by
Classroom | New Construction
Title 24-2016
Control Functionality
Occupant Enters:
All lights automatically turn on to 50% light level. Occupant turns on lights to maximum level manually.
Maximum light level is set to 80%.
When Occupied:
Automatic: Overhead lights dim/brighten based on daylight availability. There are two perimeter daylight zones.
Manual: Occupant uses wall dimmers to set desired light levels for both general and white-board lights.
Occupant Exits:
All lights automatically turn off 15 minutes after all occupants exit.
System Events:
Demand Response: All lights automatically dim 20% during demand events.
Symbol Model Number Description Qty
RMJS-8T-DV-B PowPak dimming module with 0 –10 V 4
LRF2-DCRB-WH Radio Powr Savr wireless daylight sensor 1
LRF2-OKLB-P-WH
Radio Powr Savr wireless corner-mount
occupancy sensor
1
PJ2-3BRL-GWH-L01 Pico wireless 3-button with raise/lower control 2
PICO-WBX-ADAPT Pico wallbox adapter 2
HJS-1-FM Vive wireless Hub Shared
Code Notes: For non-daylit classrooms, all general lighting can be connected to a single 0 –10 V dimming module.
Go to lutron.com/vive for complete compatibility and design details.
This solution requires 0 –10 V enabled ballasts and drivers by others.
Line-voltage
wiring
Clear Connect
RF Communication
DZ 1 & DZ 2 =
Daylight Zones
Low-voltage
wiring
DZ 1 DZ 1 DZ 1
2 2 2
2 2 2
2 2 2
1
1
1
DZ 2 DZ 2 DZ 2
21
© 06/2017 Lutron Electronics Co., Inc.
I
P/N 368-4593 REV C
Insert Model Number
Insert Description
Fixture
Insert
Qty