SPECIFICATION SUBMITTAL
369-564a 1 10.25.11
Control InterfacesLUT-DMX
GRAFIKR Systems
LUT-DMX
DMX 512 Control Interface
Description
•AllowsGRAFIKEyeRlightingcontrolstooperate
lightingandotherequipmentthatusestheDMX512
protocol,including:
-Strobes,fiberopticlighting,andLED-basedlamps.
-Foggermachines.
-Animatedcharactersandmotorizedfixtures.
•ConvertsGRAFIKRzoneintensitiesintoDMX512
channelsettings.EachzoneisassignedtoaDMX
512channel.
•WorkswithGRAFIKEyeR3000andGRAFIKEyeR
4000SeriesControlUnits,aswellasGRAFIK
5000T,GRAFIK6000R,andGRAFIK7000TSystems
(seeDIPswitches1and2).Interfacedoesnot
requireanaddress.
Example of Usage
ADMX512-controlledfiberopticfixtureissetup
sothat:
•Channel5controlscolorchannelordialsetting.
•Channel6controlsshutteropen/close.
TheControlUnit’sscenesaresetupsothat:
•Zone5intensity=desiredfiberopticcolor.
•Zone6intensity=desiredshutteropen/close.
WhenasceneisselectedattheControlUnit:
•DMX512Interfaceconvertsnewscene’szone
intensitiesintoDMX512channelsettings.
•Fiberopticsautomaticallychangecolorandshutter
open/close.
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-564a 2 10.25.11
Control InterfacesLUT-DMX
GRAFIKR Systems
Power
Low-voltageIECPELV/NECRClass2
OperatingVoltage:12/24V-
Zone/Channel Capacity
MaximumtotalnumberofGRAFIKEyeRlightingzonesand
DMX512channels:
•GRX-3000ControlUnits:Upto48non-continuous.
•GRX-4000ControlUnits:Upto64.
•GRAFIK5000TSystems:Upto128.
•GRAFIK6000RSystems:Upto512.
System Communications and Capacity
•Low-voltageIECPELV/NECRClass2wiringconnects
LUT-DMXInterfacetoothercomponents.
•OneLUT-DMXpersystem-noaddress.Doesnot
countasoneofthemaximumnumberofaddresses
(Wallstations,ControlInterfaces,orControlUnits)allowed
onaIECPELV/NECRClass2wiringlink.
DMX 512 Link
•ThreeterminalsforconnectingtheLUT-DMXtoDMX
512-controlledequipment.
•Eachterminalacceptsuptotwo#18AWG(1.0mm
2
)
wires.
•Linkmustbe1000feetorless.Linkmaybeextended
withtheLutronMUX-RPTRinterface.
•LinkmustbeginandendwithLinkTerminators.
Environment
•32-104°F(0-40°C).Relativehumiditylessthan
90%non-condensing.
Specifications
2
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-564a 3 10.25.11
Control InterfacesLUT-DMX
GRAFIKR Systems
Dimensions
Measurements are shown in inches (mm).
LED1LED2
INTERFACE CONTROL
SELV(CLASS2:USA)
LUT-DMX
12 3
12 3
DMXZONE
SELECT
EARTH
4
5
6
CONTROL LINK
EXT SW
COM
DMX512OUTPUT
LINK
COM
+V
MUX
MUX
CONTROLLINK EXT SW
COM
4
5
6123
123
DMX512OUTPUT
COOPERSBURG, PA 18036
R
1 2 3 4 5 1 2 3 4 5
SERIES
LIGHTINGCONTROL SYSTEM
SW2
SW1
SW1
SW2
J1
J2
J3
1 2 3 4 5 1 2 3 4 5
FUNCTION
GRAFIKEYEIN
DMX512OUT
G6000IN
DMX512OUT
DMX512IN
DIMMING
DATA OUT
GRX
COMBINER
USEDONLYWITHGRXCOMBINERFUNCTION
SEE INSTRUCTIONS
2
ON
ON
OFF
OFF
2
ON
OFF
OFF
ON
LED1LED2
INTERFACE CONTROL
SELV(CLASS2:USA)
LUT-DMX
12 3
12 3
DMXZONE
SELECT
EARTH
4
5
6
CONTROL LINK
EXT SW
COM
DMX512OUTPUT
LINK
COM
+V
MUX
MUX
CONTROLLINK EXT SW
COM
4
5
6123
123
DMX512OUTPUT
COOPERSBURG, PA 18036
R
1 2 3 4 5 1 2 3 4 5
SERIES
LIGHTINGCONTROL SYSTEM
SW2
SW1
SW1
SW2
J1
J2
J3
1 2 3 4 5 1 2 3 4 5
FUNCTION
GRAFIKEYEIN
DMX512OUT
G6000IN
DMX512OUT
DMX512IN
DIMMING
DATA OUT
GRX
COMBINER
USEDONLYWITHGRXCOMBINERFUNCTION
SEE INSTRUCTIONS
2
ON
ON
OFF
OFF
2
ON
OFF
OFF
ON
Front Side
DIPSwitches
MUXLinkto
GRAFIKEyeR
ControlUnitsand
Wallstations
6
(127)
73/4
(197)
21/2
(84)
ICEPELV/NECR
Class2Wiring
OutputStatusLEDs
GroundScrew
•Mountona4in(101.6mm)squarejunctionbox.
•Mayalsomountdirectlytothewall.
•Ensurethatthemetalcasingisgrounded.Connecta
groundwiretothegroundscrew.
•Notethatwiresdonotfeedthroughthebackoftheunit.
Mounting
LUT-DMX
4x4
(101.6x101.6)
JunctionBox
InsertWires
Through
Punch-Outs
Wall
LUT-DMX
Wall
3
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-564a 4 10.25.11
Control InterfacesLUT-DMX
GRAFIKR Systems
•ConnecttheDMX512linkterminalsontheLUT-DMXInterfacetotheinputterminalson
DMX512-controlledequipment.
•EachterminalontheLUT-DMXacceptstwo#18AWG(1.0mm
2
)wires.
•Linkmustbe1000feetorless.
•LinkmustbeginandendwithLinkTerminators.
Functions and Zone Capacities
DIPSwitchSettings
1 2
LUT-DMXInterfaceFunctionality
WorkswithGRAFIKEyeR3000and4000SeriesControlUnits.Enablesthemto
operateupto48or64totalGRAFIKEyeRlightingzonesandDMX512channels.
WorkswithGRAFIK5000T,GRAFIK6000R,andGRAFIK7000TSystems.
EnablesthemtooperateDMX512-controlledequipment.
•GRAFIK5000T:Upto128totallightingzonesandDMX512channels.
•GRAFIK6000R:Upto512totallightingzonesandDMX512channels.
AllowsDMX512stageboardstocontrolGPDimmingPanels.
1
1
Fornewconstruction,GPDimmingPanelsareavailablewith2LinkToption,whichprovidesDMX512
controlcapabilitywithoutaninterface.
UsedonlytoretrofitexistingGRAFIKEyeRlighting.GP4000combinerfunction.
1
DMX 512 Link Wiring
DMX512LinkTerminalson
LUT-DMX
1:DMX512systemCOMMON
2:DMX512systemDATA-(MUX)
3:DMX512systemDATA+(MUX)
Connectto:
DONOTconnecttoCOMMONon
GRAFIKEyeRControlUnitorProcessor.
Pin2onDMX512equipment.
Pin3onDMX512equipment.
4
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-564a 5 10.25.11
Control InterfacesLUT-DMX
GRAFIKR Systems
1 2 3
5 6
COM
-
+
DMX512OUTPUT
EXT
SW
ZONE6
ZONE4
HOT/LIVE
SSA
CUWIREONLY
ZONE2
ZONE3
ZONE5
NEUTRAL
ZONE1
CLASS 2
1 2 3 4
USA
Class2
IEC
PELV
CONTROL
LINK
1 2 3 4
ToadditionalWallstations/ControlInterfaces
(16Maximum;threefromoneControlUnit
withoutexternal12V-powersupply)
1000ft(305m)
Maximum
LUT-DMXWiringTerminals
COM
Data-
Data+
DMX512
Equipment
RearViewofGRAFIKEyeRControlUnit
LutronRCable
GRX-CBL-346S
•Makedaisy-chainconnectionstothelow-voltageIECPELV/NECRClass2
MUXLinkterminalsonthefrontofLUT-DMXInterface.
•DonotuseT-taps.Runallwiresinandoutofterminalblock.
•Eachterminalacceptsuptotwo#18AWG(1.0mm
2
)wires.
IEC PELV/NECR Class 2 Wiring for GRAFIK EyeR 3000/4000 Systems
DMX512
Equipment
LUT-DMX
Interface
GRX-4000
ControlUnit
GPDimmingPanel
IECPELV/NECRClass2wiringforsystemcommunications
5
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-564a 6 10.25.11
Control InterfacesLUT-DMX
GRAFIKR Systems
When used with GRAFIK EyeR 3000 Control Units
•Two#18AWG(1.0mm
2
)conductorsforcommon(terminal1)and12V-(terminal2).
Ensurethattheterminal2connectioniswiredcorrectly.RefertoGRX-3000Specification
Submittalformoredetails.
•Oneshielded,twistedpair#18AWG(1.0mm
2
)fordatalink(terminals3and4).
When used with GRAFIK EyeR 4000 Control Units
•Two#12AWG(2.5mm
2
)conductorsforcommon(terminal1)and24V-(terminal2).
Thesewillnotfitinterminals.Connectasshown.
•Oneshielded,twistedpair#18AWG(1.0mm
2
)fordatalink(terminals3and4).
•ConnectDrain/Shieldasshown.DonotconnecttoGround(Earth)orWallstation/
ControlInterfaces.Connectthebaredrainwiresandcutofftheoutsideshield.
IEC PELV/NECR Class 2 Terminal Connections
LED1LED2
123
12 3
DMXZONE
SELECT
EARTH
4
5
6
CONTROLLINK
EXTSW
COM
+
-
DMX512OUTPUT
DMX512OUTPUT
LINK
COM
+V
MUX
MUX
CONTROLLINK EXTSW
COM
-
+
4
5
6123
123
SW1
SW2
J1
J2
J3
1 2 3 4 5 1 2 3 4 5
DataLink-(1)twisted,
shieldedpair#18AWG
(1.0mm
2
)
3:MUX
4:MUX
IECPELV/NECRClass2
Controlwiring
1:Common
2:24V-
D:Drain/Shield
(2)#12AWG
(2.5mm
2
)
(2)#12AWG
(2.5mm
2
)
(1)#18AWG
(1.0mm
2
)
(1)#18AWG
(1.0mm
2
)
LUT-DMX
6
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-564a710.25.11
Control InterfacesLUT-DMX
GRAFIKR Systems
•ConnecttheLUT-DMXonthePowerPanelLink.
•Makedaisy-chainconnectionstothelow-voltageIECPELV/NECRClass2
MUXLinkterminalsonthefrontofLUT-DMXInterface.
•UseLinkTerminatorsatthebeginningandendofthePowerPanelLink.
•RefertoProcessorPanelSpecificationSubmittalformoreinformation.
IEC PELV/NECR Class 2 Wiring for GRAFIK 5000/6000/7000 Systems
UserInterfaceLinktoPC
LUT-DMX
Interface
ControlUnit
GPDimming
Panel
PowerPanelLink
WallstationLink
Wallstations
ProcessorPanel
Control
Interface
IEC PELV/NECR Class 2 Terminal Connections
•Two#12AWG(2.5mm
2
)conductorsforcommon(terminal1)and32V-(terminal2).These
willnotfitinterminals.Connectasshown.
•Oneshielded,twistedpair#18AWG(1.0mm
2
)fordatalink(terminals3and4).
•ConnectDrain/Shieldasshown.DonotconnecttoGround(Earth)orWallstation/Control
Interfaces.Connectthebaredrainwiresandcutofftheoutsideshield.
•Donotconnecttheextra#18AWG(1.0mm
2
)wiretotheLUT-DMX.ConnectonlytoDimming
Panelsasa“senseline”foremergency(essential)lighting.
LED1LED2
123
12 3
DMXZONE
SELECT
EARTH
4
5
6
CONTROLLINK
EXTSW
COM
+
-
DMX512OUTPUT
DMX512OUTPUT
LINK
COM
+V
MUX
MUX
CONTROLLINK EXTSW
COM
-
+
4
5
6123
123
SW1
SW2
J1
J2
J3
1 2 3 4 5 1 2 3 4 5
DataLink-(1)twisted,
shieldedpair#18AWG
(1.0mm
2
)
3:MUX
4:MUX
IECPELV/NECRClass2
Controlwiring
1:Common
2:32V-
D:Drain/Shield
(2)#12AWG
(2.5mm
2
)
(2)#12AWG
(2.5mm
2
)
(1)#18AWG
(1.0mm
2
)
(1)#18AWG
(1.0mm
2
)
LUT-DMX
7