SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QuantumR QSW-S-PP-A Software
369661c 1 10.23.12
Q-AdminT Software / QuantumR Processor Software:
Shade Control and Monitoring
Description
Q-AdminT is the QuantumR software that allows facility
managers to coordinate electric shades for maximum
energy efficiency, comfort, and productivity.
Control and Monitoring Basic System View
The Q-AdminT system navigation and status reporting
is performed using a tree view of the building.
Optional Graphical Floorplan View
The Q-AdminT system navigation and status reporting
is performed using customized CAD-based drawings
of your building. Pan and Zoom features allow for
easy navigation. Basic system view is always available.
Contact Lutron for custom pricing.
Control of Shades
Allows the building manager to control and monitor the
shading system as follows:
•Areashadegroupscanbemonitoredforcurrent
preset or position.
•Areashadegroupscanbeopened/closed,senttoa
preset, or sent to a specific position.
Scheduling
Allows the building manager to schedule time of day
and astronomic timeclock events to automate shade
functions for shades not operating as a part of the
HyperionT system.
Diagnostics
Allows the building manager to check on the status of
all equipment in the system. Devices will be listed with
a reporting status of OK, Missing, or Unknown.
HyperionT Solar Adaptive Algorithm
Maximizes the use of available daylight to produce a
comfortable and productive visual environment that
reduces glare and saves energy.
During the day, the HyperionT algorithm calculates
the sun’s position in the sky relative to the building
and then creates a unique shade adjustment
schedule for each façade. It adjusts the position of
the shade to limit direct sunlight penetration, which
can cause uncomfortable glare and heat gain. At
night, all shades controlled by HyperionT can be set
to a fixed position (open or closed).
The shade movements are calculated based on specific
building characteristics that control the solar tracking
software. These characteristics are comprised of the
latitude and longitude of the building’s location, the
directional orientation of each façade, the dimensions
of the windows, the desired depth of solar penetration,
and the preferred number of shade movements
throughout each day.
Hyperion
TM can be manually overriden using a variety
of personal control options. Personal controls include
wired and wireless keypads, the Q-Control+ iPad
app, and the Personna® PC web-based personal
control software. By adding Radio Shadow Sensors
(LRFX-SSW-XX), HyperionTM can also be automatically
overriden during cloudy days or when shadows are
cast by neighboring buildings. When automatically
overridden, shades are opened to their configured visor
position. Rooftop sensor solutions are also available.
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QuantumR QSW-S-PP-A Software
369661c 2 10.23.12
Reporting
Allows the building manager to gather real-time and
historical information about the system as follows:
Activity Report: Shows what activity has taken place
over a period of time for one or more areas. Activity
includes occupant activities (i.e. wall controls being
pressed),buildingmanageroperation(controlling/
changing areas using the Q-AdminT Software), and
device failures (keypads, shades, etc., that are not
responding).
Administration
The administration tab appears only for users who
have been assigned the role of “Admin” when their
user account was created or last modified. The
administration features are as follows:
•Users:Allowsnewuseraccountstobecreated,
and existing user accounts to be edited.
•PublishGraphicalFloorplan:Allows“Admin”user
to publish new graphical floorplan files.
•Back-UpProjectDatabase:Allows“Admin”userto
back up the project database. The project database
holds all the configuration information for the system,
including keypad programming, area scenes,
daylighting, occupancy programming, emergency
levels, night lights, and timeclock. The Q-AdminT
Software can be used to adjust some of these
settings, and thus it is important to back up the
project database prior to changing settings.
•PublishProjectDatabase:Allowsthe“Admin”user
to send a new project database to the server and
upload the new configuration to the system. The
project database holds all the configuration
information for the system, including keypad
programming, area scenes, daylighting, occupancy
programming, emergency levels, night lights,
and timeclock.
Required Hardware
•LutronR QuantumR light management hub
Optional Hardware
•LutronR Q-AdminT client PC
Q-AdminT Software
•LutronwillinstallandconfiguretheQ-AdminT
client software on up to 3 client PCs on site during
the system start-up visit(s). If additional client PC
installations are required, contact Lutron for pricing.
•ThreeQ-AdminT client sessions can be connected
to the Q-Manager
TM server at any given time,
however changes can only be made by 1 session at
a time.
Licenses Required
•Onelicenseperprocessor
2