´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
12 11 10 98765432112 11 10 987654321
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
The LUT-ELI-3PH is a device that works with Lutron
lighting controls to provide an emergency lighting
solution. The device is capable of sensing normal
(non-essential) line voltage power and accepting an
output from a fire alarm control panel (FACP). Upon loss
of normal power or receiving a signal from the FACP, the
LUT-ELI-3PH will send a signal to the compatible Lutron
control(s) to which it is connected. This signal will cause
the controls to enter the emergency lighting mode and
any lights controlled will go to the emergency light level
setting.
Features
Compatible Lutron controls
GP, LP, LCP, XP, XPS, CCP, CXP, and HS
Energi Savr Node units
GRAFIK Eye QS units
Quantum lighting management hubs with EcoSystem
bus supplies
ULR 924 & CSA C22.2 No. 141-02 listed as “Emergency
Lighting and Power Equipment”
Requires a 24 V- power feed from a source on
normal / emergency (essential) power for unit to operate.
Status light indicates the phase status. Status light “ON”
is normal mode, “OFF” is emergency mode.
A test button is provided to perform a functional test of
the system by simulating an emergency situation.
Accepts a maintained dry contact closure from an FACP
to actuate the emergency mode.
Senses line voltage from 100–347 V~.
LUT-ELI-3PH Emergency Lighting Interface
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
LUT-ELI-3PH
Power Accessories
369299e 1 06.28.19
1
Specifications
Regulatory Approvals
Complies with requirements for use in other spaces
used for environmental air (plenums) per
NECR 2014 300.22(C)(3)
Meets the Canadian National Building Code plenum
requirements for a concealed space used as a
plenum within a floor or roof assembly
cULus Listed - USA & Canada
NOM Certified (LUT-ELI-3PH-S only) - Mexico
Lutron Quality Systems registered to
ISO 9001.2000
Power
Sense voltage input to the LUT-ELI-3PH unit must
be from the Normal (Non-Essential) power source.
Sense voltage range: 100–347 V~ 50/60 Hz
30 mA, 1-Phase, 3-Phase, or split phase.
Proper short-circuit and over-current protection
must be provided at the distribution panel.
A 20 A maximum circuit breaker may be used for
the installation.
Environment
Ambient Temperature Operating Range:
32 °F–104 °F (0 °C–40 °C).
Relative humidity: less than 90% non-condensing.
For indoor use only.
Inputs
2 inputs for an FACP. A normally open or normally
closed dry contact input on the FACP inputs will
activate the emergency mode.
Status Light
Status light indicates the phase status. Status light
“ON” is normal mode, “OFF” is emergency mode.
Test Button
A test button is provided to perform a functional test
of the system by simulating an emergency situation.
System Communications and Capacity
May be added to an existing Lutron system.
One LUT-ELI-3PH unit may be used with up to
32 circuit selectors, specification-grade panel
interfaces (SPI) or LCD controllers, Energi Savr
Node units, GRAFIK Eye QS units, or Quantum bus
supplies mixed in any combination.
• There can be up to 4 Quantum bus supplies in a
Quantum hub. Only 1 Quantum bus supply per hub
needs to be connected per LUT-ELI-3PH unit. There
can be up to 32 Quantum bus supplies connected
to one LUT-ELI-3PH unit.
Mounting
The interface mounts to a standard 4 x 4 in
(102 x 102 mm) junction box.
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
LUT-ELI-3PH
Power Accessories
369299e 2 06.28.19
2
Dimensions and Mounting
All dimensions shown as in (mm)
´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
12 11 10 98765432112 11 10 987654321
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
5.00
(127)
7.75
(197)
2.50
(64)
4 x 4 in (102 x 102 mm)
Junction Box
For line voltage
wiring only
Mounting Example Side View (Cross-Section)
Insert
NECR Class 2/PELV
wires through
knockouts
Front View Side View
WALL
LUT-ELI-3PH
UNIT
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
LUT-ELI-3PH
Power Accessories
369299e 3 06.28.19
3
Line Voltage Wiring Examples:
3-Phase Diagram
Split Phase Diagram
´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
12 11 10 987654321
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
Normal Power
Ground
Neutral
Phase C
Phase B
Phase A
Red Red Red White Green
Guide to Power Source Wiring
Wire Connects to
Red Phase A
Red Phase B
Red Phase C
White Neutral
Green Ground
´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
12 11 10 987654321
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
Normal Power
Ground
Neutral
Phase B
Phase A
Red Red Red White Green
Guide to Power Source Wiring
Wire Connects to
Red Phase A
Red Phase A
Red Phase B
White Neutral
Green Ground
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
LUT-ELI-3PH
Power Accessories
369299e 4 06.28.19
4
Line Voltage Wiring Examples: (continued)
Single Phase Diagram
´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
12 11 10 987654321
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
Normal Power
Ground
Neutral
Line / Hot
Red Red Red White Green
Guide to Power Source Wiring
Wire Connects to
Red * Line / Hot
White Neutral
Green Ground
* Note: All 3 Red wires must be tied together
to Line / Hot of distribution panel for single
phase application.
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
LUT-ELI-3PH
Power Accessories
369299e 5 06.28.19
5
´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
DataAOKPower Data B OK
1234D5
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
Link
A
1
2
3,4
5
1
2
3,4
DataAOKPower Data B OK
1234D5
CD
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
1234D5
S
ELECT
C
IRCUIT
S
ELECT
C
IRCUIT
Link
B
Link
A
Link
B
1234D5
CD
12 11 10 98765432112 11 10 987654321
Panel 1 Panel 2
Shield/Drain
Sense:
(1) 18 AWG
(1.0 mm
2
)
5: Sense line
To lighting controls
IEC PELV / NECR Class 2 Wiring Example:
GP, XP, LP, CCP, and CXP Panels
One LUT-ELI-3PH unit may be connected in parallel with up to 32 circuit selectors.
A LUT-ELI-3PH unit may be placed anywhere on the power panel link.
The switch position SW6 on the circuit selector / controller must be in the right-most position, “Essential” on all
Emergency Panels.
The LUT-ELI-3PH unit 24 V- input must always be connected to at least one of the Emergency Panels.
Data Link:
(1) shielded,
twisted pair
18 AWG
(1.0 mm
2
)
3: MUX
4: MUX
Control Wiring:
(2) 12 AWG
(2.5 mm
2
)
1: Common
2: 24 V-
Guide to Wiring
LUT-ELI Circuit Selector
Pin 12 Pin 5
Pin 11 Pin D
Pin 10 Pin 4
Pin 9 Pin 3
Pin 8 Pin 2
Pin 7 Pin 1
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
LUT-ELI-3PH
Power Accessories
369299e 6 06.28.19
6
IEC PELV / NECR Class 2 Wiring Example:
HomeWorks QS Panels with a Specification Grade Interface (SPI)
One LUT-ELI-3PH unit may be connected in parallel with up to 32 SPIs across two panel links.
A LUT-ELI-3PH unit may be placed anywhere on the power panel link.
The switch position SW6 on the SPI must be in the right-most position, “Essential” on all Emergency Panels.
The LUT-ELI-3PH unit 24 V- input must always be connected to at least one of the Emergency Panels.
´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
12 11 10 98765432112 11 10 987654321
Pin 12
Pin 8
Pin 7
Guide to Wiring
LUT-ELI SPI
Pin 12 Pin 5
Pin 8 Pin 2
Pin 7 Pin 1
´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
12 11 10 98765432112 11 10 987654321
Move Right
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
LUT-ELI-3PH
Power Accessories
369299e 7 06.28.19
7
IEC PELV / NECR Class 2 Wiring Example:
LCP128 and Softswitch128 (XPS) Panels
´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
1
2
3,4
5
1
2
3,4
1
234
D
5
1
234
1
234
D
5
1
234
12 11 10 98765432112 11 10 987654321
Panel 1
Panel 2
Shield/Drain
To lighting controls
or processors
Sense:
(1) 18 AWG
(1.0 mm
2
)
5: Sense line
Data Link:
(1) shielded,
twisted pair
18 AWG
(1.0 mm
2
)
3: MUX
4: MUX
Control Wiring:
(2) 12 AWG
(2.5 mm
2
)
1: Common
2: 24 V-
One LUT-ELI-3PH unit may be connected in parallel with up to 32 LCP / XPS controllers.
A LUT-ELI-3PH unit may be placed anywhere on the power panel link.
The switch position SW6 on the controller must be in the right-most position, ‘“Essential” on all Emergency
Panels.
The LUT-ELI-3PH unit 24 V- input must always be connected to at least one of the Emergency Panels.
Guide to Wiring
LUT-ELI LCD Controller
Pin 12 Pin 5
Pin 11 Pin D
Pin 10 Pin 4
Pin 9 Pin 3
Pin 8 Pin 2
Pin 7 Pin 1
´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
1
2
3,4
5
1
2
3,4
1
234
D
5
1
234
1
234
D
5
1
234
12 11 10 98765432112 11 10 987654321
Move Right
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
LUT-ELI-3PH
Power Accessories
369299e 8 06.28.19
8
´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
12 11 10 98765432112 11 10 987654321
Energi Savr Node Units
Using a LUT-ELI-3PH unit with an Energi Savr Node unit ensures that the system is compliant with ULR 924. Follow
the wiring diagram in the LUT-ELI-3PH for mains wiring. Use the diagram below to complete the installation. There
can be up to 32 Energi Savr Node units connected to one LUT-ELI-3PH unit.
Model QSN-4T16-S is shown below. Check the documentation of your particular model for proper terminal connections.
Wiring to the Energi Savr Node Unit
Wiring Summary:
Wire the power pack red wire (+24 V) to the LUT-ELI-3PH unit terminal 8 (V+).
Wire the power pack black wire (Common) to the LUT-ELI-3PH unit terminal 7 (Circuit Common) and to
Energi Savr Node “Com” terminal of the Emergency Contact Closure Input.
Wire the signal wire from the LUT-ELI-3PH unit (terminal 1) to the Energi Savr Node “Emerg” terminal of the
Emergency Contact Closure Input.
When normal power loss is detected, the LUT-ELI-3PH unit sends all programmed zones to emergency light levels
(Default is typically 100%).
When normal power loss is restored, the LUT-ELI-3PH unit causes all programmed zones to return to previous light levels.
Com – Common
Emerg – Emergency
From Normal /
Emergency supply
100–347 V~
Normal
supply
Common
Line /
Hot
Neutral
24 V-
Power
Pack
1
1
PP-DV or PP-347
Guide to Wiring
LUT-ELI Energi Savr Node
Pin 8 24 V-
Pin 7 Com
Pin 1 Emerg
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
LUT-ELI-3PH
Power Accessories
369299e 9 06.28.19
9
´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
E2
E1
1
2
3
4
5
6
7
8
E2
E1
EM C
12 11 10 98765432112 11 10 987654321
Wiring to Quantum Bus Supply
Line /
Hot
Neutral
From Normal /
Emergency supply
Quantum Systems
Using a LUT-ELI-3PH unit with a Quantum bus supply ensures that the system is compliant with ULR 924.
Follow the wiring diagram in the LUT-ELI-3PH unit for mains wiring. Use the diagram below to complete the
installation. Only 1 bus supply per hub needs to be connected per LUT-ELI-3PH unit. There can be up to
32 Quantum bus supplies connected to one LUT-ELI-3PH unit.
Wiring Summary:
Wire the power pack red wire (+24 V) to the LUT-ELI-3PH unit terminal 8 (+VFW).
Wire the power pack black wire (Common) to the LUT-ELI-3PH unit terminal 7 (Common) and to the Quantum bus
supply terminal 5 (Common).
Wire the signal wire from the LUT-ELI-3PH unit (terminal 1) to the Quantum bus supply terminal 6
(CCI-Emergency).
Note: When normal power loss is detected, the LUT-ELI-3PH unit sends a signal to the bus supplies which send
the programmed lights to emergency light levels.
Common
24 V-
100–347 V~
Normal
supply
From Normal /
Emergency Supply
Common
Emergency
signal
Power
Pack
1
1
PP-DV or PP-347
Guide to Wiring
LUT-ELI Bus Supply
Pin 8 24 V-
Pin 7 Com
Pin 1 Emerg
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
LUT-ELI-3PH
Power Accessories
369299e 10 06.28.19
10
´FACP´ N/O
CONTACTS
TAGE WIRING
GND
SENSE
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
12 987654321
C
TAGE WIRING
EN
N
T
E
LED
RADI
T
H
1
2
876543
98765432
1
´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
CLASS 2 LOW VOLTAGE WIRING
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED3
RADIOTOUCH
12 11 10 9 8 7 6 5 4 3 2 1
Installing a LUT-ELI-3PH Unit with a GRAFIK Eye QS Unit
Provide proper short-circuit and overcurrent protection at the distribution panel. Maximum circuit breaker
installation of 20 A.
When normal power loss is detected at the LUT-ELI-3PH unit, all zones in the GRAFIK Eye QS units will go to their
emergency states.
The GRAFIK Eye QS unit MUST be powered from a normal / emergency power feed.
Note: For a 1-phase 2-wire application, connect phase A, B, and C wires on
LUT-ELI-3PH together for phase sensing.
Wiring to a GRAFIK Eye QS Control Unit
Signal
+24 V-
Common
(3) 18 AWG
(0.75 mm²)
GRAFIK Eye QS unit (back view)
Normal / Emergency
20 A 120 V~
1-Phase 2-Wire
power feed
(3) 12 AWG (2.5 mm²)
120–127 V~
or
220–240 V~
distribution panel
100–347 V~
Normal supply
CCI SIG
24 V
CCI Com
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
LUT-ELI-3PH
Power Accessories
369299e 11 06.28.19
11
´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
12 11 10 98765432112 11 10 987654321
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
´FACP´ N/C
CONTACTS
´FACP´ N/O
CONTACTS
12 11 10 98765432112 11 10 987654321
CLASS 2 LOW VOLTAGE WIRING
GND
SENSE
DRAIN
MUX
MUX
+24VFW
COMMON
NOT USED
LED1
LED3
LED2
RADIOTOUCH
PHASE
FACF
S1
TEST
LUT-ELI-3PH Unit
Fire Alarm Control Panel
(provided by others)
Common
Normally
open
LUT-ELI-3PH Unit
Fire Alarm Control Panel
(provided by others)
Common
Normally
closed
Important
Use only with normally open (terminals 3
and 4) or normally closed (terminals 5 and 6)
dry contact closure. When the proper contact
state is triggered, it must be maintained for the
LUT-ELI-3PH unit to go into Emergency Mode.
Once the contact is released, the LUT-ELI-3PH
unit will return the GRAFIK Systems GP, LP,
XP panel(s), XPS, LCP, RadioTouch controller,
EcoSystem Bus Supply, GRAFIK Eye QS unit,
or Quantum Bus Supply back to normal
operation mode.
The LUT-ELI-3PH unit will have a factory
installed jumper to provide the normally closed
input signal for the supervisory circuit when a
normally closed FACP input is not provided.
Consult your Fire Alarm Control Panel’s
instruction manual before connecting to the
LUT-ELI-3PH unit.
Notice: Do not connect any voltage source to
the FACP inputs on the LUT-ELI-3PH unit. If
voltage is provided by the FACP and connected
to the LUT-ELI-3PH unit, it can damage the
LUT-ELI-3PH unit.
IEC PELV / NECR Class 2 Wiring Example:
Fire Alarm Control Panel (FACP)
Normally Open FACP Input
Supervisory Circuit (Normally Closed FACP Input)
To 24 V- power
To 24 V- power
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
LUT-ELI-3PH
Power Accessories
369299e 12 06.28.19
)Lutron, Lutron, HomeWorks, Energi Savr Node, GRAFIK
Eye, Quantum, EcoSystem, LCP128, Softswitch128, and
RadioTouch are trademarks or registered trademarks of
Lutron Electronics Co., Inc. in the US and/or other countries.
12