SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247f 1 08.26.19
GRX-TVI Ten Volt Interface
Features
100-277 V~ forward, reverse, and center phase control input
capability
Provides 0—10 V- control and switching capabilities to
switch and dim current sourcing fluorescent ballasts and LED
drivers.
Switches and dims current sourcing 010 V-
electronic dimming ballasts / drivers powered by
100—277 V~. Switches up to 16 A of electronic capacitive
ballasts / drivers.
Switches motors up to 1/2 HP @ 100-120 V~,
1 ½ HP @ 200—277 V~ and 5 A @ 230 V~ CE.
Up to five Ten Volt Interfaces may be connected to one
Control Unit zone. This allows one zone to control up to five
16 A circuits of Electronic Dimming Ballasts / Drivers or five
motors (This is not true for C5-BMJ-16A).
Provides 100—277 V~ power to loads.
Requires 100277 V~ power for internal operations.
Compatible Controls
Family Product
Wiring
Diagram
Residential Systems HW-RPM-4U I, J
HW-RPM-4A I, J
HWI-WPM-6D
(Wallbox Power
Module)
A, B
HxD-6ND C, D
HWV-FDB-8A E, F
MA-PRO C, D
Rx-6ND * C, D
RRD-10ND * C, D
GRX-IA A, B
RRD-6NA * C, D
RRD-PRO C, D
HQRD-6NA * C, D
HWD-5NE * C, D
HQRA-PRO C, D
HQRD-PRO C, D
Commercial Systems LP-RPM-4U I, J
LP-RPM-4A I, J
GRAFIK Eye
Control Unit
3000 Series or QSG
A, B
GP Panels K, L
C5-BMJ-16A ** M, N
Family Product
Wiring
Diagram
Wallbox Fluorescent 3-wire
Dimmers
AYF-103P E, F
DVF-103P E, F
DVSCF-103P E, F
LXF-103PL E, F
MAF-6AM ** G, H
MRF2-F6AN-DV G, H
MSCF-6AM ** G, H
NF-10 E, F
NF-103P E, F
NTF-10 E, F
NTF-103P E, F
SF-10P E, F
SF-103P E, F
VF-10 E, F
VTF-6AM G, H
MRF2-6ELV-120 * C, D
* The low end trim should be set at 28% and the high end trim
at 81% manually to have the output signal set to fluorescent
load type.
** These specific controls result in the GRX-TVI not conforming
to the IEC929 standard for 0—10 V- output since they cannot
reach the 1 V- minimum.
All models in this column are set to fluorescent load type except those
model numbers followed by a *.
Note: 277 V~ operation on the control terminal was a design feature
added September 2013. To check whether your TVI has this feature,
please ensure the front label of the TVI shows the acceptable voltage
range as 100—277 V~ for the control input. Prior revisions of the unit
had (2) L2/H2 terminals (one for 120 V~ and one for 240 V~). The current
design of the unit accepts a universal voltage (100—277 V~), so either
of these terminals can be used for the control feed. They are internally
tied together.
1
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247f 2 08.26.19
Specifications
Regulatory Approvals
• cUL
® Listed in US and Canada
• CE
NOM (Mexico)
Complies with requirements for use in other spaces
used for environmental air (plenums) per
NEC
® 2014 300.22(C)(3)
Meets the Canadian National Building Code plenum
requirements for a concealed space used as a
plenum within a floor or roof assembly
Power
Control circuit: 100—277 V~
Output/Load circuit: 100—277 V~
Control and Load circuits are independent of each
other and can have unique phases
Works with all ballasts and drivers that provide a
current source that is compliant to IEC 60629 Annex
E.2, and whose inrush current does not exceed
NEMA410 standards for electronic ballast/driver
0-10 V- Dimming Control
Output rating: 10 µA—300 mA. Sinks current only
(ballast / driver must source / provide 10 V- supply).
<1 V- minimum, >10 V- maximum
Zone Capacity
Up to five Ten Volt Interfaces per Control Unit zone.
(This is not true for C5-BMJ-16A)
Key Design Features
Complies with UL508 Standard
Provides a Class 2 isolated 010 V- output signal
that conforms to EN60929 and IEC929
Accepts a forward, reverse and center phase control
signal (100—277V~ 50 / 60 Hz)
Terminals
Each terminal accepts up to two 12 AWG (2.5 mm
2
)
conductors
Physical Design
Wall-mounted. Indoor use only. Type 1 enclosure.
Weight: 4.25 lbs (2 kg)
Environment
Temperature: 32 ºF to 104 ºF (0 ºC to 40 ºC)
0 to 90% humidity, non-condensing
Switching Load Types and Capacities
Source / Load Type 100—277 V~ * 230 V~ (CE)
Fluorescent
Electronic Capacitive
Non-Dim
Other manufacturers'
0—10 V- ballasts / drivers
16 A
16 A
10 A
10 A
LED 16 A 10 A
Incandescent 16 A 10 A
Low-voltage 16 A 10 A
Metal Halide 16 A 10 A
Neon / Cold Cathode 16 A 10 A
Motor 1/2 HP @ 100—120 V~
1 ½ HP @ 200—277 V~
5 A @ 230 V~ CE
* Not if product requires CE certification
2
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247f 3 08.26.19
COOPERSBURG, PA 18036 U.S.A.
0-10V INTERFACE CONTROL
Control Input: 100-120V,
220-240V 50/60Hz
Switches:
100-277VAC
GRX-TVI
Incandescent 16A
Fluorescent 5A
Magnetic Low-voltage 16A
Electronic Low-voltage 16A
Motor 1/4 HP@120V
V772@PH 2/1
¨
GRX-TVI Input Rating
I
H
2
0.02A
I
DH
2
0.1A
0-10V Output Rating
Max. 0.3A
Switched Rating
Dimensions and Mounting
Mount only where ambient temperature is 32°F to
104°F (0°C to 40°C)
Allow 4.5in (114mm) between Interfaces when
mounting several in a vertical layout
Mount so that line (mains) voltage wiring is at least
6ft (1.8m) from sound or electronic equipment and
associated wiring
Mount within 7° of true vertical
Front View
(cover closed)
Mounting Holes
0.25 in (6 mm) dia.
Load / Output Circuit
Control Circuit
0—10 V-
Dimming Control
Side View Front View
(cover open)
12.5 in
(318 mm)
4 in
(102 mm)
3.3 in
(84 mm)
6.1 in
(155 mm)
11.75 i n
(298 mm)
COOPERSBURG, PA 18036 U.S.A.
0-10V INTERFACE CONTROL
Control Input: 100-120V,
220-240V 50/60Hz
Switches:
100-277VAC
GRX-TVI
Incandescent 16A
Fluorescent 5A
Magnetic Low-voltage 16A
Electronic Low-voltage 16A
Motor 1/4 HP@120V
V772@PH 2/1
¨
GRX-TVI Input Rating
I
H
2
0.02A
I
DH
2
0.1A
0-10V Output Rating
Max. 0.3A
Switched Rating
COOPERSBURG, PA 18036 U.S.A.
0-10V INTERFACE CONTROL
Control Input: 100-120V,
220-240V 50/60Hz
Switches:
100-277VAC
GRX-TVI
Incandescent 16A
Fluorescent 5A
Magnetic Low-voltage 16A
Electronic Low-voltage 16A
Motor 1/4 HP@120V
V772@PH 2/1
¨
GRX-TVI Input Rating
I
H
2
0.02A
I
DH
2
0.1A
0-10V Output Rating
Max. 0.3A
Switched Rating
4.5 in (110 mm)
minimum
Diagnostic LED
3
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247f 4 08.26.19
Wiring Diagrams
Each terminal can accept up to two 12 AWG
(2.5 mm
2
) conductors.
L1 / H1 is the Line / Hot feed to power the load.
L2 / H2 (on the control circuit terminals) supplies
operating power for the Ten Volt Interface.
Wiring Diagrams A, C, E, G, I, and M show a
GRX-TVI wired from one distribution panel. If the
power requirement of the complete system is less
than an MCB / circuit breaker rating and L1 / H1 and
L2 / H2 are both coming from the same phase, one
feed can be jumpered inside the enclosure
(as shown).
Wiring Diagrams B, D, F, H, J, L, and N show a
GRX-TVI wired from two separate distribution panels
that may be different phases or voltages.
Wiring Diagram O shows a GRX-TVI wired from one
distribution panel with 2 separate feeds.
Make sure L2 / H2 and DL2 / DH2 (Dimmed
Line / Dimmed Hot) are fed from the same breaker
that powers the control unit.
Run separate neutrals for load circuit and control
circuit- no common neutrals.
• NEC
® Class 2 / IEC PELV, 0—10 V- wiring from a
ballast / driver to the GRX-TVI must be separated
from the power wiring. Enter the Class 2 / PELV
wires through the knockout adjacent to the
0—10 V - terminal blocks. The barrier ensures
separation and is flexible to allow access to the
terminals. The barrier must be in place when
installation is complete.
Wiring Diagram A: HomeWorks Wallbox Power Module / GRAFIK Eye Control Unit
1 Distribution Panel / 1 Feed
V-
100-
127 V~
220-
240 V~
L
2
/H
2
100-277 V~
LUTRON
LUTRON
GRX-TVI
HomeWorks Wallbox Power
Module
1
(HWI-WPM-6D)
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage
in the range of 100277 V~. Refer to
the Note on the first page of the
GRX-TVI Specification Submittal.
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
OR
Dimmed Line /
Dimmed Hot, DL / DH
Switched Line / Hot
Line / Hot
Line / Hot
0—10 V-
Ballast / Driver
1
0—10 V-
Ballast / Driver
1
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
Lutron is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
Neutral
Distribution
Panel
Neutral
Earth / Ground
Note: Ballast / driver must
provide a 0—10 V- source
only!
L1 / H1 is the Line / Hot feed that powers
the Switched Line / Hot output to the
load. Shown in picture as the same
voltage as L2 / H2.
Neutral
Line / Mains Voltage:
100—240 V~
GRAFIK EyeR
Control Unit
1
1
Control units and ballasts / drivers must be rated for the specific Line / Mains
voltage utilized.
4
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247f 5 08.26.19
L2/H2 100-277 V~
LUTRON
LUTRON
GRX-TVI
To additional ballast / drivers
Note: Ballast / driver must
provide a 0—10 V- source
only!
EARTH / GROUND
CONNECTIONS
GRAFIK Eye
Control Unit
1
OR
Dimmed Line /
Dimmed Hot, DL / DH
Switched Line / Hot
Line / Hot
Line / Hot
Line / Hot
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
Lutron is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
Neutral
Neutral
Distribution
Panel A
Distribution
Panel B
Neutral
Earth / Ground
Earth / Ground
Wiring Diagram B: HomeWorks Wallbox Power Module / GRAFIK Eye Control Unit
— 2 Distribution Panels / 2 Feeds
HomeWorks Wallbox Power
Module
1
(HWI-WPM-6D)
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage
in the range of 100277 V~. Refer to
the Note on the first page of the
GRX-TVI Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot output
to the load. Use any voltage in the
range of 100277 V~.
Note: If the voltage of the ballast / driver is
different from the voltage of the control device,
they should come from different distribution panels
(demonstrated above).
If the control side plus the load side current is
greater than the circuit breaker rating, and the
voltages of load and control are the same level,
follow Diagram O.
Line / Mains Voltage:
100—277 V~
0—10 V-
Ballast / Driver
2
0—10 V-
Ballast / Driver
2
1
Control units must be rated for the Distribution Panel A Line / Mains
voltage utilized.
2
Ballasts / drivers must be rated for the Distribution Panel B Line / Mains
voltage utilized.
Line / Mains Voltage:
100—240 V~
Wiring Diagrams (continued)
5
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247f 6 08.26.19
Wiring Diagram C: HomeWorks Maestro / RadioRA / RadioRA 2 Dimmers
— 1 Distribution Panel / 1 Feed
L2/H2 100-277 V~
GRX-TVI
Remote
Dimmer
1
Dimmer
1
To additional ballast / drivers
EARTH / GROUND
CONNECTIONS
Blue
2
Brass
Black
Blue
2
Brass
Silver
Black
Switched Line / Hot
Line / Hot
Line / Hot
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
Lutron is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
Neutral
(white wire)
Distribution
Panel
Neutral (white wire)
Earth / Ground
Note: Ballast / Driver must
provide a 0—10 V- source
only!
Note: Dimmer
must be wired on
the load side of the
Remote Dimmer.
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage in
the range of 100277 V~. Refer to the
Note on the first page of the
GRX-TVI Specification Submittal.
L1 / H1 is the Line / Hot feed that powers
the Switched Line / Hot output to the
load. Shown in picture as the same
voltage as L2 / H2.
Neutral
Line / Mains Voltage:
100—240 V~
2
When used as a single-pole dimmer, the blue screw terminal is not used.
Tighten the blue screw terminal—do not connect the blue screw terminal to
ground or to any other wiring.
0—10 V-
Ballast / Driver
1
0—10 V-
Ballast / Driver
1
1
Dimmers and ballasts / drivers must be rated for the specific Line / Mains voltage
utilized.
Wiring Diagrams (continued)
6
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247f 7 08.26.19
Wiring Diagram D: HomeWorks Maestro / RadioRA / RadioRA 2 Dimmers
— 2 Distribution Panels / 2 Feeds
L2/H2 100-277 V~
GRX-TVI
To additional ballast / drivers
EARTH / GROUND
CONNECTIONS
Blue
3
Brass
Black
Blue
3
Brass
Silver
Black
Switched Line / Hot
Line / Hot
Line / Hot
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
Lutron is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
Neutral
Neutral
Earth / Ground
Note: Ballast / driver must
provide a 0—10 V- source
only!
Line / Hot
Neutral
Distribution
Panel A
Distribution
Panel B
Earth / Ground
Note: Dimmer
must be wired
on the load side
of the Remote
Dimmer.
Note: If the voltage of the ballast / driver is
different from the voltage of the control device,
they should come from different distribution panels
(demonstrated above).
If the control side plus the load side current is
greater than the circuit breaker rating, and the
voltages of load and control are the same level,
follow Diagram O.
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage in
the range of 100277 V~. Refer to the
Note on the first page of the
GRX-TVI Specification Submittal.
L1 / H1 is the Line / Hot feed that powers
the Switched Line / Hot output to the
load. Use any voltage in the range of
100277 V~.
Line / Mains Voltage:
100—277 V~
Remote
Dimmer
1
Dimmer
1
0—10 V-
Ballast / Driver
2
0—10 V-
Ballast / Driver
2
1
Dimmers must be rated for the Distribution Panel A Line / Mains
voltage utilized.
2
Ballasts / drivers must be rated for the Distribution Panel B Line / Mains
voltage utilized.
3
When used as a single-pole dimmer, the blue screw terminal is not used.
Tighten the blue screw terminal—do not connect the blue screw terminal to
ground or to any other wiring.
Line / Mains Voltage:
100—240 V~
Wiring Diagrams (continued)
7
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247f 8 08.26.19
Wiring Diagram E: Ariadni / Diva / Lyneo / Skylark / Nova / Nova T / Vareo 3-wire Fluorescent Dimmers — 1
Distribution Panel / 1 Feed
L2/H2 100-277 V~
GRX-TVI
Dimmer
1
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
Red
3
Blue
2
Brass /
Gold
Copper /
Black
Copper /
Black
Violet
or Blue
Switched Line / Hot
Line / Hot
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
Lutron is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
White
Yellow or
Orange
Distribution
Panel
Neutral
Earth / Ground
Note: Ballast / driver must
provide a 0—10 V- source
only!
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage in
the range of 100277 V~. Refer to the
Note on the first page of the GRX-TVI
Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot
output to the load. Shown in
picture as the same voltage as
L2 / H2.
Neutral
Line / Mains Voltage:
100—277 V~
0—10 V-
Ballast / Driver
1
0—10 V-
Ballast / Driver
1
1
Switches, dimmers, and ballasts / drivers must be rated for the specific Line / Mains
voltage utilized.
2
Single pole dimmers use black for the line / hot wire. Refer to the single-pole dimmer's
installation instructions to identify the line / hot wire for that product.
3
The red wire is not used. Cap off the red wire using a wire connector. Do not wire the
red wire to ground or to any other wiring.
3-way
Switch
1
Wiring Diagrams (continued)
8
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247f 9 08.26.19
Wiring Diagram F: Ariadni / Diva / Lyneo / Skylark / Nova / Nova T / Vareo 3-wire Fluorescent Dimmers — 2
Distribution Panels / 2 Feeds
L2/H2 100-277 V~
Line / Hot
Neutral
Earth / Ground
Distribution
Panel B
GRX-TVI
3-way
Switch
1
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
Red
4
Blue
3
Brass /
Gold
Copper /
Black
Copper /
Black
Violet
or Blue
Switched Line / Hot
Line / Hot
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
Lutron is not liable for damage due
to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
White
Yellow or
Orange
Distribution
Panel A
Neutral
Earth / Ground
Note: Ballast / driver must
provide a 0—10 V- source
only!
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage in
the range of 100277 V~. Refer to the
Note on the first page of the GRX-TVI
Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot
output to the load. Use any
voltage in the range of
100277 V~.
Note: If the voltage of the ballast / driver is
different from the voltage of the control device,
they should come from different distribution panels
(demonstrated above).
If the control side plus the load side current is
greater than the circuit breaker rating, and the
voltages of load and control are the same level,
follow Diagram O.
Line / Mains Voltage:
100—277 V~
0—10 V-
Ballast / Driver
2
0—10 V-
Ballast / Driver
2
1
Switches and dimmers must be rated for the Distribution Panel A Line / Mains
voltage utilized.
2
Ballasts / drivers must be rated for the Distribution Panel B Line / Mains
voltage utilized.
3
Single pole dimmers use black for the line / hot wire. Refer to the single-pole
dimmer's installation instructions to identify the line / hot wire for that product.
4
The red wire is not used. Cap off the red wire using a wire connector. Do not wire
the red wire to ground or to any other wiring.
Dimmer
1
Line / Mains Voltage:
100—277 V~
Wiring Diagrams (continued)
9
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247f 10 08.26.19
Wiring Diagram G: Maestro / Vierti 3-wire Fluorescent Dimmers — 1 Distribution Panel / 1 Feed
L2/H2 100-277 V~
GRX-TVI
Companion
Dimmer
1
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
Blue
3
Blue Brass
2
Brass
Black
Silver
Black
Switched Line / Hot
Line / Hot
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
LutronR is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
Yellow or
Orange
Distribution
Panel
Neutral
Earth / Ground
Note: Ballast / driver must
provide a 0—10 V- source only!
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage in
the range of 100277 V~. Refer to the
Note on the first page of the GRX-TVI
Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot
output to the load. Shown in
picture as the same voltage as
L2 / H2.
Neutral
White
Line / Mains Voltage:
100—277 V~
0—10 V-
Ballast / Driver
1
0—10 V-
Ballast / Driver
1
1
Dimmers, companion dimmers, and ballasts / drivers must be rated for the specific
Line / Mains voltage utilized.
2
The brass screw terminal is not used. Tighten the brass screw terminal. Do not connect
the brass screw terminal to ground or to any other wiring.
3
When used as a single-pole dimmer, the blue screw terminal is not used. Tighten
the blue screw terminal—do not connect the blue screw terminal to ground or to
any other wiring.
Dimmer
1
Wiring Diagrams (continued)
10
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247f 11 08.26.19
Wiring Diagram H: Maestro / Vierti 3-wire Fluorescent Dimmers — 2 Distribution Panels / 2 Feeds
L2/H2 100-277 V~
Line / Hot
Neutral
Earth / Ground
Distribution
Panel B
GRX-TVI
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
Switched Line / Hot
Line / Hot
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
Lutron is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
Distribution
Panel A
Neutral
Earth / Ground
Note: Ballast / driver must
provide a 0—10 V- source
only!
Companion
Dimmer
1
Blue
4
Blue
Brass
3
Brass
Black
Silver
Black
Yellow or
Orange
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage in
the range of 100277 V~. Refer to the
Note on the first page of the GRX-TVI
Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot
output to the load. Use any
voltage in the range of
100277 V~.
Note: If the voltage of the ballast / driver is
different from the voltage of the control device,
they should come from different distribution panels
(demonstrated above).
If the control side plus the load side current is
greater than the circuit breaker rating, and the
voltages of load and control are the same level,
follow Diagram O.
White
Line / Mains Voltage:
100—277 V~
0—10 V-
Ballast / Driver
2
0—10 V-
Ballast / Driver
2
1
Dimmers and companion dimmers must be rated for the Distribution Panel A Line / Mains
voltage utilized.
2
Ballasts / drivers must be rated for the Distribution Panel B Line / Mains voltage utilized.
3
The brass screw terminal is not used. Tighten the brass screw terminal. Do not connect
the brass screw terminal to ground or to any other wiring.
4
When used as a single-pole dimmer, the blue screw terminal is not used. Tighten the blue
screw terminal—do not connect the blue screw terminal to ground or to any other wiring.
Dimmer
1
Line / Mains Voltage:
100—277 V~
Wiring Diagrams (continued)
11
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247f 12 08.26.19
Wiring Diagram I: HomeWorks Remote Power Module / LP Module — 1 Distribution Panel / 1 Feed
L2/H2 100-277 V~
GRX-TVI
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
Red—Module Output
Switched Line / Hot
Line / Hot
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
Lutron is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
White
Black
Distribution
Panel
Neutral
Earth / Ground
Note: Ballast / driver must
provide a 0—10 V- source
only!
RPM / LP
Module
1
Terminal
Blocks
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage
in the range of 100277 V~. Refer to
the Note on the first page of the
GRX-TVI Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot
output to the load. Shown in
picture as the same voltage as
L2 / H2.
Neutral
Line / Mains Voltage:
100—240 V~
0—10 V-
Ballast / Driver
1
0—10 V-
Ballast / Driver
1
1
Remote Power Modules and ballasts / drivers must be rated for the specific Line / Mains
voltage utilized.
Wiring Diagrams (continued)
12
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247f 13 08.26.19
L2/H2 100-277 V~
Wiring Diagram J: HomeWorks Remote Power Module / LP Module — 2 Distribution Panels / 2 Feeds
Line / Hot
Neutral (white wire)
Earth / Ground
Distribution
Panel B
Distribution
Panel A
GRX-TVI
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
Red—Module Output
Switched Line / Hot
Line / Hot
Earth / Ground
Earth / Ground
NOTICE: 0
10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
Lutron is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
White
Black
Neutral
Earth / Ground
Note: Ballast / driver must
provide a 0—10 V- source
only!
RPM / LP
Module
1
Terminal
Blocks
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage
in the range of 100277 V~. Refer to
the Note on the first page of the
GRX-TVI Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot
output to the load. Use any voltage
in the range of 100277 V~.
Note: If the voltage of the ballast / driver is
different from the voltage of the control device,
they should come from different distribution panels
(demonstrated above).
If the control side plus the load side current is
greater than the circuit breaker rating, and the
voltages of load and control are the same level,
follow Diagram O.
Line / Mains Voltage:
100277 V~
0—10 V-
Ballast / Driver
2
0—10 V-
Ballast / Driver
2
1
Remote Power Module must be rated for the Distribution Panel A Line / Mains voltage utilized.
2
Ballasts / drivers must be rated for the Distribution Panel B Line / Mains voltage utilized.
Line / Mains Voltage:
100240 V~
Wiring Diagrams (continued)
13
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247f 14 08.26.19
Wiring Diagram K: GP Panel — 1 Distribution Panel / 1 Feed
L2/H2 100-277 V~
GRX-TVI
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
Switched Line / Hot
Line / Hot
Dimmed Line /
Dimmed Hot, DL / DH
Earth / Ground
Earth / Ground
NOTICE: 0
10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
Lutron is not liable for damage due to miswiring.
Neutral
Neutral
Earth / Ground
Note: Ballast / driver must
provide a 0—10 V- source
only!
GP Panel
1
Load
Terminals
(1 circuit
shown)
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage
in the range of 100277 V~. Refer to
the Note on the first page of the
GRX-TVI Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot
output to the load. Shown in picture
as the same voltage as L2 / H2
0—10 V-
Ballast / Driver
1
0—10 V-
Ballast / Driver
1
1
GP Panel and ballasts / drivers must be rated for the specific Line / Mains voltage utilized.
Wiring Diagrams (continued)
14
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247f 15 08.26.19
L2/H2 100-277 V~
Wiring Diagram L: GP Panel — 2 Distribution Panels / 2 Feeds
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Distribution
Panel B
GRX-TVI
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
Switched Line / Hot
Line / Hot
Dimmed Line /
Dimmed Hot, DL / DH
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
Lutron is not liable for damage due to miswiring.
Neutral
Neutral
Earth / Ground
Note: Ballast / driver must
provide a 0—10 V- source
only!
GP Panel
1
Load
Terminals
(1 circuit
shown)
Line / Hot
Neutral
Earth / Ground
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage
in the range of 100277 V~. Refer to
the Note on the first page of the
GRX-TVI Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot
output to the load. Use any voltage
in the range of 100277 V~.
Line / Mains Voltage:
100—277 V~
0—10 V-
Ballast / Driver
2
0—10 V-
Ballast / Driver
2
1
GP Panel must be rated for the for the specific Line / Mains voltage utilized.
2
Ballasts / drivers must be rated for the Distribution Panel B Line / Mains voltage utilized.
15
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247f 16 08.26.19
Wiring Diagram M: EcoSystem Dimming Power Module for 3-wire Lutron Dimming Ballast / drivers
— 1 Distribution Panel / 1 Feed
L2/H2 100-277 V~
E1
E1
+20V
Common
IR
OCC
Daylight
E2
E2
Class 2 Sensors
Capteurs Classe 2
Sensores Clase 2
Class 2 Link
Lien Classe 2
Enlace Clase 2
EcoSystem
®
Multiple Fixture Dimming Control
Contrôle de gradation de multiples luminaires
Control atenuador de múltiples lámparas
PWR
STAT
Indicateur de puissance (PWR)
On: l’unité est alimentée
Off: l’unité n’est pas alimentée
ou est dysfonctionnelle
Indicateur d’activité (STAT)
Plein: Niveau de circuit
Impulsion: Aucune
communication
Power Indicator (PWR)
On: Unit is powered
Off: Unit is not powered
or is malfunctioning
Status Indicator (STAT)
Solid: Circuit Level
Pulse: No communication
Indicador de Alimentación (PWR)
Encendido: unidad tiene corriente
Apagado: unidad no tiene corriente
o no está funcionando correctamente
Indicador de estado (STAT)
Sólido: Nivel del Circuito
Pulsante: No hay comunicación
C5-BMJ-16A
COM
DYLT
P/N 500-10755
®
GRX-TVI
EcoSystem
Power
Module
2
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
Red
1
Black
Switched Line / Hot
Line / Hot
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
Lutron is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
White
Orange
Distribution
Panel
Neutral
Earth / Ground
Note: Ballast / driver must
provide a 0—10 V- source
only!
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage in
the range of 100277 V~. Refer to the
Note on the first page of the GRX-TVI
Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot
output to the load. Shown in picture
as the same voltage as L2 / H2.
Neutral
Green
E1
E2
To additional
EcoSystem
modules,
ballast / drivers
and EcoSystem
Bus Supply
Line / Mains Voltage:
100—277 V~
0—10 V-
Ballast / Driver
2
0—10 V-
Ballast / Driver
2
1
The red wire is not used. Cap off the red wire using a wire connector. Do not wire the red
wire to ground or to any other wiring.
2
The EcoSytem Power Module and ballasts / drivers must be rated for the specific
Line / Mains voltage utilized.
16
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247f 17 08.26.19
Wiring Diagram N: EcoSystem Dimming Power Module for 3-wire Lutron Dimming Ballast / drivers
— 2 Distribution Panels / 2 Feeds
L2/H2 100-277 V~
E1
E1
+20V
Common
IR
OCC
Daylight
E2
E2
Class 2 Sensors
Capteurs Classe 2
Sensores Clase 2
Class 2 Link
Lien Classe 2
Enlace Clase 2
EcoSystem
®
Multiple Fixture Dimming Control
Contrôle de gradation de multiples luminaires
Control atenuador de múltiples lámparas
PWR
STAT
Indicateur de puissance (PWR)
On: l’unité est alimentée
Off: l’unité n’est pas alimentée
ou est dysfonctionnelle
Indicateur d’activité (STAT)
Plein: Niveau de circuit
Impulsion: Aucune
communication
Power Indicator (PWR)
On: Unit is powered
Off: Unit is not powered
or is malfunctioning
Status Indicator (STAT)
Solid: Circuit Level
Pulse: No communication
Indicador de Alimentación (PWR)
Encendido: unidad tiene corriente
Apagado: unidad no tiene corriente
o no está funcionando correctamente
Indicador de estado (STAT)
Sólido: Nivel del Circuito
Pulsante: No hay comunicación
C5-BMJ-16A
COM
DYLT
P/N 500-10755
®
GRX-TVI
EcoSystem
Power
Module
2
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
Red
1
Black
Switched Line / Hot
Line / Hot
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
Lutron is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
White
Orange
Distribution
Panel A
Neutral
Earth / Ground
Note: Ballast / driver must
provide a 0—10 V- source
only!
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage in
the range of 100277 V~. Refer to the
Note on the first page of the GRX-TVI
Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot
output to the load. Use any voltage
in the range of 100277 V~.
Neutral
Green
E1
E2
To additional
EcoSystem
modules,
ballast / drivers
and EcoSystem
Bus Supply
Distribution
Panel B
Line / Hot
Earth / Ground
Neutral
Note: If the voltage of the ballast / driver is
different from the voltage of the control device,
they should come from different distribution panels
(demonstrated above).
If the control side plus the load side current is
greater than the circuit breaker rating, and the
voltages of load and control are the same level,
follow Diagram O.
Line / Mains Voltage:
100—277 V~
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
0—10 V-
Ballast / Driver
3
0—10 V-
Ballast / Driver
3
1
The red wire is not used. Cap off the red wire using a wire connector. Do not wire the red wire to
ground or to any other wiring.
2
The EcoSystem Power Module must be rated for the for the Distribution Panel A Line / Mains
voltage utilized.
3
Ballasts / drivers must be rated for the Distribution Panel B Line / Mains voltage utilized.
17
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247f 18 08.26.19
Wiring Diagram O: 1 Distribution Panel with 2 Separate Feeds
N2
N1
L2/H2 100-277 V~
GRX-TVI
Remote
Dimmer
1
Dimmer
1
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
BlueBrass
Black
BlueBrass
Silver
Black
Switched Line / Hot
Line / Hot 1
Line / Hot 2
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
Lutron is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
Neutral
Note: Ballast / driver must
provide a 0—10 V- source
only!
Line / Hot
Neutral 1
Distribution
Panel
Earth / Ground
Note: Dimmer
must be wired
on the load
side.
L2 / H2 terminals are tied to each
other internally. It is the Line / Hot
feed that powers the internal circuitry
of the GRX-TVI. Use the appropriate
voltage in the range of 100277 V~.
Refer to the Note on the first page of
the GRX-TVI Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot
output to the load.
Use any voltage in the range of
100277 V~. Shown in picture as
the same voltage as L2 / H2.
Neutral 2
Note: Wiring of the dimmer could vary depending
on the type of dimmer that you choose.
Consult Lutron at 1.844.LUTRON1 or
www.lutron.com/support
Line / Mains Voltage:
100—277 V~
0—10 V-
Ballast / Driver
1
0—10 V-
Ballast / Driver
1
1
Dimmers and ballasts / drivers must be rated for the specific Line / Mains voltage utilized.
)Lutron, Lutron, EcoSystem, HomeWorks, Maestro, Vierti, Ariadni, Diva, Lyneo, Skylark, Nova, Nova T*, Vareo, RadioRA, RadioRA 2, and GRAFIK Eye are trademarks or
registered trademarks of Lutron Electronics Co., Inc. in the US and/or other countries.
NEC is a registered trademark of National Fire Protection Association, Quincy, Massachusetts.
UL is a trademark of UL LLC.
18