by
Egress Corridor | New Construction
ASHRAE 90.1-2013
Control Functionality
Occupant Enters:
All lights automatically turn on to maximum light level. Maximum light level is set to 80%.
When Occupied:
Manual: Occupant uses wall switch to turn on, adjust, or dim all lights to low end. Manual control cannot
fully shut off the lights. Minimum light level is set to 10%.
Occupant Exits:
All lights automatically go to minimum light level 15 minutes after all occupants exit.
Emergency Mode:
Lighting connected to emergency power turns on to full output.
Symbol Model Number Description Qty
RMJS-8T-DV-B PowPak dimming module with 0-10 V 1
LRF2-OHLB-P-WH
Radio Powr Savr wireless hallway
occupancy sensor
1
PJ2-3BRL-GWH-L01 Pico wireless 3-button with raise/lower control 2
PICO-WBX-ADAPT Pico wallbox adapter 2
Code Notes: Verify that the egress fixtures go to full output upon loss of control signal. For projects that require UL 924 compliance, provide an
automatic load control relay (ALCR) per load controller connected to emergency fixtures. Add a daylight sensor for corridors with daylight zones.
Want to add a Vive wireless hub for more features? Go to lutron.com/vive for complete compatibility and design details.
This solution requires 0-10 V enabled ballasts and drivers by others.
Clear Connect
RF Communication
Line-voltage
wiring
Low-voltage
wiring
To emergency power
© 06/2017 Lutron Electronics Co., Inc.
I
P/N 368-4611 REV B
Insert Model Number
Insert Description
Fixture
Insert
Qty