Contractor's Material and Test Certificate for Aboveground Piping
PROCEDURE
Upon completion of work, inspection and tests shall be made by the contractor’s representative and witnessed by an owner’s representative. All defects shall be corrected and
system left in service before contractor’s personnel finally leave the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners and the contractor. It is understood the owner’s
representative’s signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with approving authorities requirements or
local ordinances.
Property Name
Date
Property Address
City
Zip
PLANS
Accepted by approving authorities(names)
Address
Installation conforms to accepted plans Yes No
Equipment used is approved?
Yes
No
If no, explain deviations
INST RUCT IONS
Has person in charge of fire equipment been instructed as to location of
control valves and care and maintenance of this new equipment?
Yes
No
If no, explain
Have copies of the following been left on the premises?
1. System Components Instructions
Yes
No
2. Care and Maintenance Instructions
Yes
No
3. NFPA 25
Yes
No
LOCAT ION
OF SYST EM
Supplies buildings
SPRINKLERS
Make
Model
Year of Manufacture
Orifice Size
Quantity
Temperature Rating
PIPE AND
FIT T INGS
Type of pipe
Type of fittings
ALARM
VALVE
OR FLOW
INDICAT OR
ALARM DEVICES
Maximum time to operate through test connection
Type
Make
Model
Minutes
Seconds
DRY PIPE
OPERAT ING
T EST
DRY VALVE
Q.O.D.
Make
Model
Serial No.
Make
Model
Serial No.
Time to trip through
test connection
1,2
Water Pressure
Air Pressure
Trip Point Air
Pressure
Time water reached
test outlet
1,2
Alarm operated
properly
Minutes
Seconds
psi
psi
psi
Minutes
Seconds
Yes
No
W ithout Q.O.D.
W ith Q.O.D.
If no, explain
DELUGE &
PREACT ION
VALVES
Operation
Pneumatic
Electric
Hydraulic
Piping supervised
Yes
No
Detection media supervised
Yes
No
Does valve operate from the manual trip, remote, or both control stations?
Yes
No
Is there an accessible facility in each circuit
for testing?
Yes
No
If no, explain
Make
Model
Does each circuit operate
supervision loss alarm?
Does each circuit operate valve
release?
Maximum time to operate release?
Yes
No
Yes
No
Minutes
Seconds
1
Measured from time inspector’s test connection is opened.
2
NFPA 13 only requires the 60-second limitation in specific sections
SF041 Rev. 07/09
Contractor's Material and T est Certificate for Aboveground Piping Page 1 of 2
PRESSURE
REDUCING
VALVE TEST
Location &Floor
Make & Model
Setting
STATIC PRESSURE
RESIDUAL PRESSURE (flowing)
FLOW RATE
Inlet (psi)
Outlet (psi)
Inlet (psi)
Outlet (psi)
Flow (GPM)
TEST
DESCRIPTION
HYDROSTATIC: Hydrostatic tests shall be made at not less than 200 ps i (13.6 bars) for two hours or 50 psi (3.4 bars) above static pressure in excess of
150 psi (10.2 bars) for two hours. Differential Dry-Pipe Valve clappers shall be left open during test to prevent damage. All aboveground piping leakage
shall be stopped.
PNEUMATIC: Establish 40 psi (2.7 bars) air pressure and measure drop, which shall not exceed 1 -1/2 psi (0.1 bars) in 24 hours. Test pressure tanks at
normal water level and air pressure and measure air pressure drop, which shall not exceed 1 -1/2 psi (0.1 bars) in 24 hours.
TESTS
All pipe hydraulically tested at: psi (_______ bar) for hrs
Dry Pipe pneumatically tested
Yes
No
Equipment operates properly
Yes
No
If no, state reason
Do you certify as the sprinkler contractor that additives and corrosive chemicals, sodium silicate or derivatives of sodium s ilicate, brine, or other corrosive
chemicals were not used for testing systems or stopping leaks? Yes No
DRAIN
TEST
Reading of gage located near
water supply test connection: psi (________ bar)
Residual pressure with valve
in test connection open wide. psi (________ bar)
Underground mains and lead in connections to system risers flushed before connection made to sprinkler piping
Verified by copy of the Contractor’s Material & Test
Yes
No
Certificate for Underground Piping.
Flushed by installer of underground sprinkler piping.
Yes
No
Other, explain
If powder driven fasteners are used in concrete, has representative
sample testing been satisfactorily completed?
Yes
No
If no, explain
BLANK TESTING
GASKETS
Number used
Locations
Number removed
WELDING
Welded piping Yes No
If yes…
Do you certify as the sprinkler contractor that welding procedures comply with the requirements of
at least AWS B2.1?
Yes
No
Do you certify that the welding was performed by welders qualified in compliance with the requirements
of at least AWS B2.1?
Yes
No
Do you certify that the welding was carried out in compliance with a documented quality control procedure
to ensure that all discs are retrieved, that openings in piping are smooth, that slag and other welding
residue are removed, and that the internal diameters of piping are not penetrated?
Yes
No
CUTOUTS
(DISCS)
Do you certify that you have a control feature to ensure that all cutouts (disks) are retrieved? Yes No
HYDRAULIC
DATA
NAMEPLATE
Nameplate provided?
Yes
No
If no, explain
REMARKS
DATE left in service with all control valves open: _______________________________________________________
________________________________________________________________________________
________________________________________________________________________________
Signature
Name of sprinkler contractor
C of R No. SCR-
Contractor’s Address
City
State
Zip
Tests witnessed by
For property owner (signed) Title Date
For sprinkler contractor (signed) Title Date
Additional explanation and notes
RME
I certify that the information herein is true and that this sprinkler system was installed in accordance with
Chapter 6003, Texas Insurance Code and the rules and standards adopted by the State Fire Marshal’s Office.
Responsible Managing Employee (signature)
CERTIFICATION
Responsible Managing Employee (print or type name)
RME License Number
Date
DIST RIBUT ION: Original COPY 1 Posted at site or give to owner COPY 2 for the installing firm in file accessible to SFMO
COPY 3 for local approving authority within 10 days after completion
SF041 Rev. 07/09 Contractor's Material and T est Certificate for Aboveground Piping Page 2 of 2