(16.33kg)
Min Bend Radius 1.50 in (38.1 mm)
InsulationMaterial FEP
JacketMaterial FEP
Listings
ULlistedasTypeCL3PorCMPc(UL)us,FT-6
NFPA262
UL444 and UL13
CSA-C22.2No.214
RoHS Compliant
Colors
Jacket—Clear(CL)
Conductor Color Ballast Terminal
Red +20V
Black Common
White IR
Blue Occupancy
Yellow Daylight
Jacket Markings
LUTRONC-PCBL-522S-CL-1(ULFile#)22AWG5CSHIELDED(UL)CL3P
orCMPc(UL)usFT-6200°CRoHSCOMPLIANT
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem® Cable Low Voltage Cables
369-385 Rev B 6 02.02.11
EcoSystem Class 2 Sensor Cable Specifications (continued)
C-CBL-522S-WH-1
General Description
5 conductor EcoSystem sensor cable for non-plenum applications
22AWG(0.34mm
2
)solidbarecopper,PVCinsulatedconductors
Overallaluminum-polymerfoilshield,plus24AWG(0.25mm
2
) copper drain wire
White0.047in(1.2mm)thickPVCjacket—sheathed,UVStabilized
Allexternalmarkingsuseindentedprint
Electrical
Maxoperatingvoltage 300VRMS CL3
600VRMS AWM20811
Maxcontinuouscurrentperconductor 4A at77°F(25°C)
NominalconductorDCresistance 16.5Ohm/1000ft(304.8m) at68°F(20°C)
Physical
TempRating -4°Fto221°F(-20°Cto105°C)
Nominal Diameter 0.297 in (7.54 mm)
MaxPullTension 36.0lb(16.33kg)
Min Bend Radius 3 in (76.2 mm)
InsulationMaterial PVC
JacketMaterial PVC
Listings
ULTypeCL3andCM
ULrecognizedAWMStyle20811
UL444, UL13 and UL758
CSA-C22.2No.214
ROHS Compliant
Colors
Jacket - White (WH)
Conductor Color Ballast Terminal
Red +20V
Black Common
White IR
Blue Occupancy
Yellow Daylight
Jacket Markings
LUTRONC-CBL-522S-WH-1PELV/SELV(ULFile#)22AWG5CSHIELDED(UL)CL3
orCMc(UL)us75°CORяUAWM20811105°C600VRoHSCOMPLIANT
6