Preset Dimming Controls
369309e 1 05.10.18
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Control Unit
LUTRON
GRAFIK Eye QS Control Unit
1
2
3
4
Off
Preset
Close
Open
Description
GRAFIK Eye QS is the premier energy-saving light
and shade control. The GRAFIK Eye QS control unit
includes an astronomic timeclock, intuitive lighting
presets, and direct shade control. Additionally, the
GRAFIK Eye QS control unit is compatible with all
Lutron wired QS products and systems, including
Quantum systems.
4$ in
(119 mm)
94 in
(239 mm)
4 in
(10 mm)
2 in
(51 mm)
Front View Side View
System Topology
LUTRON
LUTRON
LUTRON LUTRON
LUTRON
LUTRON LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON LUTRON
LUTRON
LUTRON LUTRON
LUTRON
LUTRON
LUTRON
Example of Wired System
QSE-CI-NWK-E
Sivoia QS
shade
seeTouch
QS
wallstation
seeTouch
QS
wallstation
Wired
occupancy
sensor
GRAFIK Eye QS
wireless control unit
GRAFIK Eye QS
wireless control unit
Wired QS link
Quantum
processor
QS Sensor
Module
Energi Savr
Node
unit
Mechanical Dimensions
Fits into a 4-gang U.S. backbox, 3` in (90.4 mm) deep (Lutron P/N 245-254) or
3 in (76.2 mm) deep (Lutron P/N 241-400)
1
Preset Dimming Controls
369309e 2 05.10.18
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Control Unit
Features
• Pushbuttonrecalloffourpresetlightingscenes,plus
Off.
• Sixteen(16)totalavailablescenes,plusOffscene.
• Zonescancontrolmanylightsourcetypesdirectly
or through power modules.
• Optionalintegratedshadecontrolbuttons,which
canalsobeaddedtotheunitafterinstallation.
• Masteroverridebuttonstoraiseandloweralllights.
• Allowssetupoflightingscenesandshadepresets
using buttons on the control unit.
• Built-ininfrared(IR)receiver.
• ExternalIRconnection.
• Built-inastronomictimeclock.
• Infoscreenshowszonelightlevelpercentage,
energysavings,zonelabeling,andprogramming.
• Lockoutoptionpreventsaccidentalchanges.
• Occupancysensorinputand24V-powerforone
occupancy sensor.
• QScommunicationlinkforseamlessintegrationof
lights,motorizedwindowtreatments,occupancy
sensors,wallstations,andintegrationinterfaces.
• CompatiblewithallLutronQSsystemcomponents.
• Backlitbuttonswithengravingmakeuniteasyto
locate and operate.
• Availableinavarietyofcolorsandfinishes.
LUTRON
OK
Optional
shade
control
keypad
Zone
control
Infrared
receiver
USBtype
miniB
Info
screen
Lighting
control
keypad
1
2
3
4
Off
Off
Preset
Close
1
2
3
4
Open
Preset
Close
Open
Note: General Engraving (-EGN) shown.
2
Preset Dimming Controls
369309e 3 05.10.18
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Control Unit
Key Design Features
• LightningstrikeprotectionmeetsANSI/IEEEstandard
62.41-1980.Canwithstandvoltagesurgesofupto
6000 V~andcurrentsurgesofupto3000A.
• Testedtowithstand16kVelectrostaticdischargewithout
damage or memory loss.
• RTISS-equipped:Compensatesinrealtimeforincoming
linevoltagevariations(novisibleflickerwith+/-2%
changeinRMSvoltagepercycle,and+/-2%Hzchange
infrequencypersecond).
• Powerfailurememoryretainsprogrammingandlightlevel
settingsforupto10yearsintheeventofapowerloss.
• TheGRAFIKEyeQScontrolunitsupplies3PowerDraw
Units(PDUs)ontheQSlink.
Forcompleteinformation,seethePower Draw Units on
the QS Link Spec (369405) on www.lutron.com.
• Faceplateishingedatthetopandbottom,andstays
openat180°foreaseofaccess.
Scene and Shade Buttons
• Large,roundedbuttonsareeasytouse.
• Backlitbuttonswithoptionalengravingmakeiteasyto
findandtooperatethecontrolunitinlowlightconditions
(backlight can be disabled).
• Optionalbuttonengravingisangleduptotheeyefor
easy reading.
• Predefinedlabelstickersareincludedforfieldlabeling.
• 4presetlightingscenes,plusOff,areaccessiblefromthe
frontofthecontrolunit.
• 12additionalscenesarestoredinthecontrolunitand
areaccessiblefromtheintegraltimeclock,seeTouchQS
wallstations,andQSinterfaces.
• Lightlevelsfadesmoothlybetweenscenes.Fadetime
canbesetdifferentlyforeachscene:0to59seconds,or
1to60minutes.MaximumfadetimefromSceneOffis
3seconds.
Input Power
• 120–127V~50/60Hz
• 220–240V~50/60Hz
Listings (120 127 V~)
• UL •NOM
• CSA •CEC(Title24)
Environment
• 32to104°F(0to40°C).
• Relativehumiditylessthan90%non-condensing.
Lighting Sources/Load Types
• ZonesonEnergiSavrNodeproductswiredtothesame
QS link
–ZonesonEnergiSavrNodewithSoftswitch
–ZonesonEnergiSavrNodefor0–10V
–ZonesonEnergiSavrNodewithEcoSystem
Pleasereferto“RemoteZoneMapping”forimportant
information.
• DMXchannel(s)throughDMXoutputinterface
(QSE-CI-DMX).Pleasereferto“AccessoryControls:DMX
OutputInterface”
Controlsthefollowinglightingsourceswithasmooth,
continuoussquarelawdimmingcurveoronafull
conduction non-dim basis:
• Incandescent
• Halogen
• Magneticlow-voltagetransformer
• LutronTu-Wireelectronicfluorescentdimmingballast
• LutronHi-lume2-wireLTELEDdriver
• AdvanceMarkXR electronic dimming ballast
• Neonandcoldcathode
• Non-dim(incandescent,magneticlow-voltage,Tu-Wire,
or neon/cold cathode)
• CreeLR4/6,120V~fixtures(forloadingcapacities,
pleaserefertotheLEDreportcardlocatedat
www.lutron.com/LEDtool)
Pleasereferto“Capacities”formoreinformation.
Controlsthefollowinglightingsourceswithasmooth,
continuoussquarelawdimmingcurveoronafull
conduction non-dim basis through separate Lutron power
interfaces:
• Electroniclow-voltagetransformers(useELVor
Phase-Adaptive power module)
• Lutron3-wirecontrolledelectronicfluorescentdimming
ballasts(usefluorescent3-wirepowermodule)
• Lutron3-wirecontrolledLEDdrivers(useflourescent
3-wire power module)
• Non-dim(useswitchingmodule)
• 0–10V(useTVI)
Note:Azonemaybeprogrammedtocontrolonlyone
load type at a time.
Specifications
3
Preset Dimming Controls
369309e 4 05.10.18
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Control Unit
Astronomic Timeclock
• Integraltoallunits.
• 7dailyschedulesavailable.
• Oneavailableholidayscheduleisprogrammablebydate
up to one year in advance.
• 25eventsperdaymaximum.
• Timeclockeventsareprogrammabletocontrolscenes
thataffectanyEnergiSavrNodeunitconnectedon
the QS link without changing the local scene on the
GRAFIKEye QS control unit.
• Astronomictimesareprogrammablebyintegralcity
database or by entering latitude and longitude. Sunrise/
Sunset times automatically adjust throughout the year
based on location.
• AutomaticallyadjustsforDaylightSavingTime(DST);
DSTisprogrammable.
• Localtimeclockeventscanactivateanyofthefollowing
features:
–Scenes1to16andOff
–Anyavailableshadepresets
–StartandEndafterhoursmode
–EnableandDisabledaylightingforallzones/groups
–EnableandDisableoccupancyforoccupancy/vacancy
sensors
–EnableandDisableoccupiedeventsforalloccupancy
sensors
System Communications and Capacities
• Low-voltagetypeIECPELV/NECR Class 2 wiring
connectscontrolunits,wallstations,motorizedshades,
andcontrolinterfaces.
• AQSsystemcanhaveupto100devicesand
100zones.
Infrared
• Infrared(IR)receiverallowsinfraredtransmitterstoselect
8scenes,raise/lowerlightingzones,orraise/lower
shades.
• Transmitterbuttonsimitatebuttonsonfaceplate.
• 50ft(15m)lineofsightrange.
• Terminalblockinfraredinputforconnectiontoawired
IRinputfromthird-partyequipment.
• IRcanbedisabledviaprogramming.
• WorkswithLutronGRX-ITandGRX-8ITinfraredremote
controls.
Shade Control
• TheGRAFIKEyeQScontrolunitcanincludeupto
3shade button columns. Each column has backlit open,
preset, close, and raise/lower buttons.
• Eachshadebuttoncolumncanbeprogrammedto
operateoneshadeoragroupofshades.(Shadesmay
be assigned to more than one shade button column).
• Faceplatesareavailablewith1,2and3shadebutton
columns.
Zone Control
• Eachzonehasadedicatedraiseandlowerbuttonto
adjustthezone.
• Eachzonehasadedicated7LEDbargraphforlevel
status.Percentageoflightlevelandenergysavedis
displayedontheinfoscreen.
• AllzoneinformationhasbluebacklitLEDs.Backlight
turnsoffwhenidlefor30seconds.
• High-endandlow-endtrimsettingsareadjustableper
zone(highendfrom99to55%;lowendfrom45to1%).
Note:Trimforremotezonesmustbeadjustedlocallyon
the Energi Savr Node unit.
• Eachzoneisprogrammabletoonlyoneloadtypeata
time.
Info Screen
• OLED(organicLED)screenisviewablefromallangles.
• Screenturnsoffwhenidlefor30seconds.
• Programmablezonelabels.
• Programmablescenelabels.
• Statusofreal-timezonepercentageandenergysavings.
• Programmabletimeclockschedules.
• Programmableshadelabels.
• Selectabledisplaylanguages:
–English –Spanish –French
–Italian –German –Portuguese
Specifications
4
Preset Dimming Controls
369309e 5 05.10.18
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Control Unit
Specifications
Accessory Controls: seeTouch QS Wallstations
(QSWS2)
• WiredseeTouchQSwallstationsprovidethefollowing
features:
–Accesstooneormoreofthe16scenesonthe
GRAFIK Eye QS control unit
–Zonetoggle,partitioning,sequencing,finetune,panic
mode, and timeclock enable/disable
–Contactclosureinputs
–Certainfunctionsareonlyavailableonspecific
wallstationconfigurations.RefertotheseeTouchQS
specificationsubmittal.
Accessory Controls: QS Sensor Module (QSM2)
• TheQSSensorModuleprovidesameanstolinkwired
or wireless occupancy sensors or daylight sensors, Pico
controls,andwiredinfraredsensorstoaGRAFIKEyeQS
control unit via the wired QS link.
–Occupancysensorswired(orwirelesslylinked)toa
QS Sensor Module can be used by one or more
GRAFIK Eye QS control units on the wired link.
–Daylightsensorswired(orwirelesslylinked)toa
QS Sensor Module can be used by one or more
GRAFIK Eye QS control units on the wired link.
–Infraredsensorscancontroleitheroneormore
zonesorscenesontheGRAFIKEyeQScontrolunit.
Functionalityvaries;refertothedocumentationforthe
QSSensorModulefordetails.
–PicowirelesscontrolswirelesslylinkedtoaQSSensor
Modulecanbeusedtocontroloneormorezonesor
scenes on the GRAFIK Eye QS control unit.
–Picowiredcontrolscanbeused,whenconnectedto
aQSSensorModule,tocontroloneormorezonesor
scenes on the GRAFIK Eye QS control unit.
Accessory Controls: Contact Closure Input/Output
Interface (QSE-IO)
• Recallspresetlightlevelsforthefollowingsetofsceneson
the GRAFIK Eye QS control unit:
Scenes1-4andOff Scenes9-12andOff
Scenes5-8andOff Scenes13-16andOff
• Sequencescenes5-16,Enable/DisableZoneLockout,
Enable/DisableSceneLockout,Enable/DisablePanicMode,
Enable/DisableTimeclock.
• OccupancySensors.Anindividualinputcountsas
1occupancysensorfortheGRAFIKEyeQScontrolunit.
EachinputcanbeassignedtoeitherSceneControlorZone
Control(pleaserefertotheOccupancySensor(s)sectionof
this guide).
• ZoneToggle.Allowsaninputtotoggleoneormorezones
betweenprogrammablepresetlevel(s)andoff.
• ShadeOutputmode.AShadeColumnontheGRAFIKEye
QS control unit can be linked to control outputs 1-3 and/or
outputs 4-5 on the QSE-IO.
Accessory Controls:
DMX Output Interface (QSE-CI-DMX)
• AnyzoneontheGRAFIKEyeQScontrolunitcanbe
mappedtoanysingleDMX512Channel.
• AnyzoneontheGRAFIKEyeQScontrolunitcanbe
simultaneouslymappedtoanythreeDMX512channels
(providingRGB/CMYcontrol).
• DMXloadscannotbeusedwithdaylighting.
Accessory Controls: Ethernet and RS232 Interface
(QSE-CI-NWK-E)
• Allowsformonitoringandcontroloftheoutputsandlocal
scenesoftheGRAFIKEyeQScontrolunit.
Accessory Controls: QS Keyswitch Wallstations
(QSWS2-KS)
• RecallspresetlightlevelsforanytwoscenesincludingOff.
• Allowsfine-tuning(raise/lowerlevel)ofazoneorgroupof
zones.
• Starts/Stopsscenesequencings(Scenes1-4or
Scenes5-16)
• Enables/DisablesTimeclock
• Enables/Disablesoccupancysensors
• Enables/Disableddaylightsensors
• AllowstoggleofZone(s)toapresetlevelandoff.
• Enables/Disablespanicmode.
• Starts/Stopsafterhoursmode.
Other Accessory Controls and Devices
• EnergiSavrNode QS (ESN).Seethespecificationsubmittal
forcompletedetails.
5
Preset Dimming Controls
369309e 6 05.10.18
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Control Unit
Specifications
Occupancy Sensor(s)
• TheGRAFIKEyeQScontrolunitworkswithoccupancy
sensors through either:
–SceneControl:Upto16sensorsactivateuser-selected
occupancy and vacancy scenes.*
–ZoneControl:uptofoursensorsperzoneactivate
user-selectedoccupancyandvacancyzonelevels.
• Occupancysensorsmayinclude:
–ContactclosuresensorswiredtoCCIinputonbackof
GRAFIK Eye QS control unit
–WiredorwirelesssensorsconnectedQSSensorModule
(QSM)
• Ifanysensorinagroupdetectsoccupancy,thenthe
GRAFIK Eye QS control unit will go to the designated
occupancysceneorzonelevel.
• Ifallsensorsinagroupdetectvacancy,thenthe
GRAFIK Eye QS control unit will go to the designated
vacancysceneorzonelevel.
• Lowbattery:theDiagnosticsscreenwilldisplayalow
battery symbol when applicable.
• IftheGRAFIKEyeQScontrolunitdoesnotreceivea
signalfromanoccupancysensoronthelink(usuallydue
to a dead battery), the lights associated with that sensor
will go to the occupied level.
Daylight Sensor(s)
• TheGRAFIKEyeQScontrolunitallowsdaylightsensors
tocontroloneormorelightingzonestoadjustelectric
light levels based on measured daylight levels.
• Daylightsensorsmayinclude:
–WiredorwirelesssensorsconnectedtoaQSsensor
module (QSM)
• Adaylightsensorcancontroloneormore
GRAFIKEyeQScontrolunitzones:
–Eachzonecanbecalibratedtotargetlightlevels
–Azonecanbecontrolledbynomorethanonedaylight
sensor
• Daylightcontrolcanbeenabledordisabledona
scene-by-scene basis
–Bydefault,daylightcontrolisenabledinallscenes
Note:DaylightcontrolthroughtheGRAFIKEyeQScontrol
unitonlyaffectsselectlightingloads.Shadegroups
cannotbecontrolledbydaylightsensors.Daylightingdoes
notaffectDMXorRGB/CMYDMXloads.
DaylightingofRemoteZoneslinkedtoEnergiSavrNode
zonesmustbeconfiguredattheEnergiSavrNodeunitor
throughtheEnergiSavrNodeappforiPod.
Contact Closure Input (CCI)
with Power Supply Output
• EachGRAFIKEyeQScontrolunithasonecontactclosure
input (Terminal A).
–Theattacheddevicemustprovideadrycontactclosure
or solid-state output.
–Inputismiswire-protectedupto36V-.
• Thecontactclosureiscapableofacceptingthefollowing
typesofinputs:
–Maintained(default):TheGRAFIKEyeQScontrolunitwill
act on both a contact closure and a contact open/release
event.
–Momentary:TheGRAFIKEyeQScontrolunitwillacton
only contact closure events.
• EachGRAFIKEyeQScontrolunitcansupply
50mA maximum at 24 V-.
–Usefulforpoweringoccupancysensors.
–Anauxiliarypowersupplymustbeusedifthedevice
requiresmorethan50mA.
• TheCCIiscapableofoperatinginthefollowingmodes
–Occupancy:Ifanoccupancysensoriswireddirectlyto
the GRAFIK Eye QS control unit.
–Emergency:ThissettingallowstheGRAFIKEye QS
control unit to work with a LUT-ELI. When an emergency
situationisdetected,alllightswillgotofullon,andno
operations will be allowed until the emergency signal is
cleared.
–Afterhours:AllowstheCCItostartandendtheafterhours
mode.
–Timeclock:AllowstheCCItoenableanddisablethe
timeclock.
–SceneLockout:Preventstheuserfrommakingany
changes to the control unit. The current scene will stay on
until the CCI enables normal operation.
–SaveNever:Preventsanychangesfrombeingsaved
while the CCI is being used.
–DisableCCI:TheCCIwillhavenoeffectonthesystem
andwillnotappearonthelistofavailablesensors.
Security Lockout Password
• A4-characterpassword(usingcharactersAtoZand
0to 9) can be enabled/disabled to lock out access to the
Programming Menu.
• Bydefaultthereisnopasswordenabledonthe
GRAFIKEye QS control unit.
• Ifcasethe4-digitpasswordisforgotten,contactLutron
Customer Assistance to regain access.
* Applicable only to units that ship with firmware version 9.002 and higher. Previous versions support up to 4 sensors.
6
Preset Dimming Controls
369309e 7 05.10.18
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Control Unit
Remote Zone Mapping
• MapaGRAFIKEyeQSzonedirectlytoanEnergiSavr
Node output so that programmed scenes in the GRAFIK
EyeQScontrolunitwilldirectlycontroltheoutputlevelsof
the Energi Savr Node.
• Adjusthigh-endandlow-endtrimforremotezonesthrough
theEnergiSavrNodeorEnergiSavrappsoftware.
• ChangeloadtypesofremotezonesthroughtheEnergiSavr
NodeorEnergiSavrappsoftware.
• ConfiguredaylightingforremotezonesthroughtheEnergi
SavrNodeorEnergiSavrappsoftware.
• Required:
–GRAFIKEyeQScontrolunitwithfirmwareversion7.000
or higher
–EnergiSavrNodeunitwithfirmwareversion6.000or
higher
–EnergiSavrappversion6.0.0orhigher(requiredonlyif
theEnergiSavrNodeunithasbeenconfiguredusingthe
app)
Partitioning
• Whenpartitionisopen,creatingonelargespace,
automaticallycombineslightingpresetfunctionsformultiple
GRAFIK Eye QS control units.
• Whenpartitionisclosed,creatingtwoormoresmaller
spaces,lightingpresetfunctionsbecomeindependent.
• RequiresoneQSWS2-2Bwallstation,aGRX-IRPSinfrared
transmitter/receiverpair,andaGRX-12VDCpowersupply
foroperation.
• Ifoccupancysensorsarerequiredinapartitionedspace,
note that each room’s occupancy sensor(s) will operate
independentofthepartitionstatus.
Specifications
7
Preset Dimming Controls
369309e 8 05.10.18
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Control Unit
220 240 V~ 50 / 60 Hz 120 127 V~ 50 / 60 Hz
Unit Capacity (watts) 3000 2000
MLV 3000 VA / 2400 W 2000 VA / 1600 W
ZoneCapacity(watts) 40 1200 25 800
MLV 40
1200 VA / 40 960 W 25 800 VA / 25 600 W
Load Type Notes (Zones 1, 2 and 3)
• Allelectroniclow-voltage(ELV)lightingusedwithaninterfacemustberatedforreversephasecontroldimming.Before
installinganELVlightsource,verifywiththemanufacturerthattheirtransformercanbedimmed.Whendimming,an
ELVinterface(suchasthePHPM-PA-DV-WH)mustbeusedwiththecontrolunit.
• Notallzonesmustbeconnected;however,connectedzonesmusthaveaminimumloadasspecifiedabove.
• Maximumtotallightingloadforamagneticlow-voltage(MLV)variesbyinputvoltage:
120 127 V~: 800 VA / 600 W
220 240 V~: 1200 VA / 960 W
• MaximumtotallightingloadforLutronTu-WireandAdvanceMarkXR electronic dimming ballasts (120 to 127 V~ only)
mustnotexceed6Aperzoneor16Aperunit.
• Nozonemaybeloadedwithmorethanthecapacityspecifiedabove.Forhigherwattageapplications,orfor277V~
applications,useLutronpowermodulePHPM-PA,PHPM-WBX,PHPM-PA-DV,PHPM-SW,orPHPM-WBX-DV.
• Forcontrollinglow-wattageloads(CFL,LED)inanon-dimapplication,contactLutronCustomerAssistanceforthe
appropriate solution.
System Limits
• TheQSwiredcommunicationlinkislimitedto100devicesor100zones.
Capacities
8
Preset Dimming Controls
369309e 9 05.10.18
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Control Unit
GRAFIK Eye QS Control Unit
Custom Color Options and Model Numbers
You must order a Base Unit and a Faceplate Kit
See Standard Color Combinations page for faceplate, stripe, and button colors
QSGFP - -
Faceplate
Prefix
Color/
Finish
Number
ofShade
Columns
Omit = none
1 = 1 column
2 = 2 columns
3 = 3 columns
Architectural Matte
Finishes
Standard
(ship in 48 hours)
White WH
Ivory IV
Beige BE
Gray GR
Brown BR
Black BL
Almond AL
Light Almond LA
Architectural Metal
Finishes
BrightBrass BB
BrightChrome BC
BrightNickel BN
SatinBrass SB
Satin Chrome SC
Satin Nickel SN
AntiqueBrass QB
AntiqueBronze QZ
Anodized Aluminum
Finishes
Clear CLA
Black BLA
Brass BRA
Satin Color Matte
Finishes
Snow SW
Biscuit BI
Eggshell ES
Taupe TP
Midnight MN
Limestone LS
Stone ST
DesertStone DS
Terracotta TC
Hot HT
Goldstone GS
Palladium PD
Plum PL
Turquoise TQ
Bluestone BG
Sea Glass SG
Greenbriar GB
Sienna SI
Merlot MR
Mocha Stone MS
Top
Door
Color
Faceplate Kit
(includes coordinating stripe and buttons)
Faceplate Custom Color/Finish Codes
Keypad
Engraving
Code
Keypad Engraving Codes
Omit = Unengraved
Shipswithengravingcertificatethat
customer can redeem at no charge
EGN = General Engraving
NST = Non-Standard Text Engraving
Please visit the GRAFIK Eye QS website
at www.lutron.com/grafikeyeqs
forcustomengravingforms.Submit
completedformwithorder,andunitwill
shipengravedasspecifiedbycustomer.
Omit = same as
unit
T = Translucent
Base Unit
QSGR - _ P
Prefix
Number
ofZones
3=3zones
4=4zones
6=6zones
Phase Control Triac
OK
12
3
4
5
6910
11 12
13
14
7
815 16
9-16
1-8
1
2
3
4
Off
OK
12
3
4
5
6910
11 12
13
14
7
815 16
9-16
1-8
Open
Preset
Close
Lighting
keypad
Shade
column
Example:
QSGR-6P
6-zonebaseunit
and
QSGFP-2IV-EGN
Ivoryfaceplatekitwithtwo
shade columns and general
engraving
9
Preset Dimming Controls
369309e 10 05.10.18
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Control Unit
QSGB - 5B - WH -
CustomButton
KitPrefix
Keypad
Engraving
Code
Button
Configuration
3BRL=3-buttonwith
raise/lower
(shade column)
5B=5-button
(lighting keypad)
Button
Color/
Finish
GRAFIK Eye QS Control Unit
Custom Options and Model Numbers
See previous page for Other Custom Model Numbers
See Standard Color Combinations page for faceplate, stripe, and button colors
Custom Button Kit
Button Kit Custom
Color/Finish Codes
Architectural Matte
Finishes
White WH
Ivory IV
Beige BE
Gray GR
Brown BR
Black BL
Almond AL
Light Almond LA
Satin Color Matte
Finishes
Snow SW
Biscuit BI
Eggshell ES
Taupe TP
Custom Stripe Kit
QSGS - WH
Stripe
Kit
Prefix
Stripe Color/
Finish
Stripe Custom Color/Finish Codes
Same as Faceplate colors on previous page
Keypad Engraving Codes
Omit = Unengraved
Shipswithengravingcertificatethat
customer can redeem at no charge
EGN = General Engraving
NST = Non-Standard Text Engraving
Please visit the GRAFIK Eye QS website
at www.lutron.com/grafikeyeqs
forcustomengravingforms.Submit
completedformwithorder,andunitwill
shipengravedasspecifiedbycustomer.
OK
12
3
4
5
6910
11 12
13
14
7
815 16
9-16
1-8
1
2
3
4
Off
OK
12
3
4
5
6910
11 12
13
14
7
815 16
9-16
1-8
Open
Preset
Close
Lighting
keypad
Shade
column
10
Preset Dimming Controls
369309e 11 05.10.18
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Control Unit
GRAFIK Eye QS Control Unit Standard Color Combinations
See previous pages for Custom Model Numbers
Suffix Faceplate (F) Stripe (S) Button (B)
Architectural Matte
WH White Gray White
IV Ivory Beige Ivory
BE Beige Ivory Beige
GR Gray Black Gray
BR Brown Black Brown
BL Black Gray Black
AL Almond Light Almond Almond
LA Light Almond Almond Light Almond
Architectural Metal
BB BrightBrass Black Black
BC BrightChrome Black Black
BN BrightNickel Black Black
SB SatinBrass Black Black
SC SatinChrome Black Black
SN SatinNickel Black Black
QB AntiqueBrass Black Black
QZ AntiqueBronze Black Black
Anodized
CLA Black Black
BLA Black Black Black
BRA Brass Black Black
Suffix Faceplate (F) Stripe (S) Button (B)
Satin Matte
MN Midnight Gray Black
TP Taupe Gray Taupe
SW Snow Gray Snow
ES Eggshell Beige Eggshell
BI Biscuit Eggshell Biscuit
LS Limestone Gray Gray
ST Stone Gray Gray
DS DesertStone Taupe Taupe
TC Terracotta Taupe Taupe
BG Bluestone Gray Gray
HT Hot Taupe Taupe
MR Merlot Taupe Taupe
SI Sienna Brown Brown
GB Greenbriar Gray Gray
SG Sea Glass Gray Gray
MS Mocha Stone Taupe Taupe
GS Goldstone Ivory Ivory
PD Palladium Gray Gray
PL Plum Taupe Taupe
TQ Turquoise Gray Gray
LUTRON
1
2
3
4
Off
Preset
Close
Open
F(faceplate)
F(faceplate)
B(buttons)
S (stripe)
Faceplateiscomprisedofatopandbottom.
The bottom will always be the color indicated
under“faceplate.”Thetopmaybethe
samecolorortranslucent.Usethechartfor
faceplatesthathavethesamecolortopand
bottom.Ifatranslucentlidischosen,the
stripe will automatically be the same color as
the bottom lid.
Example:
IfyouorderQSGR-4P-1WH,yourGRAFIK
EyeQScontrolunitwith4lightingzonesand
1shadezonewillcomewithawhitefaceplate
(both top and bottom), gray stripe, and white
buttons.
11
Preset Dimming Controls
369309e 12 05.10.18
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Control Unit
Wiring Diagrams
1234
12
ABC
123456LN
Load wiring
Communication link
Occupancy sensor/contact closure input and 24 V- power
IR input
Terminations
12
Preset Dimming Controls
369309e 13 05.10.18
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Control Unit
Power Group Wiring Example
OntheQSlink,therearedevicesthatsupplypoweranddevicesthatconsumepower.Eachdevicehasaspecific
numberofPowerDrawUnits(PDUs)iteithersuppliesorconsumes.APowerGroupconsistsofonedevicethat
suppliespowerandoneormoredevicesthatconsumepower;eachPowerGroupmayhaveonlyonepower-supplying
device.RefertothePower Draw Units on the QS LinkSpec(369405)onwww.lutron.comformoreinformation
concerningPDUs.
Within Power Groups on the QS link, connect all 4 terminals (1, 2, 3, and 4), shown by the letter A in the diagram.
BetweendevicesontheQSlinkthatsupplypower,connectonlyterminals1,3,and4(NOTterminal2),shownbythe
letterBonthediagram.
Wiring can be T-tapped or daisy-chained.
LUTRON
LUTRON LUTRON
LUTRON
LUTRON
LUTRON
Power Group 1
Power Group 2
Power Group 3
A
A
A
B
B
B
(Do not connect
terminal 2: 24 V-)
(Do not connect
terminal 2: 24 V-)
(Do not connect
terminal 2: 24 V-)
Connect all 4
terminals within a
power group:
1: Common
2: 24 V-
3 and 4: Data
Connect only 3
terminals between
power groups:
1: Common
3 and 4: Data
Do not connect
Terminal 2: 24 V-
A
B
GRAFIK Eye QS
control unit
Supplies PDUs
QS Power Supply
Supplies PDUs
Energi Savr Node QS unit
Supplies PDUs
Control Interfaces
Consume PDUs
Control Interfaces
Consume PDUs
Quantum panel
Supplies PDUs
Wallstations
Consume PDUs
Wallstations
Consume PDUs
Wallstations
Consume PDUs
QS Sensor Module with
wired Occupancy Sensor
Consumes PDUs
Wireless Occupancy Sensor
does not consume PDUs
13
Preset Dimming Controls
369309e 14 05.10.18
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Control Unit
Mounting
Line Voltage Wiring
Fits into a 4-gang
U.S. backbox,
3` in (90.4 mm) deep
(Lutron P/N 245-254)
or
3 in (76.2 mm) deep
(Lutron P/N 241-400)
1234
12
ABC
123456LN
Distribution Panel
120 – 127 V~ 50 / 60 Hz
or
220 – 240 V~ 50 / 60 Hz
1234
12
ABC
123456LN
To Load 1
To Load 2
To Load 3
To Load 4
To Load 5
To Load 6
Rear of
QS control unit
• Pullpowerwiringfromdistributionpanelandtolightfixtures.
• Eachlinevoltageterminalcanacceptone12AWG(4.0mm
2
) wire.
• ConsultLutronfornon-dimrelaywiringand/orloadsideemergencytransferwiring.
Mounting
screws (4)
GRAFIK Eye
QS control unit
Hinged
bottom lid
Hinged
top lid
Line voltage (Hot/Live)
is labeled L.
14
Preset Dimming Controls
369309e 15 05.10.18
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Control Unit
IEC PELV/NECR Class 2 QS System Wiring
• Wiringcanbedaisy-chainedorT-tapped.
• Wiringmustberunseparatelyfromline/mainsvoltage.
• Totallengthofcontrollinkmustnotexceed2000ft(610m).
LUTRON
LUTRON
LUTRON
LUTRONLUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON LUTRON LUTRON
LUTRON
GRAFIK Eye QS
Control Unit
Sivoia QS
Shade
seeTouch QS
wallstations
LUTRON
LUTRON
LUTRON
LUTRONLUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON LUTRON LUTRON
LUTRON
Daisy-Chain Wiring Example
T-Tap Wiring Example
GRAFIK Eye QS
Control Unit
Sivoia QS
Shade
Sivoia QS
smart panel
Sivoia QS
smart panel
seeTouch QS
wallstations
Wire Sizes (check compatibility in your area)
QS Link Wiring Length Wire Gauge Lutron Cable Part Number
Lessthan500ft(153m) Power (terminals 1 and 2)
1 pair 18 AWG (1.0 mm
2
) GRX-CBL-346S(non-plenum)
GRX-PCBL-346S(plenum)
Data(terminals3and4)
1 twisted, shielded pair 22 AWG (0.5 mm
2
)
500to2000ft
(153 to 610 m)
Power (terminals 1 and 2)
1 pair 12 AWG (4.0 mm
2
) GRX-CBL-46L(non-plenum)
GRX-PCBL-46L(plenum)
Data(terminals3and4)
1 twisted, shielded pair 22 AWG (0.5 mm
2
)
)Lutron,Lutron,GRAFIKEye,Hi-lume,Quantum,
seeTouch,Sivoia,Softswitch,Tu-Wire,Picoand
EcoSystemaretrademarksofLutronElectronicsCo.,
Inc., registered in the U.S. and other countries.
EnergiSavrNodeandRTISSaretrademarksof
Lutron Electronics Co., Inc.
iPodisatrademarkofAppleInc.registeredinthe
U.S. and other countries.
NECisaregisteredtrademarkofNationalFire
Protection Association, Quincy, Massachusetts.
AdvanceandMarkXareregisteredtrademarksof
Philips Electronics North America Corporation.
15