by
Egress Stairwell | New Construction
Title 24-2016
Symbol Model Number Description Qty
FCJS-010 Wireless Fixture Control with 0-10 V
2
(per floor)
LRF2-OKLB-P-WH
Radio Powr Savr wireless corner-mount
occupancy sensor
1
(per floor)
HJS-1-FM Vive wireless Hub Shared
Control Functionality
Occupant Enters:
All lights automatically turn on to maximum light level. Maximum light level is set to 80%.
Occupant Exits:
All lights dim to minimum light level 15 minutes after all occupants exit. Minimum light level is set to 10%.
Emergency Mode:
Lighting connected to emergency power turns on to full output.
System Events:
Demand Response: All lights automatically dim 20% during demand response event. Demand response
cannot shut off the lights.
A section of the floor is shown
A floor cross-section is shown. One fixture per landing is suggested.
Line-voltage
wiring
Clear Connect
RF Communication
Low-voltage
wiring
To
emergency
power
To
emergency
power
Code Notes: Verify that the egress fixtures go to full output upon loss of control signal. For projects that require UL 924 compliance, provide an
automatic load control relay (ALCR) per load controller connected to emergency fixtures. Add a daylight sensor for stairwells with daylight zones.
This solution requires 0-10 V enabled ballasts and drivers by others. Go to lutron.com/vive for the latest compatibility details.
© 06/2017 Lutron Electronics Co., Inc.
I
P/N 368-4599 REV B
Insert Model Number
Insert Description
Fixture
Insert
Qty