SPECIFICATION SUBMITTAL
Control Unit
Specifications
Occupancy Sensor(s)
• The GRAFIK Eye QS control unit works with occupancy
sensors through either:
– Scene Control: Up to 16 sensors activate user-selected
occupancy and vacancy scenes.*
– Zone Control: up to four sensors per zone activate
user-selected occupancy and vacancy zone levels.
• Occupancy sensors may include:
– Contact closure sensors wired to CCI input on back of
GRAFIK Eye QS control unit
– Wired or wireless sensors connected QS sensor
module (QSM)
• If any sensor in a group detects occupancy, then the
GRAFIK Eye QS control unit will go to the designated
occupancy scene or zone level.
• If all sensors in a group detect vacancy, then the
GRAFIK Eye QS control unit will go to the designated
vacancy scene or zone level.
• Low battery: the Diagnostics screen will display a low
battery symbol when applicable.
• If the GRAFIK Eye QS control unit does not receive a
signal from an occupancy sensor on the link (usually due
to a dead battery), the lights associated with that sensor
will go to the occupied level.
Daylight Sensor(s)
• The GRAFIK Eye QS control unit allows daylight sensors
to control one or more lighting zones to adjust electric
light levels based on measured daylight levels.
• Daylight sensors may include:
– Wired or wireless sensors connected to a QS sensor
module (QSM)
• A daylight sensor can control one or more
GRAFIK Eye QS control unit zones:
– Each zone can be calibrated to target light levels
– A zone can be controlled by no more than one
daylight sensor
• Daylight control can be enabled or disabled on a
scene-by-scene basis
– By default, daylight control is enabled in all scenes
Note: Daylight control through the GRAFIK Eye QS control
unit only affects select lighting loads. Shade groups
cannot be controlled by daylight sensors. Daylighting does
not affect DMX or RGB/CMY DMX loads.
Daylighting of Remote Zones linked to Energi Savr Node
zones must be configured at the Energi Savr Node unit or
through the Energi Savr Node app for iPod.
Contact Closure Input (CCI)
with Power Supply Output
• Each GRAFIK Eye QS control unit has one contact closure
input (Terminal A).
– The attached device must provide a dry contact closure
or solid-state output.
– Input is miswire-protected up to 36 V-.
• The contact closure is capable of accepting the following
types of inputs:
– Maintained (default): The GRAFIK Eye QS control unit
will act on both a contact closure and a contact
open/release event.
– Momentary: The GRAFIK Eye QS control unit will act on
only contact closure events.
• Each GRAFIK Eye QS control unit can supply
50mA maximum at 24 V-.
– Useful for powering occupancy sensors.
– An auxiliary power supply must be used if the device
requires more than 50 mA.
• The CCI is capable of operating in the following modes
– Occupancy: If an occupancy sensor is wired directly to
the GRAFIK Eye QS control unit.
– Emergency: This setting allows the GRAFIK Eye QS
control unit to work with a LUT-ELI. When an emergency
situation is detected, all lights will go to full on, and no
operations will be allowed until the emergency signal
is cleared.
– Afterhours: Allows the CCI to start and end the
afterhours mode.
– Timeclock: Allows the CCI to enable and disable
the timeclock.
– Scene Lockout: Prevents the user from making any
changes to the control unit. The current scene will stay
on until the CCI enables normal operation.
– Save Never: Prevents any changes from being saved
while the CCI is being used.
– Disable CCI: The CCI will have no effect on the system
and will not appear on the list of available sensors.
Security Lockout Password
• A 4-character password (using characters A to Z and
0to 9) can be enabled/disabled to lock out access to the
Programming Menu.
• By default there is no password enabled on the
GRAFIKEye QS control unit.
• If case the 4-digit password is forgotten, contact Lutron
Customer Assistance to regain access.
* Applicable only to units that ship with firmware version 9.002 and higher. Previous versions support up to 4 sensors.