QS System QSE-IO Control Interface
369374d 1 02.02.2018
QSE-IO Control Interface
The QSE-IO contact closure interface provides
integration with third-party equipment requiring
contact closure input / output, including occupancy
and vacancy sensors; motorized projection screens,
skylights, and window shades; AV equipment; security
systems; movable partition walls; and timeclocks. One
QSE-IO interface provides five (5) dry contact closure
outputs and five (5) inputs.
For complete functionality, programming
instructions, and detailed DIP switch settings, see
the QSE-IO Programming Guide,
www.lutron.com/TechnicalDocumentLibrary/040391.pdf
Features
Integrates a QS control system with equipment that
has contact-closure inputs and outputs.
Provides five inputs and five dry contact closure
outputs.
Provides both normally open (NO) and normally closed
(NC) contacts.
May be programmed to control or be controlled on a
QS system.
QSE-IO
24 - 36 V- 100 mA
SELV / PELV / NEC Class 2
R
www.lutron.com/qs
+ 1.610.282.3800
+ 1.800.523.9466
lutron.com
8 7 6 5 4 3 2 1
PGM
CCO 5
CCO 4
CCO 3
CCO 2
CCO 1
Status
0 27557 61323 1
4321
COM
V+
MUX
MUX
QS
CCO 1 NC
CCO 1 NO
CCO 2 NC
CCO 2 NO
1-2 COM
CCO 3 NC
CCO 4 NO
CCO 3 NO
CCO 4 NC
3-4 COM
CCO 5 NC
5 COM
CCO 5 NO
CCI 1
CCI 2
CCI 3
CCI 4
COM
CCI 5
V
R
V
0-36 V-
0-36 V~ ½ A
R
1 A
O
N
QSE-IO Contact Closure Interface
1
R
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS System QSE-IO Control Interface
369374d 2 02.02.2018
Specifications
Regulatory Approvals
• UL
® Listed
• cUL
® Listed
• CE compliant
Power
SELV / PELV / NEC
® Class 2
Operating voltage: 24–36 V- 100 mA
QS Link Limits
The QS wired communications link is limited to
100 devices and 100 zones. Each QSE-IO control
interface counts as 1 device and 5 zones.
Each QSE-IO control interface consumes 3 Power
Draw Units (PDU) on the QS link. Refer to the QS
Link Power Draw Units Specification Submittal
(P/N 369405) at www.lutron.com for more
information.
The maximum wiring length for the QS link is
2000 ft (610 m).
Environment
32 °F to 104 °F (0 °C to 40 °C).
• Relative humidity less than 90% non-condensing.
Indoor use only.
Unit generates heat, maximum 8 BTU / hr.
Functionality and Operating Modes
Using the inputs, contact closures in other
equipment can operate control units to:
– Select scenes
– Adjust scenes to reflect status of movable walls
Toggle any combination of zones in the system
between Off and a configurable preset value
Turn lights on or off and / or move shades based
on room occupancy
Perform special functions such as sequencing,
panic, control lockout, or timeclock disable
Using the outputs, scene and / or zone changes in
control units can:
– Trigger outputs to control other equipment
– Provide status feedback to other equipment
Functionality and Operating Modes
(continued)
Using the inputs, contact closures in other equipment
can operate Sivoia
® QS window treatments to:
– Open or close.
– Raise, lower, or stop.
– Select one of three adjustable presets.
Using the outputs, key presses on QS window
treatment keypads or GRAFIK Eye
® QS window
treatment buttons can:
Trigger outputs to other motorized window treatment
equipment
• Scene selection
• Occupancy sensor
• Zone toggle
• Shade input
• Special functions
• Shade output
• Partitioning
For a full list of functionality and operating modes,
please see the Operating Modes and Dipswitch
Settings table on Pages 8 and 9
Requirements
• QS Link Power Supply, such as a:
- GRAFIK Eye
® QS
- QS Link power supply, such as the QSPS-P1-1-50
- Energi Savr Node
TM QS
- Quantum
® light management hub
• QS Communication Link (SELV / PELV/NEC
® Class 2)
(see QS Link Wire Sizes table)
2
R
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS System QSE-IO Control Interface
369374d 3 02.02.2018
Supply
Voltage
0 – 24 V-
0 – 24 V~
Resistive
Load
1.0 A
0.5 A
R
Output Ratings
+
-
24 V-
max.
Inductive
Load
Flyback
Diode
(required for
inductive
loads)
QSE-IO
Output
NO
NC
Specifications (continued)
Five Input Terminals
Accept maintained inputs and momentary inputs
with
40 msec minimum pulse times
Off-state leakage current must be less than 100 μA
Open circuit voltage: 24 V- maximum
Inputs must be dry contact closure, solid state,
open collector, or active-low (NPN) / active high
(PNP) output
Open collector NPN or active-low on-state voltage
must be less than 2 V- and sink 3.0 mA
Open collector PNP or active-high on-state voltage
must be greater than 12 V- and source 3.0 mA
Five Output Terminals
Provide selectable maintained or momentary
(1/4 second) outputs (SELV / PELV / NEC
® Class 2
rated only)
The QSE-IO is not rated to control unclamped,
inductive loads. Inductive loads include, but are not
limited to, relays, solenoids, and motors. To control
these types of equipment, a flyback diode must be
used (DC voltages only). See "Terminal Locations"
Output relays are non-latching (if relays are closed
and power is lost, relays will open)
Status LEDs
Five Status LEDs light when associated output is
active (on)
3
R
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS System QSE-IO Control Interface
369374d 4 02.02.2018
Dimensions
Dimensions are in inches (mm)
2.5
(63)
3.75
(95)
4.25
(108)
5.25
(134)
1.0
(27)
Mounting holes
Terminal
blocks
on this side
LEDs and addressing
switches on this side
0.3125
(9) dia.
0.1875 (5)
dia.
0.1875
(5) dia.
0.25
(6)
#6 or #8 (M3 or M4)
screw recommended
Mounting Hole Detail
Mounting Options
Mounting Methods
LUT-19AV-1U
2
LUT-5x10-ENC
Control Interface
Wall
1
3
Mount where terminal blocks, switches, and LEDs
are accessible. Strip 3/8 in (10 mm) of insulation
from wires. Each data link terminal will accept up
to two 18 AWG (1.0 mm
2
) wires. Connect wiring as
shown on the Wiring page. LED 1 lights
continuously (Power) and LED 7 blinks rapidly
(Data Link RX) when the SELV / PELV / NEC® Class
2 Data Link is installed correctly. Choose from the
following mounting methods:
1 Direct Wall Mounting
Mount the control interface directly on a wall, as
shown in Mounting Methods at right, using screws
(not included). When mounting, provide sufficient
space for connecting cables.
2 Rack Mounting
Place the unit in the LUT-19AV-1U AV rack using
screws provided with the unit. The LUT-19AV-1U
will hold up to four units.
3 Enclosed Wall Mounting
If conduit is desired for wiring, use the
LUT-5x10-ENC to mount one unit.
4
R
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS System QSE-IO Control Interface
369374d 5 02.02.2018
Terminal Locations
4321
Relay 1 NC
Relay 1 NO
Relay 1 & 2 Common
Relay 2 NC
Relay 2 NO
Relay 3 NC
Relay 3 NO
Relay 3 & 4 Common
Relay 4 NC
Relay 4 NO
Relay 5 NC
Relay 5 NO
Relay 5 Common
Input 1
Input 2
Input 3
Input 4
Input 5
Common
CCI and CCO terminals each hold one
28 to 16 AWG (0.08 to 1.5 mm
2
) wire
QS Data Link (to control
units, processor, and
wallstations)
1: Common
2: V+
3: MUX
4: MUX
CCO 1 NC
CCO 1 NO
1-2 COM
CCO 2 NC
CCO 2 NO
CCO 3 NC
CCO 3 NO
3-4 COM
CCO 4 NC
CCO 4 NO
CCO 5 NC
CCO 5 NO
5 COM
CCI 1
CCI 2
CCI 3
CCI 4
CCI 5
COM
QSE-IO
Program
Button
1234567
DIP switches
LED 1: CCO 1
LED 2: CCO 2
LED 3: CCO 3
LED 4: CCO 4
LED 5: CCO 5
LED 6: Unused
LED 7: Status
Note: CCO LED is ON when CCO NO
(normally open contact) is closed.
}
Contact Closure Outputs
Contact
Closure
Inputs
LED and DIP Switch Locations
QS Link Wire Sizes (check compatibility in your area)
QS Link Wiring Length Wire Gauge LutronR Cable Part Number
< 500 ft (153 m)
Power (terminals 1 and 2)
1 pair 18 AWG (1.0 mm
2
)
GRX-CBL-346S (non-plenum)
GRX-PCBL-346S (plenum)
Data (terminals 3 and 4)
1 twisted, shielded pair 22 AWG (0.5 mm
2
)
500 to 2000 ft
(153 to 610 m)
Power (terminals 1 and 2)
1 pair 12 AWG (4.0 mm
2
)
GRX-CBL-46L (non-plenum)
GRX-PCBL-46L (plenum)
Data (terminals 3 and 4)
1 twisted, shielded pair 22 AWG (0.5 mm
2
)
5
R
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS System QSE-IO Control Interface
369374d 6 02.02.2018
QS Link Wiring Methods (choose one)
Powered by GRAFIK Eye® QS Control Unit
Powered by a QS Link Power Supply
1234
12
ABC
123456LN
To additional wallstations/
control interfaces
To additional wallstations/
control interfaces
Rear View of
GRAFIK Eye
® QS
Control Unit
Rear View of
GRAFIK Eye
® QS
Control Unit
QS
Link
QS
Link
QS Link
1: Common
2: V+
3: MUX
4: MUX
Data Link:
4: MUX
3: MUX
See QS Link
Wire Sizes table
previous page
SELV / PELV/NEC Class 2 Power wiring:
2: V+
1: Common
See QS Link Wire Sizes
table previous page
System communication uses SELV / PELV/NEC® Class
2 wiring.
Follow all local and national electrical codes when
installing SELV / PELV/NEC
® Class 2 wiring with line
voltage / mains wiring.
Each terminal accepts up to two 18 AWG (1.0 mm²)
wires.
Total length of control link must not exceed 2000 ft
(610 m).
Typical Wire Sizes: See QS Link Wire Sizes table,
previous page.
Connect the terminal 1, 3, and 4 connections to all
control units, wallstations, and control interfaces in
the QS system. For terminal 2 connectivity, please
refer to the wiring diagrams below.
LutronR Cable
See QS Link Wire Sizes table
previous page
QS Power Supply
To power source
(1) 18 AWG
(1.0 mm
2
)
Common
(1) twisted pair
22 AWG
(0.5 mm
2
)
6
R
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS System QSE-IO Control Interface
369374d 7 02.02.2018
Wiring Application Examples
1 LutronR Occupancy Sensor Wired to 1 QSE-IO Device Input
QSE-IO Terminals
Occupancy Sensor
(Wiring diagram is not applicable to:
-500R, -1000R, or -2000R models)
Power Pack
(use model that
corresponds to
input voltage)
Hot
Neutral
Red (+20 to 24 V-)
Blue (signal)
Black (common)
Blue (signal)
Black
(common)
Black
White
Red
Red
120 / 277 / 347 V~ 60 Hz
230 V~ 50 / 60 Hz
CCI1
CCI2
CCI3
CCI4
CCI5
COM
Power Pack
(use model that
corresponds to
input voltage)
Blue (signal)
Black
(common)
3 LutronR Occupancy Sensors Wired to 1 QSE-IO Device Input
QSE-IO Terminals
Hot
Neutral
Red (+20 to 24 V-)
Blue (signal)
Black (common)
Black
White
Red
Red
120 / 277 / 347 V~ 60 Hz
230 V~ 50 / 60 Hz
CCI1
CCI2
CCI3
CCI4
CCI5
COM
Occupancy Sensors
(Wiring diagram is not applicable to:
-500R, -1000R, or -2000R models)
NOTE: Refer to Spec Submittal #369653 LOS-CDT Series on www.lutron.com for wiring details regarding
Models -500R, -1000R, and -2000R for wiring the dry contact output from LOS sensors to the QSE-IO
(e.g. 7 wire Occ Sensor with photocell)
Note: When used with a GRAFIK EyeR QS standalone system in partitioned areas, each
occupancy sensor input will only control the individual area. Changes in occupancy sensor
state will not control adjacent areas. If partitioning functionality is required a QuantumR
processor is needed.
7
R
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS System QSE-IO Control Interface
369374d 8 02.02.2018
Multiple LutronR Occupancy Sensors Wired to Multiple QSE-IO Device Inputs
QSE-IO Terminals
Hot
Neutral
Red (+20 to 24 V-)
Blue (signal)
Black (common)
Red (+20 to 24 V
-)
Blue (signal)
Black (common)
Black
White
Red
Red
120 / 277 / 347 V
~ 60 Hz
230 V
~ 50 / 60 Hz
CCI1
CCI2
CCI3
CCI4
CCI5
COM
Power
Pack*
Hot
Neutral
120 / 277 / 347 V~ 60 Hz
230 V
~ 50 / 60 Hz
Power
Pack*
Neutral
Hot
Power
Pack*
Neutral
Hot
Black
White
Red
Red
Black
White
Red
Red
Black
White
Red
Red
Black
White
Red
Red
Occupancy Sensor
(
Wiring diagram is not applicable to:
-500R, -1000R, or -2000R models)
Power
Pack*
Neutral
Hot
Red (+20 to 24 V-)
Blue (signal)
Black (common)
Red (+20 to 24 V
-)
Blue (signal)
Black (common)
Red (+20 to 24 V
-)
Blue (signal)
Black (common)
Wiring Application Examples
Power
Pack*
* (use power
pack model that
corresponds to
input voltage)
Occupancy Sensors
(Wiring diagram is not applicable
to: -500R, -1000R, or -2000R models)
Occupancy Sensors
(Wiring diagram is not applicable to:
-500R, -1000R, or -2000R models)
Occupancy Sensors
(Wiring diagram is not applicable to:
-500R, -1000R, or -2000R models)
Occupancy Sensor: ( Wiring diagram is not applicable to: -500R, -1000R, or -2000R models)
120 / 277 / 347 V~ 60 Hz
230 V
~ 50 / 60 Hz
120 / 277 / 347 V
~ 60 Hz
230 V
~ 50 / 60 Hz
120 / 277 / 347 V
~ 60 Hz
230 V
~ 50 / 60 Hz
NOTE: Refer to Spec Submittal #369653 LOS-CDT Series on
www.lutron.com for wiring details regarding Models -500R,
-1000R, and -2000R for wiring the dry contact output from LOS
sensors to the QSE-IO (e.g. 7 wire Occ Sensor with photocell)
Note: When used with
a GRAFIK EyeR QS
standalone system in
partitioned areas, each
occupancy sensor input
will only control the
individual area. Changes
in occupancy sensor
state will not control
adjacent areas. If
partitioning functionality
is required a QuantumR
processor is needed.
8
R
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS System QSE-IO Control Interface
369374d 9 02.02.2018
QSE-IO Operating Modes and DIP Switch Settings Overview
Mode Dip Switch Contact Closures Invoke:
Configuration 345678Input 1 Input 2 Input 3 Input 4 Input 5 Inputs Outputs
Scene selection
Scene 1 Scene 2 Scene 3 Scene 4 Scene Off
Maintained or
Momentary
Maintained
Scene 5 Scene 6 Scene 7 Scene 8 Scene Off
Scene 9 Scene 10 Scene 11 Scene 12 Scene Off
Scene 13 Scene 14 Scene 15 Scene 16 Scene Off
Scene 1 Scene 2 Scene 3 Scene 4 Scene Off
Maintained or
Momentary
Momentary
Scene 5 Scene 6 Scene 7 Scene 8 Scene Off
Scene 9 Scene 10 Scene 11 Scene 12 Scene Off
Scene 13 Scene 14 Scene 15 Scene 16 Scene Off
Special
(maintained)
Sequence
516
Zone
lockout
Scene
lockout
Panic
mode
Timeclock Maintained
Maintained
Special
(momentary)
Sequence
516
Zone
lockout
Scene
lockout
Panic
mode
Timeclock Momentary
Special 2
(maintained)
Sequence
14
Zone
lockout
Scene
lockout
Panic
mode
Afterhours
mode
Maintained
Maintained
Special 2
(momentary)
Sequence
14
Zone
lockout
Scene
lockout
Panic
mode
Afterhours
mode
Momentary
Shade input preset
(“stop if moving”)
Shade
open
Shade
preset 1
Shade
preset 2
Shade
preset 3
Shade
close
Maintained or
Momentary
Maintained
Shade input preset
(no “stop if moving”)
Shade input
(raise, lower, stop)
Shade
open
Shade
raise
Shade
lower
Shade stop
Shade
close
Momentary or
Maintained
Maintained
Shade input dual group
(“stop if moving”)
Open
Group 1
Close
Group 1
Open
Group 2
Close
Group 2
Maintained or
Momentary
Maintained
Shade input dual group
(no “stop if moving”)
Shade input dual group
(raise/lower)
Raise/Stop
Group 1
Lower/Stop
Group 1
Raise/Stop
Group 2
Lower/Stop
Group 2
Momentary Momentary
Shade input toggle
(“stop if moving”:
open/stop/close/stop)
Toggle
Group 1
Toggle
Group 2
Toggle
Group 3
Toggle
Group 4
Toggle
Group 5
Momentary Momentary
Shade input toggle
(no “stop if moving”:
open/close)
Toggle
Group 1
Toggle
Group 2
Toggle
Group 3
Toggle
Group 4
Toggle
Group 5
Maintained Momentary
AC Shade output
(maintained outputs)
Open
Group 1
Stop
Group 1
Close
Group 1
Open
Group 2
Close
Group 2
Maintained or
Momentary
Maintained
AC Shade output
(momentary stop)
Open
Group 1
Stop
Group 1
if moving
Close
Group 1
Open
Group 2
Close
Group 2
Maintained or
Momentary
Maintained
(except 2, which
is Momentary)
AC Shade output
(momentary outputs)
Open
Group 1
Stop
Group 1
if moving
Close
Group 1
Open
Group 2
Close
Group 2
Maintained or
Momentary
Momentary
Notes
• For AC shades with only 2 inputs (open/close), set DIP switch 1 to the up/on position to enable the feature
that mimics “stop” (asserts both “open” and “close” CCOs together when a “stop” command is received).
• The QSE-IO provides no power, only a control signal, to AC shades. Refer to the instructions that came with your shades for more
information.
Legend:
Up/On
Down/Off
9
R
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS System QSE-IO Control Interface
369374d 10 02.02.2018
QSE-IO Operating Modes and DIP Switch Settings Overview (continued)
Mode Dip Switch Contact Closures Invoke:
Configuration 345678Input 1 Input 2 Input 3 Input 4 Input 5 Inputs Outputs
Partitioning
(momentary)
Wall 1 Wall 2 Wall 3 Wall 4 Wall 5 Momentary Maintained
Partitioning
(maintained)
Wall 1 Wall 2 Wall 3 Wall 4 Wall 5 Maintained Maintained
Occupancy sensor
(auto on/off)
Generates events on occupancy and vacancy Maintained Maintained
Occupancy sensor
(manual on/auto off)
Generates events on vacancy only Maintained Maintained
Zone toggle
(maintained)
Toggle 1 Toggle 2 Toggle 3 Toggle 4 Toggle 5 Maintained
Maintained
Zone toggle
(momentary)
Toggle 1 Toggle 2 Toggle 3 Toggle 4 Toggle 5 Momentary
Zone toggle with raise/lower
(maintained)
Toggle 1 Toggle 2 Toggle 3 Raise Lower Maintained
Zone toggle with raise/lower
(momentary)
Toggle 1 Toggle 2 Toggle 3 Raise Lower Momentary
Zone control
(maintained output)
Toggle 1 Toggle 2 Toggle 3 Toggle 4 Toggle 5 Maintained
Maintained
Toggle 1 Toggle 2 Toggle 3 Toggle 4 Toggle 5 Momentary
Zone control
(momentary output)
Pulse 1 Pulse 2 Pulse 3 Pulse 4 Pulse 5 Maintained
Momentary
Pulse 1 Pulse 2 Pulse 3 Pulse 4 Pulse 5 Momentary
Zone control
(pulsed output)
Pulse 1 Pulse 2 Pulse 3 Pulse 4 Pulse 5 Maintained
Pulsed
Pulse 1 Pulse 2 Pulse 3 Pulse 4 Pulse 5 Momentary
Hotel configuration 1
Service
(make up
room)
Privacy
(do not
disturb)
Doorbell
Start/end
afterhours
mode
Toggle
Scene 1/
Off
1-3:
Maintained or
Momentary
4-5:
Maintained
Maintained
(except 3)
Hotel configuration 2
Service
(make up
room)
Privacy
(do not
disturb)
Doorbell
Start/end
afterhours
mode
Enable/
disable
Scene
lockout
1-3:
Maintained or
Momentary
4-5:
Maintained
Maintained
(except 3)
Integration configuration
Control
output 1
Control
output 2
Control
output 3
Control
output 4
Control
output 5
Maintained or
Momentary
Maintained or
Momentary
Notes
• Occupancy sensor: Each input represents 1 sensor/group of sensors. Response to sensor event is programmable at the assigned lighting
control.
• “Momentary” output pulse is of fixed duration (250 ms default).
“Pulsed” output duration corresponds to activating button being held/released.
• Hotel: “Service” and “Privacy” are mutually exclusive; “Doorbell” is locked out when “Privacy” is active.
• DIP switch 1 must be up/on to activate the "Start/End Afterhours" feature on CCI4.
• DIP switch 2 must be up/on to activate the "Toggle Scene" or "Scene Blackout" feature on CCI 5.
• Occupancy sensors will not participate in partitioning logic.
Legend:
Up/On
Down/Off