Preset Dimming Controls
369309e 6 05.10.18
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Control Unit
Specifications
Occupancy Sensor(s)
• TheGRAFIKEyeQScontrolunitworkswithoccupancy
sensors through either:
–SceneControl:Upto16sensorsactivateuser-selected
occupancy and vacancy scenes.*
–ZoneControl:uptofoursensorsperzoneactivate
user-selectedoccupancyandvacancyzonelevels.
• Occupancysensorsmayinclude:
–ContactclosuresensorswiredtoCCIinputonbackof
GRAFIK Eye QS control unit
–WiredorwirelesssensorsconnectedQSSensorModule
(QSM)
• Ifanysensorinagroupdetectsoccupancy,thenthe
GRAFIK Eye QS control unit will go to the designated
occupancysceneorzonelevel.
• Ifallsensorsinagroupdetectvacancy,thenthe
GRAFIK Eye QS control unit will go to the designated
vacancysceneorzonelevel.
• Lowbattery:theDiagnosticsscreenwilldisplayalow
battery symbol when applicable.
• IftheGRAFIKEyeQScontrolunitdoesnotreceivea
signalfromanoccupancysensoronthelink(usuallydue
to a dead battery), the lights associated with that sensor
will go to the occupied level.
Daylight Sensor(s)
• TheGRAFIKEyeQScontrolunitallowsdaylightsensors
tocontroloneormorelightingzonestoadjustelectric
light levels based on measured daylight levels.
• Daylightsensorsmayinclude:
–WiredorwirelesssensorsconnectedtoaQSsensor
module (QSM)
• Adaylightsensorcancontroloneormore
GRAFIKEyeQScontrolunitzones:
–Eachzonecanbecalibratedtotargetlightlevels
–Azonecanbecontrolledbynomorethanonedaylight
sensor
• Daylightcontrolcanbeenabledordisabledona
scene-by-scene basis
–Bydefault,daylightcontrolisenabledinallscenes
Note:DaylightcontrolthroughtheGRAFIKEyeQScontrol
unitonlyaffectsselectlightingloads.Shadegroups
cannotbecontrolledbydaylightsensors.Daylightingdoes
notaffectDMXorRGB/CMYDMXloads.
DaylightingofRemoteZoneslinkedtoEnergiSavrNode
zonesmustbeconfiguredattheEnergiSavrNodeunitor
throughtheEnergiSavrNodeappforiPod.
Contact Closure Input (CCI)
with Power Supply Output
• EachGRAFIKEyeQScontrolunithasonecontactclosure
input (Terminal A).
–Theattacheddevicemustprovideadrycontactclosure
or solid-state output.
–Inputismiswire-protectedupto36V-.
• Thecontactclosureiscapableofacceptingthefollowing
typesofinputs:
–Maintained(default):TheGRAFIKEyeQScontrolunitwill
act on both a contact closure and a contact open/release
event.
–Momentary:TheGRAFIKEyeQScontrolunitwillacton
only contact closure events.
• EachGRAFIKEyeQScontrolunitcansupply
50mA maximum at 24 V-.
–Usefulforpoweringoccupancysensors.
–Anauxiliarypowersupplymustbeusedifthedevice
requiresmorethan50mA.
• TheCCIiscapableofoperatinginthefollowingmodes
–Occupancy:Ifanoccupancysensoriswireddirectlyto
the GRAFIK Eye QS control unit.
–Emergency:ThissettingallowstheGRAFIKEye QS
control unit to work with a LUT-ELI. When an emergency
situationisdetected,alllightswillgotofullon,andno
operations will be allowed until the emergency signal is
cleared.
–Afterhours:AllowstheCCItostartandendtheafterhours
mode.
–Timeclock:AllowstheCCItoenableanddisablethe
timeclock.
–SceneLockout:Preventstheuserfrommakingany
changes to the control unit. The current scene will stay on
until the CCI enables normal operation.
–SaveNever:Preventsanychangesfrombeingsaved
while the CCI is being used.
–DisableCCI:TheCCIwillhavenoeffectonthesystem
andwillnotappearonthelistofavailablesensors.
Security Lockout Password
• A4-characterpassword(usingcharactersAtoZand
0to 9) can be enabled/disabled to lock out access to the
Programming Menu.
• Bydefaultthereisnopasswordenabledonthe
GRAFIKEye QS control unit.
• Ifcasethe4-digitpasswordisforgotten,contactLutron
Customer Assistance to regain access.