QSN
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node 0 –10 V-/Softswitch 20 A Receptacle/Fixture Controllers
369791e 1 08.05.19
Energi Savr Node for 010 V-
Energi Savr Node with Softswitch
The Energi Savr Node (ESN) family is a group of modular
products for the control of lighting, receptacles, and other loads.
This document describes the following products:
Energi Savr Node for 010 V-
(models QSN-4T20-S, QSN-4T16-S-347)
Energi Savr Node with Softswitch
(models QSN-4S20-S, QSN-4S16-S-347)
Features
Rated to switch 20 A receptacles with any output.
Default configuration requires no commissioning.
Program using integral interface on the ESN unit.
Four occupancy sensor inputs for automated control of loads in
4 zones.
Four daylight sensor inputs automatically adjust light levels based
on the amount of natural light entering through the windows.
Four IR receiver inputs for personal control.
Four inputs for IEC PELV / NEC® Class 2 dry-contact switches.
Includes QS control link for seamless integration of loads, control
stations, and QS sensor modules.
Patented Softswitch circuit eliminates arcing at mechanical
contacts when loads are switched, prolonging relay life to an
average of 1,000,000 cycles at 16 A.
Contact Lutron for compatibility with a Quantum system.
System Example
QSN-4T20-S
QSN-4T20-S
QSN-4T20-S
Control Power
120 277 V~
4 Load Input Feeds
120 277 V~ ; 347 V~
1
4 0–10 V Channels
(QSN-4T20-S;
QSN-4T16-S-347 only)
4 Switched-Load Outputs
(20 A Softswitch 120–277 V~ ; 347 V~
1
)
Wired
Daylight Sensors
(up to 4)
2,3
Wired
Occupancy Sensors
(up to 4)
2
Wired
Wallstation or IR Receivers
(up to 4)
2
IR
Transmitter
IR
Transmitter
QS link
Emergency
Contact
Closure
Input
Contact
Closure
Input
Wired Daylight Sensors (up to 4)
3
Wired Occupancy Sensors (up to 4)
Wired Wallstation or IR receivers (up to 4)
IEC PELV/NEC® Class 2
Dry-Contact Switch
(up to 4) (by others)
seeTouch QS Wallstation
Wireless Communication
OR
OR
OR
OR
QSM
ESN
Programming
Interface
Radio Powr Savr
Occupancy Sensor
(up to 10 per QSM)
Radio Powr Savr
Daylight Sensor
(up to 10 per QSM)
3
Pico
Wireless Controller
(up to 10 per QSM)
Notes
1
For 347 V~ models only.
2
Up to 4 wired devices total (of any type).
3
The maximum number of daylight
sensors (wired and wireless) that an ESN
unit can support is four (1 per zone).
1
QSN
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node 0 –10 V-/Softswitch 20 A Receptacle/Fixture Controllers
369791e 2 08.05.19
Specifications
Regulatory Approvals
• UL® Listed
• CSA
• NOM
Lutron Quality Systems registered to ISO 9001:2015
Complies with requirements for use in other spaces
used for environmental air (plenums) per
NEC® 2014 300.22(C)(3)
Meets the Canadian National Building Code plenum
requirements for a concealed space used as a plenum
within a floor or roof assembly
For commercial use, Class A only
Power
Control Power: 120 V~; 220–240 V~;
277 V~ 50/60Hz
Lightning strike protection meets ANSI/IEEE standard
62.41-1991. Can withstand voltage surges of up to
6000V~ and current surges of up to 3000 A
Current draw: 0.5A max
10-year power failure memory: restores lighting to
levels prior to power interruption
Latching relays keep previously illuminated zones on
when control power feed is lost
Environment
Ambient Temperature Operating Range:
32ºF to 104ºF (0ºC to 40ºC)
Relative humidity: less than 90% non-condensing
For indoor use only
Thermal dissipation: 40 BTU/hr
Terminal Wiring
Control Power Wiring: 14 AWGto 12AWG
(2.5 mm
2
to 4.0mm
2
)
Load Wiring: 14 AWGto 12AWG
(2.5 mm
2
to 4.0mm
2
)
010 V Wiring: 20 AWGto 12AWG
(0.5 mm
2
to 4.0mm
2
)
Input Group Wiring: 20 AWGto 12AWG
(0.5 mm
2
to 4.0mm
2
); maximum wire run length to
each input not to exceed 150ft (46m)
QS Link Wiring: 22 AWGto 12AWG
(0.5 mm
2
to 4.0mm
2
)
Contact Closure Wiring: 20 AWGto 12AWG
(0.5 mm
2
to 4.0mm
2
)
Physical Design and Mounting
NEMA Type1, IP-20 protection
• Surface-mount
Load Types (relay ratings)
Rated to control 20A receptacles with any output.
When using the Energi Savr Node to control
receptacles, it may be used with, but is not limited to,
the following:
– Monitors
– Fans
– Humidifiers
– Printers
Note: Refer to the manufacturer’s guidelines for
acceptable switching methods.
When using the Energi Savr Node to control
receptacles, it may NOT be suitable for use with
devices that require any of the following:
Shut-down process before power is interrupted,
such as computers.
Cool-down process before power is interrupted,
such as projectors.
Programming, such as clocks or DVRs.
Long warm-up cycle.
2
QSN
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node 0 –10 V-/Softswitch 20 A Receptacle/Fixture Controllers
369791e 3 08.05.19
Specifications (continued)
Load Types (relay ratings) (continued)
Not for use with loads that present a hazard if
automatically energized (e.g., heaters).
Any receptacles that are controlled by an automatic
control device must be marked withu” located on
the controlled receptacle outlet where visible after
installation as stated in 2014 NEC® Article 406.3(E).
Load Type
Relay Ratings
120 – 277 V~
QSN-4S20-S
QSN-4T20-S
347 V~
QSN-4S16-S-347
QSN-4T16-S-347
Tungste n 20 A 16 A
AC General Use 20 A 16 A
Electric Discharge Lamp 16 A 16 A
Electric Ballast
(NEMA 410)
16 A 16 A
Resistive 20 A 16 A
Inductive 20 A 16 A
Motor
1.0 HP 120 V~
2.0 HP 277 V~
Input Default Associations
Inputs/Outputs Zone 1 Zone 2 Zone 3 Zone 4
Group 1
Occ
X
Daylight
X
IR
X
Switch
X
Group 2
Occ
X
Daylight
X
IR
X
Switch
X
Group 3
Occ
X
Daylight
X
IR
X
Switch
X
Group 4
Occ
X
Daylight
X
IR
X
Switch
X
CCI
X X X X
Emergency CCI
X X X X
Softswitch 120 – 277V~
Softswitch relay is rated for 20A continuous use per
channel.
Relay is mechanically held.
0–10 V- Output Ratings (QSN-4T20-S)
Each output sinks up to 50mA maximum.
Each output sinks current only (load device must
provide 10V- supply).
Provides an IEC PELV / NEC® Class2 isolated 010V
output signal that conforms to IEC 60929.
Occupancy Sensors
Up to 16 occupancy sensors can be programmed to
the Energi Savr Node device.
Manual Programming: up to 4 occupancy sensors
wired directly to the Energi Savr Node device, up to
4 occupancy sensors wired to a QS Sensor Module
(QSM), and up to 10 wireless occupancy sensors
through the same QSM; the total programmed to the
Energi Savr Node device cannot exceed 16.
HHD (iPod/iPhone) Programming: up to 16 occupancy
sensors from any source (wired directly to the
Energi Savr Node device, wired to any other
Energi Savr Node device, or wired/wireless from any
QSM on the QS link); the total programmed to the
Energi Savr Node device cannot exceed 16.
Use Lutron occupancy sensors to control one or
more zones.
• Lutron occupancy sensors can be programmed to
automatically turn on the lights and receptacles in an
area when it becomes occupied and turn off the lights
and receptacles in an area after it becomes vacant.
For spaces that require vacancy mode operation
for lights, a single occupancy sensor can control a
zone of lights in vacancy mode and control a zone of
receptacles in occupancy mode.
3
QSN
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node 0 –10 V-/Softswitch 20 A Receptacle/Fixture Controllers
369791e 4 08.05.19
Specifications (continued)
Occupancy Sensors (continued)
Each of the four occupancy inputs can power one Lutron
occupant sensor.
Each area’s occupied scene and unoccupied scene can
be programmed independently.
Occupancy sensor must provide a dry-contact closure
or solid-state output.
Additional occupancy sensors can be used with the
Energi Savr Node device. Refer to the “Programming
Options and Features” table for system rules.
seeTouch QS Controls
seeTouch QS wallstations can be configured to control
ESN unit scenes or zones.
In zone toggle mode, zone buttons can be assigned to
one or more zones on any ESN unit connected to the
QS Link.
In scene mode, wallstations can be assigned to one or
more ESN units connected to the QS Link.
LED indicator displays zone or scene status.
Table 1: seeTouch QS Wallstation Configurations
# Buttons
Wallstation
Function
1 2 3 5 7
Zone Toggle
Scene 1, Off (toggle) 1, Of f 1, 2, Off 1–4, Off N/A
IR Wallstation or Receiver Input
Four inputs for IR receivers or wallstations for control of
lighting zones can be connected directly to the ESN unit
Use Lutron Pico wired control or CC-4BRL-WH
wallstation to control one or more zones.
Up to four additional wired wallstations or IR receivers
can be assigned when associated with a QSM.
Associate additional QSMs and sensors/controls with
ESN unit when programming with an Apple iPod touch
or iPhone. Refer to “Programming Options” section for
details.
Daylight Sensors
Lutron daylight sensors allow daylight harvesting with
programmable effect on light output.
Four daylight sensors can be connected directly to
the ESN unit.
Use Lutron EC-DIR-WH sensors to control one or
more zones.
Alternatively, up to 4 sensors (Lutron wired daylight
sensors or Radio Powr Savr daylight sensors) can be
assigned when associated with a QSM.
The maximum number of Lutron daylight sensors
(wired or wireless), either wired directly to the unit or
indirectly (associated with a QSM) cannot exceed 4.
Associate additional QSMs and sensors/controls
with ESN unit when programming with an Apple iPod
touch or iPhone. Refer to “Programming Options
section for details.
Contact Closure Input (CCI)
Activate scenes using momentary or maintained
closures from an external device such as a timeclock.
Start or stop Afterhours Mode using a maintained
closure.
The attached device must provide a dry-contact
closure or solid-state output.
Configurable for Normally-Open (NO) or
Normally-Closed (NC) operation.
Input is miswire-protected up to 36 V-.
4
QSN
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node 0 –10 V-/Softswitch 20 A Receptacle/Fixture Controllers
369791e 5 08.05.19
Specifications (continued)
Emergency Contact Closure Input
By default, contact closure input from Lutron Emergency
Lighting Interface (LUT-ELI-3PH), security, or fire
alarm systems turns all zones on to full output when
emergency state is detected.
Emergency contact closure input is normally closed (NC).
The ESN unit is shipped with a jumper pre-installed.
Response of each zone is configurable.
Attached devices, by default, will go to maximum output
and ignore control inputs.
No operations will be allowed until emergency signal is
cleared.
The attached device must provide a dry-contact closure
or solid-state output.
Input is miswire-protected up to 36 V-.
Emergency CCI cannot control other ESN units.
Functionality with GRAFIK Eye QS
• ESN unit follows GRAFIK Eye QS scene activations when
associated with the GRAFIK Eye QS.
• ESN unit responds to commands initiated by the GRAFIK
Eye QS astronomic time clock when associated with the
GRAFIK Eye QS.
• ESN unit operates in afterhours mode when associated
with a GRAFIK Eye QS that is in afterhours mode.
Functionality with QSE-IO
• ESN unit responds to scene commands initiated by the
QSE-IO if the QSE-IO DIP switches have been set to
either scene selection mode, zone toggle mode, partition
mode, or occupancy sensor mode.
Functionality with QSE-CI-NWK-E
Integrate ESN unit with touchscreens, PCs, A / V
systems, or other digital systems and devices.
Recall scenes and set/adjust zone levels.
IEC PELV / NEC® Class 2 Dry-Contact Switches
Four inputs for IEC PELV / NEC® Class 2 dry-contact
switches can be assigned to turn on and off one or more
zones.
Configure for momentary or maintained operation.
QS Link Limits
Each ESN unit can provide up to 14 Power Draw
Units (PDUs) for other QS devices. Refer to the QS
Link Power Draw Unit specification submittal (Lutron
P/N369405) for more information concerning PDUs.
The QS Link can have up to 100 devices and
100 zones.
Each ESN unit counts as 1 device towards the
100device limit.
Each ESN unit counts as 4 zones towards the
100zone limit.
QSM (QS Sensor Module)
Use the QSM to integrate Radio Powr Savr
occupancy sensors, Radio Powr Savr daylight
sensors, and Pico wireless controllers to control
zones on the ESN unit.
Associate 1 QSM per ESN unit with manual
programming.
Associate multiple QSMs per ESN unit with Apple
iPod touch or iPhone programming (requires
QSE-CI-AP-D and Wi-Fi router). See “Programming
Options” for details.
Assign up to 10 Radio Powr Savr occupancy sensors
per ESN unit via QSM.
Assign up to 4 Radio Powr Savr daylight sensors per
ESN unit via QSM.
Assign up to 10 Pico wireless controllers per ESN unit
via QSM.
The sensors and Pico wireless controllers associated
with the QSM should be mounted within 60 ft (18 m)
line of sight, or 30 ft (9 m) through walls, of the QSM.
Wire and power up to 4 wired sensors per QSM
Daylight Sensors
Occupancy Sensors
Infrared (IR) Receivers or Wallstations
Refer to QSM Specification Submittal for more
information.
5
QSN
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node 0 –10 V-/Softswitch 20 A Receptacle/Fixture Controllers
369791e 6 08.05.19
Wireless router may be removed for normal operation.
Ethernet connection may be made via an ESN
Programming Interface (QSE-CI-AP-D) or an ESN QS
unit with integral Ethernet jack.
Lutron recommends that an ESN Programming
Interface (or ESN QS unit with Ethernet jack) be wired
to an Ethernet jack in the space for ease of access
and proximity to power for the wireless router.
Works with any standard wireless router that supports
multicast packets.
Apple iPod touch or iPhone can program all ESN QS
units connected to an ESN Programming Interface via
the QS Link (except when part of a Quantum system).
ESN app is required and is available from the Apple
App Store online marketplace.
Programming Options
Manual Programming
Use buttons on the front of the ESN unit.
Use manual programming in installations with only one
ESN unit and with one QSM or fewer on the QS link.
HHD Programming
Requires ESN Programming Interface (QSE-CI-AP-D).
• Requires Apple iPod touch or iPhone mobile digital
device.
Use the intuitive programming application for the
Apple iPod touch or iPhone to program systems with
multiple ESN units and QSMs on the QS link.
Wireless router required for programming with an
Apple iPod touch or iPhone only.
QS Link
QS Link
QSM QSM QSM
ESN Unit ESN Unit ESN Unit
Apple iPod touch or iPhone
mobile digital device
Wireless Router
(by others)
ESN Programming Interface
QSE-CI-AP-D
Dedicated Ethernet Connection
for ESN units
1,2
1
Standard CAT5/CAT5E cable: Total length not to exceed 300 ft (100 m)
2
Note: ESN units are not designed to exist on an open network. Connection to an open network
could result in reduced performance and Ethernet connectivity issues.
6
QSN
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node 0 –10 V-/Softswitch 20 A Receptacle/Fixture Controllers
369791e 7 08.05.19
Programming Options and Features
Manual Programming HHD Programming
Requires ESN Programming Interface QSE-CI-AP-D
Requires Apple iPod touch or iPhone mobile digital device
ESN units connected to 1QS
Link
Not more than 1 Multiple (100 QS devices and 100 zone limits apply)
QSMs connected to 1 QS link Not more than 1 Multiple (100 QS devices limit applies)
Wired Occupancy Sensors
System Limits 4 connected directly to ESN unit;
Up to 4 wired to QSM
Maximum of 16 occupancy sensors per ESN
Up to 100 total occupancy sensors per QS link (wired and
wireless)
Can be assigned to Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same
QSlink
Occupancy Dependency
Supported
No Yes
Wireless Occupancy Sensors
System Limits Associate 10 occupancy sensors to QSM
to control zones on the ESN unit
Maximum of 16 occupancy sensors per ESN
Up to 100 total occupancy sensors per QS link (wired and
wireless)
Can be assigned to Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same
QSlink
Occupancy Dependency
Supported
No Yes
Wired Daylight Sensors
System Limits Maximum of 1 daylight sensor per zone
connected directly to the ESN unit or to the
QSM
Maximum of 2 daylight sensors per zone;
Up to 100 total daylight sensors per QS link (wired and
wireless)
Can be assigned to Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same
QSlink
Disable daylighting in Scenes No Yes
Wireless Daylight Sensors
System Limits Maximum of 1 daylight sensor per zone;
Associate wireless daylight sensors to
the QSM
Maximum of 2 daylight sensors per zone;
Associate up to 10 wireless daylight sensors per QSM;
Up to 100 total daylight sensors per QS link (wired and
wireless)
Can be assigned to Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same
QSlink
Disable daylighting in Scenes No Yes
Pico Wireless Controllers
System Limits Associate 10 Pico wireless controllers to
QSM to control zones on the ESN unit
Up to 100 total controls per QS link (wired wallstations, Pico
wireless controllers, IR receivers)
Can be assigned to Any zone on the local ESN unit Zones on ESN unit or share to other ESN units on same
QSlink
IR Receivers and Wallstations
System Limits 4 connect directly to the ESN unit;
Up to 4 wired to the QSM
Up to 100 total controls per QS link (wired wallstations, Pico
wireless controllers, IR receivers)
Can be assigned to Any zone on the local ESN unit Zones on ESN unit or share to other ESN units on same
QSlink
7
QSN
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node 0 –10 V-/Softswitch 20 A Receptacle/Fixture Controllers
369791e 8 08.05.19
Programming Options and Features (continued)
Manual Programming HHD Programming
Requires ESN Programming Interface QSE-CI-AP-D
Requires Apple iPod touch or iPhone mobile digital device
NEC® Dry-Contact Switches Inputs
Can be assigned to Any zone(s) on the connected ESN Any zone(s) on the connected ESN
Contact Closure Input
Can be assigned to Any zone(s) on the ESN unit Any or all local ESN unit zones
Functions • Sweep to off
• Enable/disable afterhours
• Turn on to preset and turn off
• Sweep to off
• Enable/disable afterhours
• Turn on to preset and turn off
• Load shed
Afterhours Configuration Afterhours timeout: 15 minutes
Blink-warn timeout: 5 minutes
Afterhours timeout and blink-warn timeouts are
configurable
Emergency Contact Closure Input
Can be assigned to Any zone(s) on the ESN unit Any or all local ESN zones
Emergency Light level Configurable Configurable
seeTouch QS wallstations
Scene Keypads assigned to Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link
Scene + Off Keypads
assigned to
Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link
Zone toggle keypad buttons
assigned to
Any zone(s) on the ESN unit Any zone(s) on on or more ESN units on the link
Change Keypad to Scene or
Zone
Yes Yes
Changing keypads to shade,
panic, fine tune
No Yes
Zone Configuration Parameters
Load type 010, 100, or switched 010, 100, or switched
High-end trim Adjustable Adjustable
Low-end trim Adjustable Adjustable
Absolute minimum level Adjustable Adjustable
Scenes
Available scenes Scenes 1–16 + Off Scenes 1–16 + Off
GRAFIK Eye QS Share scenes, timeclock events, afterhours
events, or remote zone mapping to ESN
units on QS Link
Share scenes, timeclock events, afterhours events, or
remote zone mapping to ESN units on QS Link
QSE-IO Scene, zone toggle, occupancy Scene, zone toggle, occupancy
QSE-CI-NWK-E Yes Yes
8
QSN
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node 0 –10 V-/Softswitch 20 A Receptacle/Fixture Controllers
369791e 9 08.05.19
Mechanical Dimensions
All dimensions shown as in (mm)
0.20 (5.16) Ø
1.41
(35.81)
1.00
(25.40)
11.25
(286)
13.25
(336.55)
0.88
(22.23)
9.25
(235)
7. 5 0
(190.50)
Do not use
side knockouts
Line Voltage Shield
1.80
(45.72)
3.14
(79.71)
1.03
(26.04)
9
QSN
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node 0 –10 V-/Softswitch 20 A Receptacle/Fixture Controllers
369791e 10 08.05.19
Wiring: QS Link
Only terminals 1, 3, and 4 connected
between devices that supply PDUs
Terminal 2 NEVER connected
between devices that supply PDUs
Devices that
supply PDUs
Devices that
consume PDUs
COM
+24 V
MUX
MUX
COM
MUX
MUX
QSM
QSM QSM
Wired
QS Keypad
Wired
QS Keypad
Wired
QS Keypad
Wired
QS Keypad
QS Input/
Output Interface
QS Input/
Output Interface
QS Link
power supply**
QS Link: no terminal 2QS Link: no terminal 2
QS Link: all 4 terminals
QS Link: all 4 terminals
QS Link: all 4 terminals
All 4 terminals connected to QS link
devices that consume PDUs
ESN QS unit
ESN QS unit
Terminal 2 (+24 V)
NEVER connected*
Terminal 2 (+24 V)
NEVER connected*
Terminal 2 (+24 V)
NEVER connected*
QS Link Wiring Rules
* Terminal 2 (+24 V) should NEVER be connected between devices that supply PDUs.
** For QS Link power supply wiring connection details, refer to the installation instructions for the specific power supply model being used.
10
QSN
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node 0 –10 V-/Softswitch 20 A Receptacle/Fixture Controllers
369791e 11 08.05.19
Wiring: IEC PELV / NEC® Class 2 Inputs
Blue/Gray**
Black
Red
Occupancy SensorDaylight/IR Sensor*
IR Transmitter IR Transmitter
Note: Maximum wire run length to each
input not to exceed 150 ft (46 m).
IR Receiver or
Wired Wallstation*
IEC PELV / NEC® Class 2
Dry-Contact Switch
Red
Black
Yellow
20 V: 20 V-
OCC: Occupancy Sensor
DAYLIGHT: Daylight Sensor
IR: IR Receiver*
SWITCH: IEC PELV / NEC® Class 2
COM: Common
LUTRON
Note: There are four input groups;
each group has the same inputs as shown in the diagram below.
Group 1 shown Group 2 shown
White
IR
Black
COM
Red
20 V
Input Group Wiring
20to 12AWG (0.5to 4.0mm
2
)
Strip length: 1/4in (6mm)
Torque: 5 in-lb (0.5 N•m)
* Note: Only one IR device may be connected per input. If the IR signal from a daylight sensor is
connected, a wall control may not be connected to the same input, and vice-versa.
** Connect the gray wire on -R model occupancy sensors.
11
QSN
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node 0 –10 V-/Softswitch 20 A Receptacle/Fixture Controllers
369791e 12 08.05.19
Wiring: Contact Closure Inputs (CCI and Emerg)
Contact Closure Wiring
20 to 12AWG (0.5 to 4.0mm
2
)
Strip length: 1/4in (6mm)
Torque: 5 in-lb (0.5 N•m)
CCI: Contact Closure Input
COM: Common
EMERG: Emergency
COM: Common
12
QSN
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node 0 –10 V-/Softswitch 20 A Receptacle/Fixture Controllers
369791e 13 08.05.19
Wiring: 4 Circuits, Multiple Feeds
Load Wiring
Two (2) 14 to 12AWG (2.5 to 4.0mm
2
)
Strip length: 3/8in (8.5mm)
Torque: 7 in-lb (0.79 N•m)
010 V- Wiring (QSN-4T20-S)
20 to 12AWG (0.5 to 4.0mm
2
)
Strip length: 1/4in (6mm)
Torque: 5 in-lb (0.5 N•m)
Connect only IEC PELV/NEC® Class 2 circuits or connect only non-IEC
PELV/NEC® Class 2 circuits to 010 V zones 14.
010 V zones 1–4 are not isolated from each other.
Negative (–) terminals are not internally connected to each other; both
positive (+) and negative (–) connections must be made.
Follow all national and local codes for separation requirements.
WARNING. Entrapment / Fire Hazard. To avoid the risk of entrapment, serious injury, or death, these controls must not be used to
control equipment which is not visible from every control location or which could create hazardous situations such as entrapment if
operated accidentally. Examples of such equipment which must not be operated by these controls include (but are not limited to)
motorized gates, industrial doors, space heaters, etc. It is the installer’s responsibility to ensure that the equipment being controlled is
visible from every control location and that only suitable equipment is connected to these controls. Failure to do so could result in
serious injury or death.
Distribution Panel
Neutral
Neutral
Neutral
Neutral
Neutral
Ground
Hot
Hot
Hot
Hot
Hot
Hot
Neutral
Neutral Wires
Ground
Lug
Switched Hot (1B)
Switched Hot (2B)
Switched Hot (3B)
Switched Hot (4B)
Hot Feed (1A)
Hot Feed (2A)
Hot Feed (3A)
Hot Feed (4A)
Load
Load
Zone Switching:
120 277 V~
010 V Zones:
(QSN-4T20-S)
0–10 V- Wiring
(QSN-4T20-S)
Zone
1
Zone
1
+
1A 2A 3A 4A1B 2B 3B 4B
+
+
+
+
+
+
+
Zone
3
Zone
3
Zone
2
Zone
2
Zone
4
Zone
4
010 V Outputs
u
u
Attention Installer
Any receptacles that are controlled by an automatic control device
must be marked with “u” located on the controlled receptacle outlet
where visible after installation as stated in 2014 NEC® Article 406.3(E).
Zone 4
Zone 3
Zone 2
Zone 1
13
QSN
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node 0 –10 V-/Softswitch 20 A Receptacle/Fixture Controllers
369791e 14 08.05.19
Wiring: 4 Circuits, Multiple Feeds, 120 V~ Receptacles and 347 V~ Lighting
Load Wiring
Two (2) 14 to 12AWG (2.5 to 4.0mm
2
)
Strip length: 3/8in (8.5mm)
Torque: 7 in-lb (0.79 N•m)
010 V- Wiring (QSN-4T16-S-347)
20 to 12AWG (0.5 to 4.0mm
2
)
Strip length: 1/4in (6mm)
Torque: 5 in-lb (0.5 N•m)
Connect only IEC PELV/NEC® Class 2 circuits or connect only non-IEC
PELV/NEC® Class 2 circuits to 010 V zones 14.
010 V zones 1–4 are not isolated from each other.
Negative (–) terminals are not internally connected to each other; both
positive (+) and negative (–) connections must be made.
Follow all national and local codes for separation requirements.
WARNING. Entrapment / Fire Hazard. To avoid the risk of entrapment, serious injury, or death, these controls must not be used to
control equipment which is not visible from every control location or which could create hazardous situations such as entrapment if
operated accidentally. Examples of such equipment which must not be operated by these controls include (but are not limited to)
motorized gates, industrial doors, space heaters, etc. It is the installer’s responsibility to ensure that the equipment being controlled is
visible from every control location and that only suitable equipment is connected to these controls. Failure to do so could result in
serious injury or death.
120 V~
Distribution Panel
347 V~
Distribution Panel
Attention Installer
Any receptacles that are controlled by an automatic control device
must be marked with “u” located on the controlled receptacle outlet
where visible after installation as stated in 2014 NEC® Article 406.3(E).
Neutral
Neutral
Ground
Ground
Hot
Hot
Hot
Hot
Hot
Neutral
Neutral Wires
Ground
Lug
Switched Hot (1B)
Switched Hot (2B)
Switched Hot (3B)
Switched Hot (4B)
Hot Feed (1A)
Hot Feed (2A)
Hot Feed (3A)
Hot Feed (4A)
Load
Load
Zone Switching:
120 347 V~
010 V Zones:
(QSN-4T16-S-347)
0–10 V- Wiring
(QSN-4T16-S-347)
Zone
1
Zone
1
+
1A 2A 3A 4A1B 2B 3B 4B
+
+
+
+
+
+
+
Zone
3
Zone
3
Zone
2
Zone
2
Zone
4
Zone
4
010 V Outputs
u
u
Zone 4
Zone 3
Zone 2
Zone 1
Voltage Barrier
Separates 120 V~ and 347 V~
as required by 2012 Canadian
Electrical Code, Article 12-3030
14
QSN
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node 0 –10 V-/Softswitch 20 A Receptacle/Fixture Controllers
369791e 15 08.05.19
Distribution Panel A
Distribution Panel B
Ground
Hot
Hot
Hot
Ground
Ground
Neutral
Neutral
Neutral
Neutral Wires
Ground
Lug
Switched Hot (1B)
Switched Hot (2B)
Switched Hot (3B)
Switched Hot (4B)
Hot Feed (1A)
Load
Load
Load
Load
Zone Switching:
120 277 V~; 347 V~
010 V Zones:
(QSN-4T20-S)
0–10 V- Wiring
(QSN-4T20-S)
Wiring: 4 Circuits, Single Feed
Load Wiring
Two (2) 14 to 12AWG (2.5 to 4.0mm
2
)
Strip length: 3/8in (8.5mm)
Torque: 7 in-lb (0.79 N•m)
010 V- Wiring (QSN-4T20-S)
20 to 12AWG (0.5 to 4.0mm
2
)
Strip length: 1/4in (6mm)
Torque: 5 in-lb (0.5 N•m)
Connect only IEC PELV/NEC® Class 2 circuits or connect only non-IEC
PELV/NEC® Class 2 circuits to 010 V- zones 14.
010 V- zones 14 are not isolated from each other.
Negative (–) terminals are not internally connected to each other; both
positive (+) and negative (–) connections must be made.
Follow all national and local codes for separation requirements.
Zone
1
Zone
3
Zone
2
Zone
4
Zone
1
1A 2A 3A 4A1B 2B 3B 4B
Zone
3
Zone
2
Zone
4
+
+
+
+
+
+
+
+
010 V Outputs
)Lutron, Lutron, Softswitch, Pico, Quantum, seeTouch, and GRAFIK Eye are trademarks of Lutron Electronics Co., Inc. registered in the U.S. and other countries.
Energi Savr Node and Radio Powr Savr are trademarks of Lutron Electronics Co., Inc.
Apple, iPhone, and iPod touch are trademarks of Apple Inc., registered in the U.S. and other countries.