Control Functionality
Occupant Enters:
Lights do not automatically turn on when an occupant enters the space; lights must be turned
on manually. Maximum light level is set to 80%.
When Occupied:
Automatic: Overhead lights dim/brighten based on daylight availability. There is one perimeter daylight zone.
Manual: Occupant uses wall dimmers to set desired light levels for both general and white-board lights.
Occupant Exits:
All lights automatically turn off 15 minutes after all occupants exit.
Add a Vive wireless hub to enable simple setup and re-zoning, system monitoring, timeclock
functionality, and advanced integration.
Symbol Model Number Description Qty
RMJS-8T-DV-B PowPak dimming module with 0-10 V 3
LRF2-DCRB-WH Radio Powr Savr wireless daylight sensor 1
LRF2-VKLB-P-WH
Radio Powr Savr wireless corner-mount
vacancy sensor
1
PJ2-3BRL-GWH-L01 Pico wireless 3-button with raise/lower control 2
PICO-WBX-ADAPT Pico wallbox adapter 2
Line-voltage
wiring
Clear Connect
RF Communication
DZ 1 =
Daylight Zone
Low-voltage
wiring
DZ 1 DZ 1 DZ 1
2 2 2
2 2 2
2 2 2
1
1
1
21
Code Notes: For non-daylight classrooms, all general lighting can be connected to a single 0-10 V dimming module.
Receptacle Control is required for Shop and Laboratory classrooms.
Want to add a Vive wireless hub for more features? Go to lutron.com/vive for complete compatibility and design details.
This solution requires 0-10 V enabled ballasts and drivers by others.