Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-270a 1 07.21.10
Maestro® Sensors Dimmer/Switch with Occupancy and Vacancy Sensor
Maestro Sensors
Lutron’s Maestro Dimmer and Switch with occupancy and vacancy sensors are lighting controls with passive
infrared sensors that automatically control the lights in an area. These sensors detect the heat from occupants
moving within an area to determine when the space is occupied.
The Dimmer with Sensor combines a Maestro 600 W incandescent/halogen dimmer with an occupancy or
vacancy sensor.
The Switch with Sensor combines a Maestro switch with an occupancy or vacancy sensor.
Family Features
Passive infrared motion detection with exclusive Lutron® XCTTM Technology for fine motion detection
180˚ sensor field-of-view
Up to 30 ft x 30 ft (9.14 m x 9.14 m) [900 ft
2
(274.32 m²)] major motion coverage and
20 ft x 20 ft (6.1 m x 6.1 m) [400 ft
2
(121.92 m²)] minor motion coverage
Occupancy/vacancy version can be set to auto-on/auto-off or manual-on/auto-off
Vacancy version available to meet CA title 24 requirements
Dimmer with sensor:
Model Number * Description Sensor Operation Maximum Capacity
MS-OP600M-XX Occupancy/vacancy
single-pole/multi-location
Auto-on/auto-off or
manual-on/auto-off
600 W incandescent/
halogen
MS-VP600M-XX
Vacancy single-pole/
multi-location
Manual-on/auto-off
600 W incandescent/
halogen
Adjustable timeout - 1, 3, 5, 15, or 30 minutes
Optional off warning dims the lights by 50%, 30 seconds before the light turns off
High-low sensitivity adjustment
Standard Maestro dimmer features: locked preset, fade-to-on, and fade-to-off
Works with up to 9 companion dimmers (MA-R-XX) *
Switch with sensor:
Adjustable timeout - 1, 5, 15, or 30 minutes
High-low sensitivity adjustment
Switch lighting loads: incandescent, halogen, MLV, ELV, and non-dim fluorescent
Works with up to 9 companion switches (MA-AS-XX* or MA-AS-277-XX*)
* XX in model number represents color/finish code
Model Number * Description Sensor Operation Maximum Capacity
MS-OPS5AM-XX
Occupancy/vacancy single-
pole/multi-location 120 V
;
neutral wire required
Auto-on/auto-off
or manual-on/
auto-off
5 A lighting
MS-VPS5AM-XX
Vacancy single-pole/multi-
location 120 V
; neutral
wire required
Manual-on/auto-
off
5 A lighting
MS-OPS6M-DV-XX
Occupancy/vacancy single-
pole/multi-location
120-277 V
spec grade
electronic switch; no neutral
wire required
Auto-on/auto-off
or manual-on/
auto-off
6 A lighting
3 A 1/10 HP Fan
(Fan 120 V only)
MS-VPS6M-DV-XX
Vacancy single-pole/multi-
location 120-277 V
spec
grade electronic switch; no
neutral wire required
Manual-on/auto-
off
6 A lighting
3 A 1/10 HP Fan
(Fan 120 V
only)
1
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-270a 2 07.21.10
Maestro® Sensors Dimmer/Switch with Occupancy and Vacancy Sensor
Colors and Finishes
Gloss Finishes Satin Finishes
Taupe
TP
Turquoise
TQ
Plum
PL
Merlot
MR
Terracotta
TC
Sienna
SI
Midnight
MN
Hot
HT
Desert Stone
DS
Due to printing limitations, colors
and finishes shown cannot be
guaranteed to perfectly match
actual product colors.
Eggshell
ES
Biscuit
BI
Snow
SW
Palladium
PD
Greenbriar
GB
Bluestone
BG
Mocha
Stone
MS
Goldstone
GS
Sea Glass
SG
Stone
ST
Limestone
LS
White
WH
Gray
GR
Brown
BR
Ivory
IV
Almond
AL
Black
BL
Light
Almond
LA
2
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-270a 3 07.21.10
Maestro® Sensors Dimmer/Switch with Occupancy and Vacancy Sensor
Control Voltage Load
Type
Minimum
Load
Maximum Load Neutral
Connection
Required
Not
Ganged
End of
Gang
Middle of
Gang
MS-OP600M
MS-VP600M
120 V
Incand.
1
40 W 600 W 500 W 400 W NO
MS-OPS5AM
MS-VPS5AM
120 V
Lighting
2
5 W 5 A 4 A 3.2 A YES
MS-OPS6M-DV
MS-VPS6M-DV
120 -
277 V
Lighting
2
25 W 6 A 6 A 6 A NO
120 V
Fan 0.4 A 3 A
(1/10 HP)
3 A
(1/10 HP)
3 A
(1/10 HP)
NO
Load Type and Capacity
1
Dimmer Load Type: designed for use with permanently installed incandescent or tungsten halogen only. Do not install dimmers to control recep-
tacles or motor-operated appliances.
2
Switch Load Type: designed for use with permanently installed lighting loads.
3
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-270a 4 07.21.10
Maestro® Sensors Dimmer/Switch with Occupancy and Vacancy Sensor
Specifications
Regulatory Approvals
UL Listed and cUL Listed.
Power
Operating voltage:
120 V 60 Hz
120-277 V 50/60 Hz
(-OPS6M-DV and -VPS6M-DV)
Key Design Features
Dimmer
On a single-tap, lights fade ON or OFF.
On a double-tap, lights go to full ON.
When ON, press and hold to engage up to
60-second fade to OFF.
Light levels can be fine-tuned by pressing and
holding the dimming rocker until the desired
light level is reached.
Switch
On a single-tap, lights turn ON or OFF.
Two-wire switches available.
Environment
Ambient operating temperature: 32 °F to 104 °F
(0 °C to 40 °C), 0%-90% humidity, non-condensing.
Indoor use only.
Warranty
1 Year Limited Warranty.
For additional Warranty information, please visit
http://www.lutron.com/TechnicalDocumentLibrary/
369-119_Wallbox_Warranty.pdf
Timeout Options
1 Minute
3 Minutes*
5 Minutes
15 Minutes
30 Minutes
* dimmer only
Sensitivity Options
High sensitivity
Low sensitivity
Auto-On Options (occupancy/vacancy version)
“Enabled” - Auto-On
“Disabled” - Manual-On
Ambient Light Detection Options (-OPS6M-DV):
Disabled: Lights turn on regardless of light level in
the room.
Enabled with High Light Level: Prevents lights
from turning on automatically when there is a high
amount of ambient light.
Enabled with Medium Light Level: Prevents
lights from turning on automatically when there is a
medium amount of ambient light.
Enabled with Low Light Level: Prevents lights
from turning on automatically when there is a low
amount of ambient light.
Off While Occupied (-OPS6M-DV only)
When Switch is manually turned off, the Sensor
will not turn the lights back on automatically while
the room is occupied.
Once the room is vacated, the Auto-on feature
returns to normal operation after the timeout
duration has expired.
When this feature is disabled, after being manually
turned off, the Auto-on feature will return to normal
operation after 25 seconds.
4
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-270a 5 07.21.10
Maestro® Sensors Dimmer/Switch with Occupancy and Vacancy Sensor
Range Diagrams
Horizontal Coverage
Vertical Coverage
Sensor Placement and Operation
The Sensor’s ability to detect motion requires line-of-sight of room occupants. The Sensor must have an
unobstructed view of the room.
Hot objects and moving air currents can affect the Sensor’s performance.
The Sensor’s performance depends on a temperature differential between the ambient room temperature
and that of room occupants. Warmer rooms may reduce the Sensor’s ability to detect occupants.
5 ft
(1.5 m)
5 ft
(1.5 m)
15 ft
(4.6 m)
15 ft
(4.6 m)
25 ft
(7.7 m)
25 ft
(7.7 m)
5 ft
(1.5 m)
15 ft
(4.6 m)
25 ft
(7.7 m)
35 ft
(11 m)
Major Motion | Movimientos grandes | Grands mouvements
Minor Motion | Movimientos menores | Petits mouvements
0 ft
(0 m)
5 ft
(1.5 m)
5 ft
(1.5 m)
15 ft
(4.6 m)
25 ft
(7.7 m)
35 ft
(11 m
)
Sensor
Sensor
3.8 ft
(1.2 m)
5
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-270a 6 07.21.10
Maestro® Sensors Dimmer/Switch with Occupancy and Vacancy Sensor
Mounting
Wallbox
Control
Adapter
Mounting
Screws
Control
Mounting
Screws
Wallplate / Adapter purchased
separately.
Operation
Status LEDs
Indicate light level; glow softly as night
light when light is off
Sensor LED
Pulses or
“breathes” to
acknowledge
motion
Dimming Rocker
Press to brighten
Press to dim
Tapswitch
Tap on / off;
Double-tap - lights go to full on
Sensor Lens
Sensor Lens
FASSTM
Front
Accessible
Service
Switch
IMPORTANT NOTICE:
FASS - Front Accessible Service Switch - to service load, remove power by pulling the FASS switch out completely
on either the Dimmer or Companion Dimmer. After servicing load, push the FASS switch back in fully to restore
power to the control.
Dimmer
Tapswitch
Tap on / off
FASSTM
Front
Accessible
Service
Switch
Switch
Status LED
Indicates load status; glows softly as
night light when light is off
Sensor LED
Pulses or
“breathes” to
acknowledge
motion
6
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-270a 7 07.21.10
Maestro® Sensors Dimmer/Switch with Occupancy and Vacancy Sensor
Dimensions
Front View
Side View
5/16 in
(8 mm)
1/8 in
(3 mm)
1
1
8 in.
(30 mm)
4
11
16 in
(119 mm)
2
15
16 in
(75 mm)
When ganging with other controls in the same wallbox, derating is required. See Load Type and Capacity chart.
Do Not remove outside fins on
End of Gang Controls
Middle of Gang
Control has all fins
removed
Ganging and Derating
Each Control has
inside fins removed
Note: MS-OPS6M-DV and MS-VPS6M-DV have leaded wire terminations. MS-OP600M, MS-VP600M,
MS-OPS5AM, and MS-VPS5AM have screw terminals.
7
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-270a 8 07.21.10
Maestro® Sensors Dimmer/Switch with Occupancy and Vacancy Sensor
Wiring Diagrams:
Single Location
1
Dimmer Installation without Neutral
-OP600M and -VP600M
Single Location
1
Switch Installation with Neutral
-OPS5AM and -VPS5AM
Brass
Black
Blue
Tighten
1
Green
Ground
Hot/Live
Neutral
120 V 60 Hz
120 V
60 Hz
Brass
Silver
Black
Green
Ground
Hot/Live
Neutral
Load
Blue
Tighten
1
Load
Switch
Wiring Diagram 1 Wiring Diagram 2
Dimmer
Single Location
1
Switch (2-wire) Installation
without Neutral
-OPS6M-DV, and -VPS6M-DV
Wiring Diagram 3
Continued on next page...
Single Location
1
Switch (2-wire) Installation
without Neutral and with Shunt Capacitor
2
-OPS6M-DV, and -VPS6M-DV
Wiring Diagram 4
Switch
120-277 V
50 / 60 Hz
Red
Black
Green
Ground
Hot/Live
Neutral
Load
Blue
1
Shunt
Capacitor
2
Optional
Switch
120-277 V
50 / 60 Hz
Red
Black
Green
Ground
Hot/Live
Neutral
Load
Blue
1
8
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-270a 9 07.21.10
Maestro® Sensors Dimmer/Switch with Occupancy and Vacancy Sensor
Multi-Location
3
Switch Installation with Neutral
5
-OPS5AM and -VPS5AM with MA-AS
Brass
Silver
Black
Blue
Green
Ground
Load
Brass
Black
Blue
Green
Ground
Companion Switch
120 V 60 Hz
Brass
Black
Blue
Green
Ground
Hot/Live
Neutral
Companion Switch Switch
4
Wiring Diagram 6
Multi-Location
3
Dimmer Installation without Neutral
5
-OP600M and -VP600M with MA-R
Brass
Black
Blue
Green
Ground
Dimmer or
Campanion Dimmer
Brass
Black
Blue
Green
Ground
120 V 60 Hz
Brass
Black
Blue
Green
Ground
Hot/Live
Neutral
Load
Note: Dimmer can be installed in
any location in the circuit.
Companion Dimmer or
Dimmer
Companion Dimmer or
Dimmer
Wiring Diagram 5
Note: Neutral wire Switch must be
connected on the Load side of a
multi-location installation.
Wiring Diagrams: (continued)
Continued on next page...
9
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-270a 10 07.21.10
Maestro® Sensors Dimmer/Switch with Occupancy and Vacancy Sensor
Multi-Location
3
Switch (2-wire) Installation without Neutral
5
(120 V )
-OPS6M-DV and -VPS6M-DV with MA-AS
Red/
Brass
Black
Blue
Green
Ground
Switch or
Campanion Switch
Brass/
Red
Black
Blue
Green
Ground
120 V 50 / 60 Hz
Brass/
Red
Black
Blue
Green
Ground
Hot/Live
Neutral
Load
Note: Switch can be installed in any
location in the circuit.
Companion Switch
or Switch
Companion Switch
or Switch
Wiring Diagram 7
Wiring Diagrams: (continued)
Multi-Location
3
Switch (2-wire) Installation without Neutral
5
(277 V )
-OPS6M-DV and -VPS6M-DV with MA-AS-277
Black
Blue
Green
Ground
Switch or
Campanion Switch
Black
Blue
Green
Ground
277 V 50 / 60 Hz
Black
Blue
Green
Ground
Hot/Live
Neutral
Load
Note: Switch can be installed in any
location in the circuit.
Companion Switch
or Switch
Companion Switch
or Switch
Wiring Diagram 8
RedRedRed
Multi-Location
3
Switch (2-wire) Installation without Neutral and with Shunt Capacitor
2,5
(120 V )
-OPS6M-DV and -VPS6M-DV with MA-AS
Red/
Brass
Black
Blue
Green
Ground
Switch or
Campanion Switch
Brass/
Red
Black
Blue
Green
Ground
120 V 50 / 60 Hz
Brass/
Red
Black
Blue
Green
Ground
Hot/Live
Neutral
Load
Note: Switch can be installed in any
location in the circuit.
Companion Switch
or Switch
Companion Switch
or Switch
Wiring Diagram 9
Continued on next page...
Shunt
Capacitor
2
Optional
10
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-270a 11 07.21.10
Maestro® Sensors Dimmer/Switch with Occupancy and Vacancy Sensor
Wiring Diagrams: (continued)
Multi-Location
3
Switch (2-wire) Installation without Neutral and with Shunt Capacitor
2,5
(277 V )
-OPS6M-DV and -VPS6M-DV with MA-AS-277
Black
Blue
Green
Ground
Switch or
Campanion Switch
Black
Blue
Green
Ground
277 V 50 / 60 Hz
Black
Blue
Green
Ground
Hot/Live
Neutral
Load
Note: Switch can be installed in any
location in the circuit.
Companion Switch
or Switch
Companion Switch
or Switch
Wiring Diagram 10
RedRedRed
Shunt
Capacitor
2
Optional
1
When using controls in single location installations, tighten the blue terminal or cap blue wire. Do not connect the blue terminal / wire to any
other wiring or to ground.
2
Optional shunt capacitor must be installed inside the load fixture or in a separate J-box.
3
Up to 9 Companion Dimmers / Switches may be connected to a Dimmer / Switch. Total blue terminal wire length may be up to 250 ft (76 m).
4
Neutral wire Switches must be connected on the Load side of a multi-location installation.
5
Only one sensor unit can be used per multi-location circuit.
11