SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369642c 1 12.11.18
LCP128T Spec Grade Dimming System
System Overview
LCP128T is a combination dimming and switching
system that provides a complete lighting control
solution. The system consists of panels and control
station devices. An integrated astronomical time clock
provides system automation capability.
System Features
•32programmablelightingscenesandoff.
•Connectupto8powerpanels(specgradeand
standard) for up to 128 dimmed/switched outputs.
•Connectupto32wallstationsorcontroldevicesfor
multiple points of control.
•EntiresystemisprogrammedusingtheLCD
controller mounted in the panel.
•Astronomicaltimeclockprovidesautomated
selection of lighting scenes.
•Worksdirectlywithincandescent,magneticlow-
voltage,electroniclow-voltage,neon,LutronR
and switched load types.
•WorkswithDSI,DALIR,and0-10V- dimming
ballastsusingoptional10Vmodulesinthepanel.
•WorkswithLutronREco-10RandHi-lumeR
FluorescentDimmingBallasts.
•Feed-throughorbranchcircuitbreakerpanelsare
available.
•Panelispre-wiredandpre-tested.
•Spec-gradepanelmaybesurfacemountedonly.
LCP128TSpec-GradePanel
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369642c 2 12.11.18
LCP128T Controller
Overview
Lighting control may be automated by using the
astronomical time clock integrated into the LCP128T
controller.ThecontrollerhasanLCDscreenforeasy
programming.
Features
•LCDinterfacesimpliesscene,timeclockevent,and
control station programming.
•Timeclockeventsautomaticallyrecallpresetsat
aspecictimeofdayoratanoffsetfromsunrise
or sunset.
•Upto500totaleventsareprogrammablewithin
7dailyschedulesand40holidayschedules.
•Holidayschedulesareprogrammabletorunonceor
repeatupto90daysinarow.
•Twointegratedcontactclosureinputsprovidean
interface with occupancy sensors or building
management systems.
•Selectsystemlocationfromabuilt-incitydatabase
or by entering latitude and longitude.
•Timeclockisbatterybacked;timeandevent
settings are remembered even after power failures.
•Programmableash-warnfeature.
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369642c 3 12.11.18
Specifications
Standards
•ULRListed(Reference:ULFileE42071)
•CSACertied
•SeismicCertiedmodelsavailable(TestMethod
AC156.ReferenceOSHPDPreapprovalOSP-0215-10).
Contact Lutron for details.
•NOMcertiedmodelsavailable.
Power
•Inputpower:100-127V~and277V~,50/60Hz,
phase-to-neutral.
•BranchCircuitCapacity:
–120-127V~:upto2000W/VA
–277V~:4500W/VA
•Branchcircuitbreakers(ifapplicable):UL-rated
thermal magnetic.
AICrating:
–100127V~:10,000A
–277V~: 14,000A
NOTE:Seepage4forSCCRratings.
•Lightningstrikeprotection:meetsANSI/IEEE
standard62.41-1980.Canwithstandsurgesofupto
6000V~andupto3000A.
•10-yearpowerfailurememory:automaticallyrestores
lighting to scene selected prior to power interruption.
•RTISSltercircuittechnologycompensatesfor
incominglinevoltagevariations:novisibleickerwith
+
/-2%changeinRMSvoltage/cycleand
+
/-2%Hzchangeinfrequency/second.
Lighting Sources/Load Types
Operatesthesesourceswithasmoothcontinuous
SquareLawdimmingcurveoronafullconduction
non-dimbasis:
•Incandescent(tungsten)/halogen
•LEDlamps(withinternalorexternaldrivers)specied
bythemanufacturertoworkwithforward-phase
dimming controls *
•Magneticlow-voltagetransformer**
•Neon
•HID(full-conductionnon-dimbasisonly)
•Optionalmodulesallowforcontrolof0–10V-,DSI,
andPWMloadtypes
•LEDdriversspeciedbythemanufacturertowork
withforward-phasedimmingcontrols
•Electroniclow-voltagetransformersspeciedbythe
manufacturertoworkwithforward-phasedimming
controls
Physical Design
•Enclosure:NEMA-Type1,IP-20protection(Type2
availableuponrequest);16U.S.gaugesteel.
Indoorsonly.
•Panelweight:
–Spec-grade:115to175lb(52to79kg)
•SeismicCertificationLimits:S
DS
=2.5g,z/h=1.0,
I
P
=1.5.ContactLutronfordetails.
Mounting
•Spec-gradepanelssurfacemountonly;allowspace
for ventilating.
Environment
•32to104°F(0to40°C).
•Relativehumiditylessthan90%non-condensing.
Heat Dissipation
•Panelscoolbyconvection.Nofans.
Wiring
•Internal:PrewiredbyLutron.
•Systemcommunications:IECPELVNECR Class2
wiring connects dimming panels to other components.
•Line(mains)voltage:Feedandloadwiringonly.No
otherwiringorassemblyrequired.
LCP128T Controller
•ConguresentireLCP128T system.
•Twolow-voltage(15–24V-)contactclosureinputs,
momentaryormaintained,pull-uporpull-down.
•Emergencysensing.
•Astronomicaltimeclock.
•Digitalcontrollink.
•MountedinsideLCP128T panel.
*LutroncannotguaranteecompatibilitywithuntestedLEDdrivers.RefertotheLEDProductSelectiontoolatwww.lutron.com/ledtool
foralistofcompatibleproducts;seelistforGPpanels.
**SeeAppNote#559atwww.lutron.comformoreinformationaboutusingMR16LEDlampswithMLVtransformers;seelistforGP(Harrier)cards.
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369642c 4 12.11.18
Specifications (Continued)
Filter Chokes (spec-grade panel)
•Loadcurrentrisetimeismeasuredata90˚
conduction angle.
•1090%ofloadcurrentwaveform:
–350µsrisetimeat50%dimmercapacity.
–400µsrisetimeat100%dimmercapacity.
•0100%ofloadcurrentwaveform:
–525µsrisetimeat50%dimmercapacity.
–600µsrisetimeat100%dimmercapacity.
•Atnopointinthewaveformcantherateofcurrent
changeexceed300mAperµs.
•ConsultLutronforhigherrisetimeoptions.
Astronomical Time Clock
•Capableofupto500events.
•7dailyschedulesand40holidayschedules
are available.
•25eventsperday.
•Holidayeventsareprogrammableoneyear
in advance.
•Holidayschedulesareprogrammabletorunforup
to90days.
•ATClocationprogrammablebybuilt-incitydatabase
orbyenteringlatitudeandlongitude,plusasunrise
or sunset offset to adjust for local geography.
Dimming Cards
•Panelcurrentratingsarelistedforcontinuous
operation.ULRListedspecicallyforeachlightsource.
•Arcless-relayairgap-offswitches(oneperloadcircuit)
ensure open load circuits when off function selected.
Eliminatearcingatmechanicalcontactswhenloads
are switched
Control Station Devices
•OnetosevenbuttonseeTouchR wallstations.
•Buttonsareprogrammabletoselectscenesor
patterns,togglecircuits,oractivatedelay-to-off.
•ButtonsareprogrammedattheLCP128T controller.
•Keyswitchcontrolisalsoavailable.
•Controlsarepoweredbyandcommunicateviathe
LCP128Tlow-voltagecommunicationlink.
•OMX-CCO-8integratesthirdpartymotorized
windowtreatmentsorA/Vequipment.
•OMX-AVinterfaceswithoccupantorphotosensors.
•OMX-RS232interfacestheLCP128TsystemtoaPC,
touchscreen,orbuildingmanagementsystem.
•ODMX-512interfacestotheatricalstageboards.
•Seespecicproductspecicationsheetsfor
further details.
LCP Spec Grade Panels Short Circuit Current Ratings (other ratings available)
Panel Type V~ Standard SCCR Rating
LCPSpecGradeMainLug
(standardandlargesize)
120,277 25,000A
LCPSpecGradeMainBreaker
(standardsize)
120 10,000A
LCPSpecGradeMainBreaker
(standardsize)
277 18,000A
LCPSpecGradeMainBreaker
(largesize)
120 25,000A
LCPSpecGradeMainBreaker
(largesize)
277 25,000A
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369642c 5 12.11.18
seeTouch ® Wallstations
Description
•EachseeTouchRwallstationfeaturesengraved,backlit
buttonsallowingquickandeasyrecalloflighting
presets,eveninlowlightconditions.
•Buttonfunctionalityisfullyprogrammable.
Specifications
•Low-voltagetypeIECPELV/NECRClass2Operating
voltage:24V-.
•MeetsIEC801-2.Testedtowithstand15kV
electrostatic discharge without damage or
memory loss.
•Faceplatesnapsonwithnovisiblemeansof
attachment.
•Terminalsacceptuptotwo18AWG(1.0mm
2
)
wires typical.
•Environment:32˚°Fto104°F(0˚°Cto40°C).
Relativehumiditylessthan90%non-condensing.
seeTouchR Models
•Modelsavailablewithonetosevenbuttons,with
or without raise/lower.
•UseSOseriesmodelnumbers.
•Availablewithallstandardcolorsandengraving.
•Availablewithbuilt-incontactclosureinputsor
with optional occupant sensor inputs.
Button Programming
•Eachbuttonmaybeprogrammedforscene
selection,toggle,delay-to-off,raise,orlower
functionality.
•Buttonprogrammingcanbeusedtoprovide
specializedmanualcontrolofmultipleareas.
Button Engraving
Custom engraving is available using button/
faceplate replacement kits.
Toorder,contactLutronRCustomerServiceat
1.844.LUTRON1.
seeTouchRWallstation
(SO-4SN-WH-EGN)
Off
Typicalwallboxdimensions:3.74in(95mm)Hx
2.17in(55mm)Wx2.75in(70mm)D.
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369642c 6 12.11.18
Feed-Through Model Numbers
Example
LCP12-120FTML
NumberofCircuits
in Panel
Voltage
Feed-Through
Type
Branch Circuit Breaker Model Numbers
Example
LCP24-1204ML-20
NumberofCircuits
in Panel
Voltage
Feed
Type
Feed Branch
Circuit
Rating
Number of Circuits in Panel
Indicatesnumberofswitchingcircuitsinthepanel:
8,12,16,20,or24
Voltage
120for120V~
277for277V~
Load Circuit Rating
16Apercircuit
Frequency - All Model Numbers and Voltages
50/60Hz
Output Voltages
120V~or277V~
Feed Input Ratings
4for3phase4wire 120/208V~or277/480V~
3for1phase3wire120/240V~
2for1phase2wire120V~or277V~
Feed Type
M or ML for main lugs
DTML for dual tap main lugs
Mxxxformainbreaker(xxx=breakersizeinamps)
Branch Circuit Rating
20for20Abranchcircuitbreakers
20Abranchcircuitbreakershavea16A
continuous load rating
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369642c 7 12.11.18
Ratings: LCP8-24 Spec-Grade
Onlystandardpanelslisted;consultLutronforfurtheroptions
120 127 V
Power
Panel Branch Ratings
Number of
Circuits
Feed Type Panel Feed Maximum
Feed
Circuit
Breakers
1
Maximum Dimmed
Hot Load
2
LCP8 1Ø,2W MainLugsOnly 175A 20A 2000W/VA
1Ø,3W MainLugsOnly
DualTapMainLugs
80AMainBreaker
175A
225A
80A
20A
20A
20A
2000W/VA
2000W/VA
2000W/VA
3Ø,4W MainLugsOnly
DualTapMainLugs
60AMainBreaker
175A
225A
60A
20A
20A
20A
2000W/VA
2000W/VA
2000W/VA
LCP12 1Ø,3W MainLugsOnly
DualTapMainLugs
175A
225A
20A
20A
2000W/VA
2000W/VA
3Ø,4W MainLugsOnly
DualTapMainLugs
80AMainBreaker
175A
225A
80A
20A
20A
20A
2000W/VA
2000W/VA
2000W/VA
LCP16 1Ø,3W MainLugsOnly
DualTapMainLugs
175AMainBreaker
175A
225A
175A
20A
20A
20A
2000W/VA
2000W/VA
2000W/VA
3Ø,4W MainLugsOnly
DualTapMainLugs
125AMainBreaker
175A
225A
125A
20A
20A
20A
2000W/VA
2000W/VA
2000W/VA
LCP20 1Ø,3W MainLugsOnly 225A 20A 2000W/VA
3Ø,4W MainLugsOnly
DualTapMainLugs
150AMainBreaker
175A
225A
150A
20A
20A
20A
2000W/VA
2000W/VA
2000W/VA
LCP24 1Ø,3W MainLugsOnly 225A 20A 2000W/VA
3Ø,4W MainLugsOnly
DualTapMainLugs
150AMainBreaker
175A
225A
175A
20A
20A
20A
2000W/VA
2000W/VA
2000W/VA
1
20/16A,15/12Acontinuous load rating.
2
Measuredcurrentwillnotexceedcontinuousloadratingduetovoltagedropinthedimmer.
7
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369642c 8 12.11.18
Ratings: LCP8-24 Spec-Grade
Onlystandardpanelslisted;consultLutronforfurtheroptions
277 V Power
Panel Branch Ratings
Number of
Circuits
Feed Type Panel Feed Maximum
Feed
Circuit
Breakers
1
Maximum Dimmed
Hot Load
2
LCP8 1Ø,2W MainLugsOnly 175A 20A 4500W/VA
3Ø,4W MainLugsOnly
DualTapMainLugs
60AMainBreaker
175A
225A
60A
20A
20A
20A
4500W/VA
4500W/VA
4500W/VA
LCP12 3Ø,4W MainLugsOnly
DualTapMainLugs
80AMainBreaker
175A
225A
80A
20A
20A
20A
4500W/VA
4500W/VA
4500W/VA
LCP16 ,4W MainLugsOnly
DualTapMainLugs
125AMainBreaker
175A
225A
125A
20A
20A
20A
4500W/VA
4500W/VA
4500W/VA
1
20/16A,15/12Acontinuous load rating.
2
Measuredcurrentwillnotexceedcontinuousloadratingduetovoltagedropinthedimmer.
8
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369642c 9 12.11.18
LCP8-24 Spec-Grade Panel Dimensions
Dimensionsshownas:in(mm)
Suggestedfeedwiringentry;
punch cover
Suggestedfeedwiringentry;
punch cover
Removabletopcoveris
shippedtheboxwiththepanel.
28(711)
12
(304)
12
(304)
2(50)
13
(330)
33
(838)
37
(940)
35
(889)
4(100)
2(50)
Left Side
Top View
Front View Right Side
Bottom View
2(50)
Requiredcontrol
wiring entry
Keyholeacceptsamaximum5/16in(8mm)mountingbolt(1/4in[M8]recommended).
IECPELV/NECRClass2entryknockoutis7/8in(22mm)diameter.
Notice: Thisequipmentisair-cooled.Ventsmustnotbeblockedorthewarrantywillbevoided.
9
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369642c 10 12.11.18
Notes
•ForIndoorUseOnly.NEMA,Type1enclosure,IP20.
•Relativehumiditymustbe<90%non-condensing.
•Panelgeneratesheat.Mountwhereambient
temperatureis32to104ºF(0to40ºC).
•Reinforcewallstructureforpanelweightand
local codes.
•Mountwithin7ºoftruevertical.
•Panelclearancesare12in(305mm)aboveand
belowand0intoeachside.Allowroomfor
IECPELV/NECR Class2 clearance.
Panel Max. BTUs/Hour
(Kcal/Hour)
Weight without
Packaging
lb (kg)
LCP8 1365(343.98) 115(52)
LCP12 2045(515.34) 120(54)
LCP16 2725(686.70) 145(66)
LCP20 3405(858.06) 160(73)
LCP24 4085(1029.42) 175(80)
Panel Mounting: LCP8-24 Spec-Grade
Front View Side View
Feed
Wiring
(top
entry)
Load
Wiring
(top
entry)
Wiringraceway
IECPELV/
NECR Class2
wiring to
controls
12 in
(305mm)
minimum
12in(305mm)
minimum
clearance
Airow
Wall
Notice:Dimmingpanelswillhumslightlyandinternalrelayswillclickwhileinoperation.Mountwhereaudible
noise is acceptable.
Notice:Mountpanelsoline(mains)voltagewiringwillbeatleast6ft(1.8m)fromsoundorelectronicequipment
and its wiring.
Notice:Thisequipmentisair-cooled.Ventsmustnotbeblockedoryouwillvoidthewarranty.
10
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369642c 11 12.11.18
Front View Side View
Feed
Wiring
Load
Wiring
Wiringraceway
IECPELV/
NECR
Class2
wiring
IECPELV/NECR
Class2 wiring
Panel Mounting: LCP8-24 Spec-Grade
Atleast8ft8in(265cm)betweenoorandsuspendedceilingisrequiredforthislayout.
6in(152mm)
minimum*
3ft45 in
(103cm)to
mounting
holes
6ft6in(195cm)
NECR breaker
height limit
7ft55 in
(228cm)to
mounting
holes
8 ft 8 in
(265cm)
minimum
to ceiling
*6in(152mm)approvedforthislayoutonly.
WARNING: Shock Hazard. Couldcausedeathorseriousinjury.Toavoidtheriskofelectricshock,install
panels where they will not get wet.
Notice: Waterdamagespanels.
Airow
Airow
12 in
(305mm)
minimum
11
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369642c 12 12.11.18
Wiring Overview:
LCP8-24 Spec-Grade
Wire Sizes
•Power Feed Standard Main Lugs
14AWG(2.0mm
2
)to2/0AWG(70.0mm
2
)
Power Feed Dual Tap Main Lugs
6AWG(10.0mm
2
)to4/0AWG
(120mm
2
)
Neutral Feed:
6AWG(10.0mm
2
)to350MCM
(177.0mm
2
)
•DimmedHot/Live:
14AWG(2.0mm
2
)to10AWG
(4.0mm
2
)
•LoadNeutral:
14AWG(2.0mm
2
)to6AWG
(10.0mm
2
)
Wiring Tips
WiretheLCP8-24similartowiringa
lightingDistributionPanel:
•Runfeedandloadwiring.Nootherwiring
orassemblyrequired.
•Commonneutralsarenotpermitted.Run
separate neutrals for each load circuit.
TheLCP8-24canprovidetemporary
lighting.
•Wireallloads.
•Donotremovethebypassjumpersthat
protect the dimming modules.
•Usebranchcircuitbreakerstoswitchlights
on and off.
IECPELV/
NECR
Class2
wiring
Branch
circuit
breakers
Terminal
block
Bypass
jumpers-
Donot
remove
Typical Load Circuit
Load Neutral
Dimmed Hot/Live
Load
Neutral
Feed
Feed
Wiring
Power
Feed
(Hot/
Live)
12
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369642c 13 12.11.18
100 127 V~ and 277 V~ Load Circuits (LCP8-24 Spec-Grade)
Incandescent Load Types
DimmedHot(DH)mustbeusedfornon-dim
loads whether they will be dimmed or switched
Hi-lumeR FDB or Eco-10R fluorescent
dimming ballasts
TVM Load Types
ELV Load Types
DimmedHot(DH)mustbeusedfornon-dim
loads whether they will be dimmed or switched
Load Circuits with Emergency Battery Pack Wiring
SH
H
DH
SH
H
DH
+ 1
+ 2
L
N
+
SH
H
DH
SH
H
DH
SH
H
DH
Bypass
jumper
Load
terminals
Dimmableor
non-dimload
Neutralbus
Neutralbus
Ballast
Fluorescent lamp
Load
terminals
Bypass
jumper
Ballast
TVM
Load
terminals
Bypass
jumper
Neutralbus
Load
terminals
Bypass
jumper
Load
Neutralbus
LCPDimmingPanel
N
Neutral(White)
DimmedHot
(Orange)
SwitchedHot
(Black)
Load Terminals
Dimming
Ballast
Lamp2(Emerg.)
Lamp 1
Battery
Connector
Indicator
Light
Emergency
Ballast
Blue
Blue
Red
Red
Yellow
Red
Yellow/Black
Yellow
Blue/White
Blue
Black(277V~)
Orange(120V~)
White
ToNeutral
ToUnswitchedAC
}
13
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369642c 14 12.11.18
IEC PELV/NECR Class2 Wiring
The LCP128TsystemcommunicatestocontrolstationsusingaIECPELV/NECRClass2low-voltagelink.Control
stationsincludewallstations,contactclosureinputandoutputdevices,andRS232interfaces.
WiretheIECPELV/NECRClass2linkaccordingtothefollowingguidelines:
•Linkmustbedaisychained.
•Mustruninseparatetroughfromline(mains)voltage.
•Linkmustbelessthan2000ft(600m)long.
•MakewireconnectionsinsidethewallboxandLCP128T panel.
•InstallLinkTerminators(LT-1)atthestartandendoftheIECPELV/NECRClass2daisy-chainedlink.
•Theorderofcontrolsonthecontrollinkisnotimportant.
•UseLutronRGRX-CBL-46Lcableorequivalent.
LT-1
LT-1
Note:LinkTerminators(LT-1)are
requiredatthestartandendofthe
LCP128TIECPELV/NECR
Class2 link.
LCP128T Panels
2000ft(600m)maximum
ControlStations:
Wallstations,contactclosure
input,contactclosureoutput,
andRS232devices
Maximumtotallengthofthecontrollinkis2000ft(600m).
This distance is based on proper shielding of the twisted/
shieldedpair,properwiresize,andtheuseoflinkterminators
(LT-1)ateachendofthelink.Ifunapprovedcableorsmaller
wireisused,controllinklengthmustbede-ratedaccordingto
thefollowingchart:
Terminal 1 & 2 Wire Sizes Maximum Control Link Length
12AWG(4.0mm
2
) 2000ft(600m)
14AWG(2.5mm
2
) 1400ft(425m)
16AWG(1.5mm
2
) 900ft(275m)
18AWG(1.0mm
2
) 600ft(180m)
Notice: IfLinkTerminators(LT-1)arenotused
orimproperwiringtopologyisemployed,the
system will not communicate properly.
14
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369642c 15 12.11.18
1
2
3,4,D
1234D5
CCI1
COM
CCI2
COM
1234D5
1
2
3,4,D
5
CCI1
COM
CCI2
COM
IEC PELV/NECR Class2 Wiring
Panel to Panel and Panel to Control Stations
Wiring Notes:
•Useawireconnectortoattachone
18AWG(1.0mm
2
) wire for Common
(terminal1)andone18AWG(1.0mm
2
)
wirefor24V-(terminal2)fromthe
IECPELV/NECR Class2 link to the
control.Two12AWG(4.0mm
2
) wires
cannot both be terminated on the
controlstation.Maximumwirelength
fromlinktocontrolis8ft(2.5m).
•OnlyconnecttheDrain/Shieldwire
(barecopper)toterminal‘D’inLCP128T
panels.Maintaintheshieldthroughout
the link but do not allow it to touch
ground(earth)orwallstationcircuitry.
4
3
2
1
1
234
D
5
Control
station
terminal
Drain
wire
LCP128T Controller LCP128T Controller
To
LCP128T
control
stations
To additional
LCP128T
panels
ControlPower:(2)
12AWG(2.5mm
2
)
1:Common
2:24V
EmergencySense:
(1)18AWG(1.0mm
2
)
5:SenseLine
ControlData:
(1)twistedshieldedpair
22AWG(0.625mm
2
)
3:MUX
4:MUX
D:Drain/Shield