S P E C I F I C AT I O N S U B M I T TA L Page
Job Name:
Job Number:
Model Numbers:
Wireless Stairwell Fixture
369471b 1 06.04.12
®
Wireless Stairwell Fixture Solution
(for the Hong Kong market)
The stairwell fixture works with a Lutron
Radio Powr Savr
TM wireless occupancy sensor (sold
separately) to save energy and lower energy costs. The
easy-to-install fixture includes a preprogrammed
dimming ballast and RF receiver that adjusts light levels
based on stairwell occupancy.
Features
•Universalinputvoltage120/277V
• Ballasthasoccupiedandunoccupiedlevelsthatcan
be preset to a specific location's code requirements for
lighted stairwells
• IntegralwirelesscontroldevicewithRFreceiver
• Integralfailsafedefaultstooccupiedlightlevelifsensoris
missing or malfunctioning
• Rotarylockinglampholders
• Alsoavailable:Emergencyballastbatterybackup
• Fullyassembledxturecomesreadytoinstall
• Powerfactorgreaterthan0.9
• Totalharmonicdistortion<10%
• ClassAsoundrating
•Novisiblelampflicker
•ApprovedtoULandCSAstandards
Fixture Specifications
• Ceilingorwallsurfacemount
• Housingandswitchbox:20gaugewhitehigh-reective
powder coat steel
Endcaps:18gaugewhitehigh-reectivepowdercoat
steel
• Lutronballastwithadjustablehigh-endoccupiedlevel
and low-end unoccupied level
Factorydefaultsetting:10%unoccupied;50%occupied
• Prismaticacryliclens
• 120/277V
universal input voltage
• CompatiblewithallLutronRadioPowrSavr
TM wireless
occupancy sensors
Environment
•10to40°C(50to104°F)
•Relativehumiditylessthan90%non-condensing
•Forindooruseonly
RF Range (occupancy sensor to wireless control)
•60foot(18m)lineofsight
•30foot(9m)throughnormalconstruction
Lamps
•UseonlywithlampsconformingtotheIEC
60081/60901specification;Lutronrecommends
Sylvania,GE,orPhilipslampsforproperdimming
performance
•Refertolampmanufacturerforlampburn-in
requirements
•Lampsarenotincludedwithfixture
•4-footxturesavailable;1or2lamps
Lampoptions:T8,T5HE,T5HO,reducedwattageT8
1
®
S P E C I F I C AT I O N S U B M I T TA L Page
Job Name:
Job Number:
Model Numbers:
Wireless Stairwell Fixture
369471b 2 06.04.12
®
Programming and Functionality
The wireless control device can be programmed to
performfourfunctions:
1.Burn-in. Pull out the air gap switch at the bottom of
the wireless control device. The lights will go to full on
(100%).Lutronrecommendsaburn-inperiodof12
hours.
2.Return to factory settings. To reset the occupied and
unoccupied light levels to their factory settings, perform
thefollowingsequenceusingthetapswitch:
Tap3times,holdingthetapswitchdownonthethird
tap. The lights will cycle up and down.
Releasethetapswitch,thenimmediatelytap3times.
Thelightswillcycleupanddown3timestoverifyyou
have returned to factory settings.
Note: Returning the wireless control device to factory
settings will disassociate it from any associated sensors.
3.Associate with sensor. Press and hold the tapswitch
onthewirelesscontroldevicefor6seconds,untilthe
LEDsash.Thenpressandholdthe"Off"or"LightsOn/
Off"buttononthesensorfor6seconds,untilthelens
onthesensorashesorange.Thesensorandlightswill
ashtoconrmassociation.
4.Set desired occupied and unoccupied light levels.
Press and hold the tapswitch and the up rocker at the
sametimefor3secondstoenterprogrammingmode.
· To set the desired occupied light level, use the up and
down rockers to raise or lower the light level. The table
below shows the approximate light levels, as displayed
bytheLEDs.
· Press the tapswitch once to continue to the unoccupied
lightlevelsetting;seethetablebelowfortheapproximate
lightlevelsasdisplayedbytheLEDs.
LED Display
= on
= off
Occupied
Setting
40% 50% 60% 70% 80% 90% 100%
Unoccupied
Setting
1% 5% 10% 20% 30% 40% 50%
Tapswitch
UpRocker
DownRocker
Airgapswitch
LEDs
Note: To set reduced wattage
T8lampstotheir10%lowend
light level, program the
unoccupied light level of the
wirelesscontroldeviceto1%.
· Press the tapswitch to save your light level settings
and return the wireless control device to normal
operation mode.
Note:Programmingmodewilltimeoutafter30
seconds if no buttons are pressed on the
wireless control device.
Wireless control device
2
®
S P E C I F I C AT I O N S U B M I T TA L Page
Job Name:
Job Number:
Model Numbers:
Wireless Stairwell Fixture
369471b 3 06.04.12
®
Photometric Data
For detailed photometric data, see www.lutron.com
Candela Plot Candela Table
0
15 30
45
60
75
90
105
120 135 150 165
180
15 30
45
60
75
90
105
120 135 150 165
250
500
750
1000
4100 K Data Zonal Lumen Summary
4 foot 2-lamp 32 W T8 stairwell fixture
Tested with clear prismatic lens
LightOutput 4406Lumens
Wattage 58.84
Lumens/Watt 74.88
ColorTemperature 4100K
Zone Lumens % of Luminaire
0-30 779 17.7
0-40 1301 29.5
0-60 2312 52.5
0-90 3403 77.2
90-180 1003 22.8
0-180 4406 100.0
0 90
0 937 937
5 929 946
15 900 981
25 841 979
35 748 883
45 619 750
55 429 614
65 195 588
75 79 575
85 23 497
90 1 426
Dimensions
513in(1299mm)
47^in(1218mm)
396in(1013mm)
47 in
(103mm)
73 in
(181mm)
6in(22mm)KO
provided at end
opposite the switch
1in(6mm)dia.
mountinghole(4x)
44 in
(111mm)
36 in
(98mm)
6in(22mm)KO
typ.
3
®
S P E C I F I C AT I O N S U B M I T TA L Page
Job Name:
Job Number:
Model Numbers:
Wireless Stairwell Fixture
369471b 4 06.04.12
®
Ordering Guide
Select appropriate code in each column to complete model number.
Example:FXSWXX12CP114U51XXXXWH
PRODUCT FAMILY TYPE SIZE LENS LAMPS
LAMP TYPE/
WATTAGE
REGION CONTROLS MOUNTING OPTIONS COLOR/FINISH
FX
Fixture
SW
Stairwell
XX
Standard
14
1 x 4 ft
CP
Clear prismatic
1
1 lamp
28
28 W T5HE,
4 ft
U
UL—North
America
51
50% high end,
10% low end
XX
Standard
XX
None
WH
Matte white
OA
Opal acrylic
2
2 lamps
32
32 W T8,
4 ft
82
80% high end,
20% low end
E1
T8 emergency
ballast
(not available for
2 ft fixture)
54
54 W T5HO,
4 ft
E3
T5HE emergency
ballast
(not available for
2 ft fixture)
RW
25,28,
30WT8
reduced
wattage,
4ft
E5
T5HO emergency
ballast
(not available for
2 ft fixture)
4