SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241m 1 08.05.19
Energi Savr Node for 010 V-
Energi Savr Node with Softswitch
The Energi Savr Node (ESN) family is a group of modular
products for the control of lighting and other loads. This
document describes the following products:
• ESN unit for 0 10 V- (models QSN-4T16-S and
QSN-4T16-S-347 — 0 10 V- Control / Softswitch)
• Softswitch ESN unit (models QSN-4S16-S and
QSN-4S16-S-347 — Softswitch)
Features
Default configuration requires no commissioning.
Programming using integral interface on the ESN unit.
Four occupancy sensor inputs for automated control of
lights in 4 zones.
Four daylight sensor inputs automatically adjust light
levels based on the amount of natural light entering
through the windows.
Four IR receiver inputs for personal control.
Four inputs for IEC PELV / NEC® Class 2 dry contact
switches.
Includes QS control link for seamless integration of lights,
control stations, and QS sensor modules.
Softswitch technology yields 1,000,000 cycle relay
lifetime.
Contact Lutron for compatibility with Quantum system.
System Example
QS link
Control Power
120–277 V~
Load Input Feeds (4)
120–277 V~; 347 V~
3
0–10 V Channels (4)
QSN-4T16-S and QSN-4T16-S-347
Emergency
Contact
Closure
Input
Contact
Closure
Input
Switched Load Outputs (4)
16 A Softswitch 120–277 V~; 347 V~
3
Wireless
Communication
Wired Daylight
Sensors (up to 4)
2
Wired
Daylight
Sensors
(up to 4)
1,2
Wired Occupancy
Sensors (up to 4)
Wired
Occupancy
Sensors
(up to 4)
1
Wired Wallstation
or IR receivers (up to 4)
Wired
Wallstation
or IR Receivers
(up to 4)
1
IEC PELV /
NECR Class 2
Dry Contact
Switch (up to 4)
(by others)
IR Transmitter
IR TransmitterOR OR
OR OR
Notes:
1 Up to 4 wired sensors total (of any type).
2 The maximum number of daylight sensors (wired and
wireless) that an ESN unit can support is
four (1 per zone).
3 For 347 V~ models only.
QSM
seeTouch QS
Wallstation
ESN
Programming
Interface
Radio Powr Savr
Occupancy
Sensor (up to 10
per QSM)
Radio Powr Savr
Daylight Sensor
(up to 10 per QSM)
2
Pico Wireless
Controller
(up to 10 per
QSM)
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241m 2 08.05.19
Specifications
Regulatory Approvals
• UL Listed
• CSA
• NOM
Lutron Quality Systems registered to ISO 9001:2015
Complies with requirements for use in other spaces
used for environmental air (plenums) per
NEC® 2014 300.22(C)(3)
Meets the Canadian National Building Code plenum
requirements for a concealed space used as a plenum
within a floor or roof assembly
For commercial use, Class A only
Power
Control Power: 120 V~; 220–240 V~; 277 V~
50 / 60 Hz
Lightning strike protection meets ANSI / IEEE standard
62.41-1991. Can withstand voltage surges of up to
6,000 V~ and current surges of up to 3,000 A
Current draw: 0.5 A max
10-year power failure memory: restores lighting to levels
prior to power interruption
Latching relays keep previously illuminated zones on
when control power feed is lost
Environment
Ambient Temperature Operating Range: 32 ºF to 104 ºF
(0 ºC to 40 ºC)
Relative humidity: less than 90% non-condensing
For indoor use only
Thermal dissipation: 40 BTU/hr
Terminal Wiring
Control Power Wiring: 14AWG to 12AWG (2.5mm
2
to
4.0mm
2
)
Load Wiring: 14AWG to 12AWG (2.5mm
2
to 4.0mm
2
)
010 V- Wiring: 20AWG to 12AWG (0.5mm
2
to 4.0mm
2
)
Input Group Wiring: 20AWG to 12AWG (0.5mm
2
to
4.0mm
2
) — maximum wire run length to each input not
to exceed 150 ft (46 m)
QS Link Wiring: 22AWG to 12AWG (0.5mm
2
to
4.0mm
2
)
Contact Closure Wiring: 20AWG to 12AWG (0.5mm
2
to 4.0mm
2
)
Physical Design and Mounting
NEMA Type 1, IP-20 protection
Surface mount
Load Types (relay ratings)
16 A Tungsten, 120 to 277 V~
16 A AC General Use, 120 to 277 V~
16 A Electric Discharge Lamp (ballast), 120 to
277 V~, 347 V~ (347 V~ models only)
16 A Inductive, 120 to 277 V~
0.5 HP, 120 V~
1.5 HP, 220 to 277 V~
Works with all ballasts and drivers that provide a current
source that is compliant to IEC 60629
Annex E.2, and whose inrush current does not exceed
NEMA410 standards for electronic ballast/driver
Input Default Associations
Inputs/Outputs Zone 1 Zone 2 Zone 3 Zone 4
Group 1
Occ X
Photo X
IR X
Switch X
Group 2
Occ X
Photo X
IR X
Switch X
Group 3
Occ X
Photo X
IR X
Switch X
Group 4
Occ X
Photo X
IR X
Switch X
CCI X X X X
Emergency CCI X X X X
Softswitch: 120 V~ to 277 V~,
347 V~ (347 V~ models only)
• Softswitch relay is rated for 16 A continuous use per
channel, which is the maximum continuous load for a
20 A Overcurrent Protection Device (Branch Breaker).
Patented Softswitch circuit eliminates arcing at
mechanical contacts when loads are switched.
Extends relay life to an average of 1,000,000 cycles
(on / off) for resistive, capacitive, or inductive sources.
Relay is mechanically held.
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241m 3 08.05.19
Specifications (continued)
010 V- Product Ratings
(QSN-4T16-S and QSN-4T16-S-347)
Each output sinks up to 50 mA maximum.
Each output sinks current only (load device must
provide 10 V- supply).
Provides an IEC PELV / NEC® Class 2 isolated 010 V-
output signal that conforms to IEC 60929.
Occupancy Sensors
Up to 16 occupancy sensors can be programmed to
the ESN device.
Manual Programming: up to 4 occupancy sensors wired
directly to the ESN device, up to 4 occupancy sensors
wired to a QS Sensor Module (QSM), and up to 10
wireless occupancy sensors through the same QSM; the
total programmed to the ESN device cannot exceed 16.
HHD (iPod / iPhone) Programming: up to 16 occupancy
sensors from any source (wired directly to the ESN
device, wired to any other ESN device, or wired / wireless
from any QSM on the QS link); the total programmed to
the ESN device cannot exceed 16.
Use Lutron occupancy sensors to control one or more
zones.
Use Lutron occupancy sensors in vacancy mode
to automatically turn the lights off in an area after it
becomes vacant.
Each zone can be programmed to automatically turn
the lights on when occupied and turn the lights off when
vacant.
Each wired occupancy input can power one Lutron
occupancy sensor.
Each occupied scene and unoccupied scene can be
programmed independently.
• Lutron occupancy sensors can be programmed to
automatically turn the lights on in area when it becomes
occupied and turn the lights off in an area after it
becomes vacant.
Each of the four occupancy inputs can power one Lutron
occupant sensor.
Each area’s occupied scene and unoccupied scene can
be programmed independently.
Occupancy sensor must provide a dry contact
closure or solid-state output.
Additional occupancy sensors can be used with the
ESN device. Refer to the “Programming Options and
Features” table for system rules.
seeTouch QS Controls
seeTouch QS wallstations can be configured to
control ESN unit scenes or zones.
In zone toggle mode, zone buttons can be assigned to one
or more zones on any ESN unit connected to the QS Link.
In scene mode, wallstations can be assigned to one
or more ESN units connected to the QS Link.
LED indicator displays zone or scene status.
Table 1: seeTouch QS Wallstation Configurations
# Buttons
Wallstation Function
1 2 3 5 7
Zone Toggle
Scene 1, Off
(toggle)
1, Off 1, 2
Off
1-4,
Off
N/A
IR Wallstation or Receiver Input
Four inputs for IR receivers or wallstations for control of
lighting zones can be connected directly to the ESN unit.
Use Lutron CC-1BRL-WH or CC-4BRL-WH
wallstations to control one or more zones.
Use Lutron EC-DIR-WH or EC-IR-WH ceiling mount
sensors to control one or more zones.
Up to four additional wired wallstations or IR receivers
can be assigned when associated with a QSM.
Associate additional QSMs and sensors/controls
with ESN unit when programming with an Apple iPod
touch or iPhone. Refer to "Programming Options"
section for details.
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241m 4 08.05.19
Specifications (continued)
Daylight Sensors
Lutron daylight sensors allow daylight harvesting with
programmable effect on light output.
Four daylight sensors can be connected directly to the
ESN unit.
Use Lutron EC-DIR-WH sensors to control one or more
zones.
Alternatively, up to four sensors (Lutron Wired Daylight
Sensors or Radio Powr Savr Daylight Sensors) can be
assigned when associated with a QSM.
The maximum number of Lutron daylight sensors (wired
or wireless), either wired directly to the unit or indirectly
(associated with a QSM) cannot exceed four.
Associate additional QSMs and sensors/controls with
ESN unit when programming with an Apple iPod touch
or iPhone. Refer to "Programming Options" section for
details.
Contact Closure Input (CCI)
Default behavior:
Activate scenes using momentary or maintained closures
from an external device such as a timeclock.
Start or stop Afterhours Mode using a maintained
closure.
The attached device must provide a dry contact closure
or solid-state output.
Configurable for Normally-Open (NO) or Normally-Closed
(NC) operation.
Input is miswire-protected up to 36 V-.
Emergency Contact Closure Input
By default, contact closure input from Lutron
Emergency Lighting Interface (LUT-ELI-3PH), security,
or fire alarm systems turns all zones on to full output
when emergency state is detected.
Emergency contact closure input is normally closed
(NC). The ESN unit is shipped with a jumper pre-
installed.
Response of each zone is configurable.
Attached devices, by default, will go to maximum
output and ignore control inputs.
No operations will be allowed until emergency signal
is cleared.
The attached device must provide a dry contact
closure or solid-state output.
Input is miswire-protected up to 36 V-.
Emergency CCI cannot control other ESN units.
Functionality with GRAFIK Eye QS
• ESN unit follows GRAFIK Eye QS scene activations
when associated with the GRAFIK Eye QS.
• ESN unit responds to commands initiated by the
GRAFIK Eye QS astronomic time clock when
associated with the GRAFIK Eye QS.
• ESN unit operates in afterhours mode when
associated with a GRAFIK Eye QS that is in afterhours
mode.
Functionality with QSE-IO
• ESN unit responds to scene commands initiated by
the QSE-IO, if the QSE-IO DIP switches have been set
to either scene selection mode, zone toggle mode,
partition mode, or occupancy sensor mode.
Functionality with QSE-CI-NWK-E
Integrate ESN unit with touchscreens, PCs, A / V
systems, or other digital systems and devices.
Recall scenes and set/adjust zone levels.
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241m 5 08.05.19
Specifications (continued)
IEC PELV / NEC® Class 2 Dry Contact Switches
Four inputs for IEC PELV / NEC® Class 2 dry contact
switches can be assigned to turn on and off one or
more zones.
Configure for momentary or maintained operation.
QS Link Limits
Each ESN unit can provide up to 14 Power Draw Units
(PDUs) for other QS devices. Refer to the QS Link
Power Draw Unit specification submittal (Lutron
P/N 369405) for more information concerning PDUs.
The QS Link can have up to 100 devices and 100 zones.
Each ESN unit counts as 1 device towards the
100 device limit.
Each ESN unit counts as 4 zones towards the
100 zone limit.
QSM (QS Sensor Module)
Use the QSM to integrate Radio Powr Savr
Occupancy sensors, Radio Powr Savr Daylight
sensors, and Pico Wireless Controllers to control
zones on the ESN unit.
Associate 1 QSM per ESN unit with manual
programming.
Associate multiple QSMs per ESN unit with Apple
iPod touch or iPhone programming (requires
QSE-CI-AP-D and Wi-Fi router). See "Programming
Options" for details.
Assign up to 10 Radio Powr Savr Occupancy sensors
per ESN unit via QSM.
Assign up to 4 Radio Powr Savr Daylight sensors per
ESN unit via QSM.
Assign up to 10 Pico Wireless Controllers per ESN
unit via QSM.
The sensors and Pico Wireless Controllers associated
with the QSM should be mounted within 60 ft (18 m)
line of sight, or 30 ft (9 m) through walls, of the QSM.
Wire and power up to 4 wired sensors per QSM
Daylight Sensors
Occupancy Sensors
Infrared (IR) Receivers or Wallstations
Refer to QSM Specification Submittal for more
information.
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241m 6 08.05.19
Programming Options
Manual Programming:
Use buttons on the front of the ESN unit.
Use manual programming in installations with only one ESN unit and with one QSM or fewer on the QS link.
HHD Programming
Requires ESN Programming Interface (QSE-CI-AP-D).
Requires Apple iPod touch or iPhone mobile digital device.
Use the intuitive programming application for the Apple iPod touch or iPhone to program systems with multiple
ESN units and QSMs in the QS link.
Wireless router only required for programming with an Apple iPod touch or iPhone.
Wireless router may be removed for normal operation.
Ethernet connection may be made via an ESN Programming Interface (QSE-CI-AP-D) or an ESN QS unit with
integral Ethernet jack.
Lutron recommends that an ESN Programming Interface (or ESN QS unit with Ethernet jack) be wired to an
Ethernet jack in the space for ease of access and proximity to power for the wireless router.
Works with any standard wireless router that supports multicast packets.
Apple iPod touch or iPhone can program all ESN QS units connected to an ESN Programming Interface via the QS
Link (except when part of a Quantum system).
ESN app is required and is available from the Apple App Store Store online marketplace.
QS Link
QSM QSM QSM
ESN Unit
Apple
iPod touch or
iPhone mobile
digital device
Wireless
Router
(by others)
ESN Programming
Interface
QSE-CI-AP-D
Dedicated Ethernet
Connection for ESN
units
1,2
ESN Unit ESN Unit
QS Link
1 Standard CAT5/CAT5E cable: Total length not to exceed 300 ft (100 m)
2 Note: ESN units are not designed to exist on an open network.
Connection to an open network could result in reduced performance and
Ethernet connectivity issues.
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241m 7 08.05.19
Programming Options and Features
Manual Programming
HHD Programming:
Requires ESN Programming Interface
QSE-CI-AP-D
Requires Apple iPod touch or iPhone mobile
digital device
ESN units connected to 1 QS
Link
Not more than 1 Multiple—100 QS devices and 100 zone limits apply
QSMs connected to 1 QS link Not more than 1 Multiple—100 QS devices limit applies
Wired Occupancy Sensors
System Limits 4 connected directly to ESN unit
Up to 4 wired to QSM
Up to 100 total occupancy sensors per QS link
(wired + wireless)
Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same
QS link
Occupancy Dependency
Supported
No Yes
Wireless Occupancy Sensors
System Limits Associate 10 occupancy sensors to QSM
to control zones on the ESN unit
Up to 100 total occupancy sensors per QS link
(wired + wireless)
Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same
QS link
Occupancy Dependency
Supported
No Yes
Wired Daylight Sensors
System Limits Maximum of 1 daylight sensor per zone
4 connect directly to the ESN unit
Additional daylight sensors can connect to
the QSM
Maximum of 2 daylight sensors per zone
Up to 100 total daylight sensors per QS link
(wired + wireless)
Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same
QS link
Disable daylighting in Scenes No Yes
Wireless Daylight Sensors
System Limits Maximum of 1 daylight sensor per zone
Associate wireless daylight sensors to the
QSM
Maximum of 2 daylight sensors per zone
Associate up to 10 wireless daylight sensors per QSM
Up to 100 total daylight sensors per QS link
(wired + wireless)
Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same
QS link
Disable daylighting in Scenes No Yes
7
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241m 8 08.05.19
Programming Options and Features (continued)
Manual Programming
HHD Programming:
Requires ESN Programming Interface
QSE-CI-AP-D
Requires Apple iPod touch or iPhone mobile
digital device
Pico Wireless Controllers
System Limits Associate 10 Pico wireless controllers to
QSM to control zones on the ESN unit
Up to 100 total controls per QS link (wired wallstations,
Pico wireless controllers, IR receivers)
Can be assigned to… Any zone on the local ESN unit Zones on ESN unit or share to other ESN units on
same QS link
IR Receivers and Wallstations
System Limits 4 connect directly to the ESN unit
Up to 4 wired to the QSM
Up to 100 total controls per QS link (wired wallstations,
Pico wireless controllers, IR receivers)
Can be assigned to… Any zone on the local ESN unit Zones on ESN unit or share to other ESN units on
same QS link
NEC® dry contact Switches Inputs
Can be assigned to… Any zone(s) on the connected ESN Any zone(s) on the connected ESN
Contact Closure Input
Can be assigned to… Any zone(s) on the ESN unit Any or all local ESN unit zones
Functions • Sweep to off
• Enable/disable afterhours
Turn on to preset and turn off
• Sweep to off
• Enable/disable afterhours
Turn on to preset and turn off
Afterhours Conguration afterhours timeout – 15 minutes
blink-warn timeout – 5 minutes
Afterhours timeout and blink-warn
timeouts are congurable
Emergency Contact Closure Input
Can be assigned to… Any zone(s) on the ESN unit Any or all local ESN zones
Emergency Light level Congurable Congurable
8
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241m 9 08.05.19
Programming Options and Features (continued)
Manual Programming
HHD Programming:
Requires ESN Programming Interface
QSE-CI-AP-D
Requires Apple iPod touch or iPhone mobile
digital device
seeTouch QS wallstations
Scene Keypads assigned to… Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link
Scene + off keypads assigned
to…
Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link
Zone toggle keypad buttons
assigned to…
Any zone(s) on the ESN unit Any zone(s) on on or more ESN units on the link
Change Keypad to Scene or
Zone
Yes Yes
Changing keypads to shade,
panic, ne tune
No Yes
Zone Configuration Parameters
Load type 0-10, 10-0, or switched 0-10, 10-0, or switched
High-end trim Adjustable Adjustable
Low-end trim Adjustable Adjustable
Absolute minimum level Adjustable Adjustable
Scenes
Available scenes Scenes 1-16 Scenes 1-16
GRAFIK Eye QS N/A Share scenes, timeclock events, or afterhours events
to ESN units on QS Link
QSE-IO Scene, zone toggle, occupancy Scene, zone toggle, occupancy
QSE-CI-NWK-E Yes Yes
9
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241m 10 08.05.19
Mechanical Dimensions
All dimensions shown as in (mm)
11.25
(285.75)
0.20 (5.16)
diameter
1.00
(25.40)
1.41
(35.81)
1.80
(45.72)
1.03
(26.04)
0.88
(22.23)
9.25
(234.95)
7.50
(190.50)
3.14
(79.71)
13.25
(336.55)
Do not
use side
knockouts
Line Voltage Shield
10
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241m 11 08.05.19
Wiring: QS Link
Only terminals 1, 3, and 4 connected
between devices that supply PDUs
Terminal 2 NEVER connected
between devices that supply PDUs
Terminal 2 (+24 V)
NEVER connected*
Devices that
supply PDUs
Devices that
consume PDUs
COM
+24 V
MUX
MUX
COM
MUX
MUX
ESN QS unit
ESN QS unit
QS
Input/
Output
Interface
Wired
QS
Keypad
QSM
QSMQSM
Wired
QS
Keypad
Wired
QS
Keypad
Wired
QS
Keypad
QS
Input/
Output
Interface
QS
Link
power
supply**
QS Link;
all 4 terminals
QS Link;
no terminal 2
QS Link;
no terminal 2
QS Link;
all 4 terminals
QS Link;
all 4 terminals
Terminal 2 (+24 V)
NEVER connected*
Terminal 2 (+24 V)
NEVER connected*
All 4 terminals connected to QS link
devices that consume PDUs
QS Link Wiring Rules
* Terminal 2 (+24 V) should NEVER be connected between devices that supply PDUs.
** For QS Link power supply wiring connection details, refer to the installation instructions
for the specific power supply model being used.
11
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241m 12 08.05.19
Wiring: IEC PELV / NECR Class 2 Inputs
Occupancy
Sensor
Daylight/
IR Sensor*
IR
Transmitter
IR
Transmitter
Note: Maximum wire
run length to each
input not to exceed
150 ft (46 m).
IR Receiver
or Wired
Wallstation*
IEC PELV / NEC®
Class 2
Dry Contact
Switch
Red
Black
Yellow
Blue/Gray**
Black
Red
20 V – 20 V-
Occ – Occupancy Sensor
Daylight – Daylight Sensor
IR – IR Receiver*
Switch – IEC PELV / NEC® Class 2
Com – Common
LUTRON
Input Group Wiring:
20AWG to 12AWG
(0.5mm
2
to 4.0mm
2
)
Strip length: 1/4in (6mm)
Torque: 5 in
lb (0.5 N
m)
NOTE: There are four input groups. Each group has the
same inputs as shown in the diagram below.
* Note: Only one IR device may be connected per input. If
the IR signal from a daylight sensor is connected, a wall
control may not be connected to the same input, and
vice-versa.
** Connect the gray wire on -R model occupancy sensors.
Group 1 shown Group 2 shown
Red
20V
Black COM
White
IR
12
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241m 13 08.05.19
Wiring: Contact Closure Inputs (CCI and Emerg)
Com – Common Emerg – Emergency
CCI – Contact Closure Input
Com – Common
Contact Closure Wiring:
20AWG to 12AWG
(0.5mm
2
to 4.0mm
2
)
Strip length: 1/4in (6mm)
Torque: 5 in
lb (0.5 N
m)
13
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241m 14 08.05.19
Wiring Diagram: Example A – 4 circuits, multiple feeds
Zone Switching:
120–277 V~;
347 V~*
0–10 V- Zones:
(QSN-4T16-S and
QSN-4T16-S-347)
Switched Hot (1B)
Hot Feed (1A)
Hot Feed (2A)
Hot Feed (3A)
Hot Feed (4A)
Switched Hot (2B)
Switched Hot (3B)
Switched Hot (4B)
Ground
Lug
Neutral Wires
Distribution
Panel
LOAD
LOAD
LOAD
LOAD
Load Wiring:
Two (2) 14AWG to
12AWG (2.5mm
2
to 4.0mm
2
)
Strip length: 3/8in
(8.5mm)
Torque: 7 in-lb
(0.79 N
m)
0–10 V- Wiring
(QSN-4T16-S and
QSN-4T16-S-347)
Hot
Hot
Hot
Hot
Hot
Neutral
Neutral
Neutral
Neutral
Neutral
Neutral
Ground
Hot
* For 347 V~
models only.
0-10 V- Wiring (QSN-4T16-S and QSN-4T16-S-347)
20AWG to 12AWG (0.5mm
2
to 4.0mm
2
)
Strip length: 1/4in (6mm)
Torque: 5 in
-
lb (0.5 N
m)
Connect only IEC PELV / NEC® Class 2 circuits or connect only
non-IEC PELV / NEC® Class 2 circuits to 0-10 V zones 1-4.
0-10 V- zones 1-4 are not isolated from each other.
Negative (–) terminals are not internally connected to each
other - both positive (+) and negative (–) connections must
be made.
Follow all national and local codes for separation
requirements.
14
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241m 15 08.05.19
Wiring Diagram: Example B – 4 circuits, single feed
0-10 V Wiring (QSN-4T16-S and QSN-4T16-S-347)
20AWG to 12AWG (0.5mm
2
to 4.0mm
2
)
Strip length: 1/4in (6mm)
Torque: 5 in
-
lb (0.5 N
m)
Connect only IEC PELV / NEC® Class 2 circuits or
connect only non-IEC PELV / NEC® Class 2 circuits to
0-10 V- zones 1-4.
0-10 V- zones 1-4 are not isolated from each other.
Negative (–) terminals are not internally connected
to each other - both positive (+) and negative (–)
connections must be made.
Follow all national and local codes for separation
requirements.
Zone Switching:
120-277 V~;
347 V~*
0-10 V- Zones:
(QSN-4T16-S and
QSN-4T16-S-347)
Hot
Neutral
Ground
Hot
Neutral
Ground
Ground
Lug
“A” Terminals Jumpered
Neutral Wires
Distribution
Panel A
Distribution
Panel B
LOAD
LOAD
LOAD
LOAD
Load Wiring:
Two (2) 14AWG to
12AWG (2.5mm
2
to 4.0mm
2
)
Strip length: 3/8in
(8.5mm)
Torque: 7 in-lb
(0.79 N
m)
0-10 V- Wiring
(QSN-4T16-S and
QSN-4T16-S-347)
Switched Hot (1B)
Hot Feed (1A)
Switched Hot (2B)
Switched Hot (3B)
Switched Hot (4B)
* For 347 V~
models only.
)Lutron, Lutron, Softswitch, seeTouch, Pico,
Quantum, Energi Savr Node, Radio Powr Savr, and
GRAFIK Eye are trademarks or registered trademarks
of Lutron Electronics Co., Inc. in the US and/or other
countries.