by
Private Office | New Construction
ASHRAE 90.1-2010
Symbol Model Number Description Qty
FCJS-010 Wireless Fixture Control with 0-10 V 2
RMJS-20R-DV-B 20 A PowPak relay module 1
FC-SENSOR PowPak Fixture Sensor 2
PJ2-3BRL-GWH-L01 Pico wireless 3-button with raise/lower control 1
PICO-WBX-ADAPT Pico wallbox adapter 1
FCJS models are capable of controlling up to 3 ballasts or drivers. Review the “Vive PowPak Fixture Controls” submittal document for more design details.
Want to add a Vive wireless hub for more features? Go to lutron.com/vive for complete compatibility and design details.
This solution requires 0-10 V enabled ballasts and drivers by others.
Control Functionality
Occupant Enters:
Lights do not automatically turn on when an occupant enters the space; lights must be turned on manually.
Maximum light level is set to 80%. Controlled receptacles automatically regain power when occupant enters.
When Occupied:
Automatic: Overhead lights dim/brighten based on daylight availability. There are two perimeter daylight zones.
Manual: Occupant uses wall dimmer to set desired light levels for all lights.
Occupant Exits:
All lights automatically turn off 15 minutes after all occupants exit. 50% of all receptacles automatically turn off
15 minutes after all occupants exit.
Add a Vive wireless hub to enable simple setup and re-zoning, system monitoring, timeclock
functionality, and advanced integration.
Line-voltage
wiring
Clear Connect
RF Communication
DZ 1 & DZ 2 =
Daylight Zones
Low-voltage
wiring
DZ 1 DZ 1DZ 1 DZ 1
DZ 2 DZ 2
1 required for each fixture control
© 06/2017 Lutron Electronics Co., Inc.
I
P/N 368-4605 REV B