SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive PowPak 20 A Receptacle Control Relay Module Wireless Receptacle Control
369966d 1 03.07.17
PowPak 20 A Receptacle Control
Relay Module
The PowPak 20 A Relay Receptacle Control Module is a
radio-frequency (RF), receptacle switching solution that
is capable of controlling 20 A receptacles based on
input from Pico remote controls and Radio Powr Savr
occupancy sensors.
Communication with RF input devices, such as Pico
remote controls and / or Radio Powr Savr
occupancy / vacancy sensors, is accomplished using
Lutron Clear Connect RF Technology.
These products are also compatible with the Vive hub
which enables a simple setup process using a standard
web browser on any Wi-Fi enabled phone, tablet or
computer. The hub also enables control and monitoring
of all Vive devices. The Vive hub can be added at any
time. System reprogramming will be required. For a
complete list of features supported with the Vive hub,
see specification submittal 369902.
Note for Replacement: RMJS-20R-DV-B or
RMJS-20RCCO1DV-B can replace RMJ-H20R-DV-B.
NOTE: Not intended for control of permanently installed
lighting fixtures.
Features
•Softswitch:Lutronpatentedtechnologypreventsarcing
of relay contacts, extending product lifetime
•Optionallow-voltagedrycontactclosureoutput
provides integration to HVAC, VAV, etc.
•Receiveswirelessinputsfromupto10Picoremote
controls, and 10 Radio Powr Savr occupancy / vacancy
sensors
•RoHSCompliant
Description Model Number Region Operating Voltage Frequency Band
PowPak 20 A Receptacle
Control Relay Module
RMJS-20R-DV-B USA, Canada, Mexico
(TA A /NAF TA approved)
120
/ 277 V~ 431.0 –437.0 MHz
PowPak 20 A Receptacle
Control Relay Module
with Contact Closure
Output
RMJS-20RCCO1DV-B USA, Canada, Mexico
(TA A /NAF TA approved)
120 / 277 V~ 431.0 –437.0 MHz
Model Numbers
RMJS-20RCCO1DV-B model shown
•Abletocontrol20Areceptacles
•Capableofswitchinggeneral-purposeloads
•UtilizesLutronClearConnectRFTechnology
•MountstoaU.S.stylejunctionboxthrougha
standard 1/2 in (12.7 mm) size knockout
•Includesrequiredcontrolledoutletlabelsforcode
compliance
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive PowPak 20 A Receptacle Control Relay Module Wireless Receptacle Control
369966d 2 03.07.17
Specifications
Regulatory Approvals
•UL
® 508 Listed (USA)
•FCCapproved.ComplieswiththelimitsforaClassB
device, pursuant to Part 15 of the FCC rules. (USA)
•IC(Canada)
•CSAcompliant(Canada)
•NOMandCOFETELcompliant(Mexico)
• Complieswithrequirementsforuseinotherspaces
used for environmental air (plenums) per
NEC
® 2014 300.22(C)(3)
• ListedinaccordancetoCAN/ULCS102.2-2010with
a Flame Spread Rating of 0 and a Smoke Developed
Classification of 40, with a minimum spacing of 6 ft
(1.83 m) off center
Power
•Operatingvoltage:
120
/ 277 V ~ 50/60 Hz
•StandbyPowerConsumption(allmodels):<1.25W
System Communication
•OperatesusingClearConnectRFTechnologyforreliable
wireless communication.
•RFrangeis30ft(9m)
•Wirelesssensorsandcontrolsmustbelocatedwithin
60ft (18 m) line of sight, or 30 ft (9 m), through walls, of
the associated control module. The 60 ft (18 m) range is
not reduced by a ceiling tile obstruction.
Environment
•Ambientoperatingtemperature:32°Fto131°F
(0°Cto55°C)
•0%to90%humidity,non-condensing
•Forindooruseonly
• AlldriversandballastsusedwithVivewireless
controls must comply with the limits for a Class A
device pursuant to Part 15 of the FCC Rules
Softswitch
•PatentedSoftswitchcircuiteliminatesrelayarcing
at mechanical contacts
•Outputisnon-latching
Load Type
Relay Ratings
120 – 277 V~ single phase only
RMJS-20R-DV-B
RMJS-20RCCO1DV-B
Tungsten 20 A
AC General Use 20 A
Resistive 20 A
Inductive 20 A
Motor
1.0 HP 120 V~
2.0 HP 277 V~
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive PowPak 20 A Receptacle Control Relay Module Wireless Receptacle Control
369966d 3 03.07.17
Specifications (continued)
Load
•20A;Nominimumloadrequirements.Ratedtocontrol20
A receptacles.
•Motorrating:
1.0 HP (120 V~), 2.0 HP (277 V~)
The 20 A Receptacle Control Relay Module may be used
with,butisnotlimitedto,thefollowing:
Monitors Fans
Humidifiers Printers
NOTE: Refer to the manufacturer’s guidelines for
acceptable switching methods.
The 20 A Receptacle Control Relay Module may NOT
be suitable for use with devices that require any of the
following:
Shut-down process before power is interrupted, such
as computers.
Cool-down process before power is interrupted, such
asprojectors.
Programming, such as clocks or DVRs.
Long warm-up cycle.
Not for use with loads that present a hazard if
automatically energized. For example, heaters.
Any receptacles that are controlled by an automatic
control device must be marked with “ u located on
the controlled receptacle outlet where visible after
installation as stated in 2014 NECR Article 406.3(E).
NOTE: Labels with this marking u
are included with the
product.
Key Design Features
•LEDstatusindicatorilluminateswhenabuttonispressed
and turns off 2 seconds after the button is released
•Powerfailurememory:Ifpowerisinterrupted,connected
receptacles will return to the state prior to the power
interruption.
NOTE: Do not tie the CCO to ground.
Contact Closure Output (CCO version only)
•Providesoccupancystatusto3rd-party
equipment such as building management
systems, HVAC, and VAV controllers
•Providesbothnormallyopen(NO)andnormally
closed (NC) dry contacts
•Maintainedoutputtype
•CCOterminalsaccept
20 AWG to 16 AWG
(0.5 mm
2
to 1.5 mm
2
)
solid or stranded wire
•Outputislatching
•Notforvoltagesgreaterthan24V-
•TheCCOisnotratedtocontrolunclamped,
inductiveloads.Inductiveloadsinclude,butare
not limited to, relays, solenoids, and motors.
To control these types of equipment, a flyback
diode must be used (DC voltages only). See
diagram below. For more information, please see
Application Note #434 (P/N 048434)
www.lutron.com/TechnicalDocumentLibrary/
048434a.pdf
Switching
Voltage
0-24 V-
0-24 V~
24 V-
max.
Inductive
Load
CCO
Output
NO
NC
COM
Flyback
Diode
(required for
inductive
loads)
Resistive
Load
1.0 A
0.5 A
R
+
-
Switching
Voltage
0-24 V-
0-24 V~
24 V-
max.
Inductive
Load
CCO
Output
NO
NC
COM
Flyback
Diode
(required for
inductive
loads)
Resistive
Load
1.0 A
0.5 A
R
+
-
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive PowPak 20 A Receptacle Control Relay Module Wireless Receptacle Control
369966d 4 03.07.17
Range Diagrams
Dimensions
Dimensionsareshownas:in(mm)
1/2 in or 21 mm trade size
knockout opening
3.94
(100)
3.42
(87)
2.82
(72)
1.25
(32)
Test
30 ft (9 m)
Maximum
40 ft (12 m)
30 ft (9 m)
Installincenterofroomto
maximize RF coverage.
Pico
remote
control
Radio Powr Savr
occupancy sensor
PowPak 20 A
Receptacle Control
Relay Module
NOTE: Wireless sensors and controls must be located within 60 ft (18 m) line of sight, or 30 ft (9 m),
through walls, of the associated control module. The 60 ft (18 m) range is not reduced by a ceiling tile
obstruction.
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive PowPak 20 A Receptacle Control Relay Module Wireless Receptacle Control
369966d 5 03.07.17
System Diagram
Radio Powr Savr occupancy/vacancy sensor
(up to 10)
Pico remote control (up to 10)
To 3rd-Party
Equipment
Note: CCO models only
To power source
and load
Default Operation
Transmitting Device Transmitted Command Softswitch
Relay Default Action
CCO Default Action
Pico
remote control
On Close No Action
Off Open No Action
Raise No Action No Action
Lower No Action No Action
Preset Close No Action
Radio Powr Savr
occupancy sensor
Occupied Close NO = Close, NC = Open
Unoccupied Open NO = Open, NC = Close
Radio Powr Savr
vacancy sensor
Occupied Close NO = Close, NC = Open
Unoccupied Open NO = Open, NC = Close
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive PowPak 20 A Receptacle Control Relay Module Wireless Receptacle Control
369966d 6 03.07.17
Wiring Diagram - for Duplex Receptacle
LINE/HOT(Black)
NEUTRAL(White)
SWITCHED
LINE/HOT(Red)
Junction Box
Controlled
20 A Receptacle *
Uncontrolled
20 A Receptacle
u
ATTENTION INSTALLER
Any receptacles that are
controlled by an automatic
control device must be marked
with “u” located on the
controlled receptacle outlet
where visible after installation as
statedin2014NECR Article
406.3(E).
NOTE: Labels with this marking
uare included with the
product.
u
To
3rd-party
equipment
NC
NO
COM
* Important Note
WARNING: Entrapment Hazard. Toavoidtheriskofentrapment,seriousinjury,ordeath,thesecontrolsmustnotbeusedtocontrolequipment
which is not visible from every control location or which could create hazardous situations such as entrapment if operated accidentally.
WARNING: Fire Hazard. Toavoidtheriskoffire,seriousinjury,ordeath,thesecontrolsmustnotbeusedtocontrolequipmentwhichisnot
visible from every control location or which could create hazardous situations such as fire if operated accidentally.
Examplesofsuchequipmentwhichmustnotbeoperatedbythesecontrolsinclude(butarenotlimitedto)motorizedgates,industrialdoors,space
heaters,etc.Itistheinstaller’sresponsibilitytoensurethattheequipmentbeingcontrolledisvisiblefromeverycontrollocationandthatonlysuitable
equipmentisconnectedtothesecontrols.Failuretodosocouldresultinseriousinjuryordeath.
NOTE:Someapplications(inUSA)requirethePowPak20AReceptacleControlRelayModuletobeinstalledinsideanadditionaljunction
box. For information about how to perform this installation, please see Application Note #423 (P/N 048423)
www.lutron.com/TechnicalDocumentLibrary/048423.pdf
Please consult all local and national electric codes for proper installation methods.
NOTE: Do not tie the CCO
to ground.
120/
277 V~
50/60 Hz
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive PowPak 20 A Receptacle Control Relay Module Wireless Receptacle Control
369966d 7 03.07.17
Wiring Diagram - for Split-Wired Duplex Receptacle
LINE/HOT(Black)
NEUTRAL(White)
SWITCHED
LINE/HOT(Red)
Junction Box
20 A Split-Wired
Receptacle. *
Note: This example is showing
a split-wired receptacle. The top
portion of the receptacle is not
controlled by the 20 A Receptacle
Control
Relay Module, while the
bottom portion is switched by the
20 A Receptacle Control
Relay
Module.
u
ATTENTION INSTALLER
Any receptacles that are
controlled by an automatic
control device must be marked
with “u” located on the
controlled receptacle outlet
where visible after installation as
statedin2014NECR Article
406.3(E).
NOTE: Labels with this marking
uare included with the
product.
u
NEUTRAL(White)
To
3rd-party
equipment
NC
NO
COM
NOTE:
Someapplications(inUSA)requirethePowPak20AReceptacleControlRelayModuletobeinstalledinsideanadditionaljunction
box. For information about how to perform this installation, please see Application Note #423 (P/N 048423).
www.lutron.com/TechnicalDocumentLibrary/048423.pdf
Please consult all local and national electric codes for proper installation methods.
)Lutron,Lutron,PowPak,Pico,ClearConnect,andSoftswitcharetrademarksofLutronElectronicsCo.,Inc.registeredintheU.S.andothercountries.
ViveandRadioPowrSavraretrademarksofLutronElectronicsCo.,Inc.
NECisaregisteredtrademarkoftheNationalFireProtectionAssociation,Quincy,Massachusetts.
NOTE: Do not tie CCO
to ground.
* Important Note
WARNING: Entrapment Hazard. Toavoidtheriskofentrapment,seriousinjury,ordeath,thesecontrolsmustnotbeusedtocontrolequipment
which is not visible from every control location or which could create hazardous situations such as entrapment if operated accidentally.
WARNING: Fire Hazard. Toavoidtheriskoffire,seriousinjury,ordeath,thesecontrolsmustnotbeusedtocontrolequipmentwhichisnot
visible from every control location or which could create hazardous situations such as fire if operated accidentally.
Examplesofsuchequipmentwhichmustnotbeoperatedbythesecontrolsinclude(butarenotlimitedto)motorizedgates,industrialdoors,space
heaters,etc.Itistheinstaller’sresponsibilitytoensurethattheequipmentbeingcontrolledisvisiblefromeverycontrollocationandthatonlysuitable
equipmentisconnectedtothesecontrols.Failuretodosocouldresultinseriousinjuryordeath.
120/
277 V~
50/60 Hz
7