QSN
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node 0 –10 V-/Softswitch 20 A Receptacle/Fixture Controllers
369791e 5 08.05.19
Specifications (continued)
Emergency Contact Closure Input
• By default, contact closure input from Lutron Emergency
Lighting Interface (LUT-ELI-3PH), security, or fire
alarm systems turns all zones on to full output when
emergency state is detected.
• Emergency contact closure input is normally closed (NC).
The ESN unit is shipped with a jumper pre-installed.
• Response of each zone is configurable.
• Attached devices, by default, will go to maximum output
and ignore control inputs.
• No operations will be allowed until emergency signal is
cleared.
• The attached device must provide a dry-contact closure
or solid-state output.
• Input is miswire-protected up to 36 V-.
• Emergency CCI cannot control other ESN units.
Functionality with GRAFIK Eye QS
• ESN unit follows GRAFIK Eye QS scene activations when
associated with the GRAFIK Eye QS.
• ESN unit responds to commands initiated by the GRAFIK
Eye QS astronomic time clock when associated with the
GRAFIK Eye QS.
• ESN unit operates in afterhours mode when associated
with a GRAFIK Eye QS that is in afterhours mode.
Functionality with QSE-IO
• ESN unit responds to scene commands initiated by the
QSE-IO if the QSE-IO DIP switches have been set to
either scene selection mode, zone toggle mode, partition
mode, or occupancy sensor mode.
Functionality with QSE-CI-NWK-E
• Integrate ESN unit with touchscreens, PCs, A / V
systems, or other digital systems and devices.
• Recall scenes and set/adjust zone levels.
IEC PELV / NEC® Class 2 Dry-Contact Switches
• Four inputs for IEC PELV / NEC® Class 2 dry-contact
switches can be assigned to turn on and off one or more
zones.
• Configure for momentary or maintained operation.
QS Link Limits
• Each ESN unit can provide up to 14 Power Draw
Units (PDUs) for other QS devices. Refer to the QS
Link Power Draw Unit specification submittal (Lutron
P/N369405) for more information concerning PDUs.
• The QS Link can have up to 100 devices and
100 zones.
• Each ESN unit counts as 1 device towards the
100device limit.
• Each ESN unit counts as 4 zones towards the
100zone limit.
QSM (QS Sensor Module)
• Use the QSM to integrate Radio Powr Savr
occupancy sensors, Radio Powr Savr daylight
sensors, and Pico wireless controllers to control
zones on the ESN unit.
• Associate 1 QSM per ESN unit with manual
programming.
• Associate multiple QSMs per ESN unit with Apple
iPod touch or iPhone programming (requires
QSE-CI-AP-D and Wi-Fi router). See “Programming
Options” for details.
• Assign up to 10 Radio Powr Savr occupancy sensors
per ESN unit via QSM.
• Assign up to 4 Radio Powr Savr daylight sensors per
ESN unit via QSM.
• Assign up to 10 Pico wireless controllers per ESN unit
via QSM.
• The sensors and Pico wireless controllers associated
with the QSM should be mounted within 60 ft (18 m)
line of sight, or 30 ft (9 m) through walls, of the QSM.
• Wire and power up to 4 wired sensors per QSM
– Daylight Sensors
– Occupancy Sensors
– Infrared (IR) Receivers or Wallstations
• Refer to QSM Specification Submittal for more
information.