Preset Dimming Controls
369314f 8 05.10.18
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Wireless Control Unit with EcoSystem
Accessory Controls: Contact Closure Input/Output
Interface (QSE-IO)
• Recallspresetlightlevelsforthefollowingsetofscenes
on the GRAFIK Eye QS control unit:
Scenes 1-4 and Off Scenes 9-12 and Off
Scenes 5-8 and Off Scenes 13-16 and Off
• Sequencescenes5-16,Enable/DisableZoneLockout,
Enable/Disable Scene Lockout, Enable/Disable Panic
Mode, Enable/Disable Timeclock.
• OccupancySensors.Anindividualinputcountsas
1occupancy sensor for the GRAFIK Eye QS control unit.
Each input can be assigned to either Scene Control or
ZoneControl(pleaserefertotheOccupancySensor(s)
section of this guide).
• ZoneToggle.Allowsaninputtotoggleoneormore
zones between programmable preset level(s) and off.
• ShadeOutputmode.AShadeColumnontheGRAFIK
Eye QS control unit can be linked to control outputs 1-3
and/or outputs 4-5 on the QSE-IO.
Accessory Controls:
DMX Output Interface (QSE-CI-DMX)
• AnyzoneontheGRAFIKEyeQScontrolunitcanbe
mappedtoanysingleDMX512Channel.
• AnyzoneontheGRAFIKEyeQScontrolunitcanbe
simultaneouslymappedtoanythreeDMX512channels
(providingRGB/CMYcontrol).
• DMXloadscannotbeusedwithdaylighting.
Accessory Controls: Ethernet and RS232 Interface
(QSE-CI-NWK-E)
• Allowsformonitoringandcontroloftheoutputsandlocal
scenes of the GRAFIK Eye QS control unit.
Accessory Controls: QS Keyswitch Wallstations
(QSWS2-KS)
• RecallspresetlightlevelsforanytwoscenesincludingOff
• Allowsfine-tuning(raise/lowerlevel)ofazoneorgroupof
zones
• Starts/Stopsscenesequencing(Scenes1-4or
Scenes 5-16)
• Enables/DisablesTimeclock
• Enables/Disablesoccupancysensors
• Enables/Disableddaylightsensors
• AllowstoggleofZone(s)toapresetlevelandoff
• Enables/Disablespanicmode
• Starts/Stopsafterhoursmode
EcoSystem Ballasts and Devices
• SupportsallHi-lumeand5-SeriesLEDdrivers(maximum64
per GRAFIK Eye control unit)
• SupportsallEcoSystemballasts(maximumof64ballasts
per GRAFIK Eye control unit)
• Supportsoccupancyanddaylightsensorswiredtoaballast
• DoesNOTsupportIRsensors(orIRkeypads)wiredtothe
ballast
Other Accessory Controls and Devices
• EnergiSavrNodeQS(ESN).RefertotheSpecification
Submittal for complete details.
Occupancy Sensor(s)
• TheGRAFIKEyeQScontrolunitworkswithoccupancy
sensors through either:
- Scene Control: Up to 16 sensors activate user-selected
occupancy and vacancy scenes.*
-ZoneControl:uptofoursensorsperzoneactivate
user-selected occupancy and vacancy zone levels.
• Occupancysensorsmayinclude:
- Contact closure sensors wired to CCI input on back of
GRAFIK Eye QS control unit
- Wireless Radio Powr Savr occupancy or vacancy sensors
(model numbers starting with LRF2)
- Wired sensors connected to EcoSystem ballasts or
interfaces
- Wired or wireless sensors connected to a QS Sensor
Module (QSM)
• Ifanysensorinagroupdetectsoccupancy,thenthe
GRAFIK Eye QS control unit will go to the designated
occupancy scene or zone level.
• Ifallsensorsinagroupdetectvacancy,thenthe
GRAFIK Eye QS control unit will go to the designated
vacancy scene or zone level.
• Lowbattery:theDiagnosticsscreenwilldisplayalow
battery symbol when applicable.
• IftheGRAFIKEyeQScontrolunitdoesnotreceiveasignal
from an occupancy sensor on the link (usually due to a
dead battery), the lights associated with that sensor will go
to the occupied level.
Specifications (continued)
* Applicable only to units that ship with firmware version 9.002 and
higher. Previous versions support up to 4 sensors.