SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LED Dimming Driver EcoSystem LED Driver Architectural Dimming
369341d 2 05.08.19
Specifications
Performance
• Dimming Range: 100% to 1%
• Operating Voltage: 220–240 V ~ 50/60 Hz
• Patented thermal foldback protection
• LEDs turn on to any dimmed level without going
to full brightness
• Non-volatile memory restores all driver settings after
power failure
• Power Factor: λ >0,90 at full output for loads greater
than 15 W
• Total Harmonic Distortion (THD): <20% for loads
greater than 10 W
• Inrush Current: <2 A
• Inrush Current Limiting Circuitry: eliminates circuit
breaker tripping, switch arcing and relay failure
• Open circuit protected
• Short circuit protected
• Lifetime: 50 000 hours @ t
c
= 75 °C
• Efficiency: > 80% at max power (25 W)
• Turn-on time: ≤ 1 second
Environmental
• Sound Rating: Inaudible in a 27 dB ambient
• Relative Humidity: maximum 90% non-condensing
• Minimum Operating Ambient Temperature: t
a
= 0 °C
• Maximum Calibration Point: t
c
= 75 °C
• Maximum Operating Ambient Temperature: t
a
= 40 °C
Consult Lutron for derating information
Standards
• CE and ENEC
– Safety: IEC/EN 61347-2-13
– Emissions: CISPR15/EN55015,
IEC 61000-3-2, -3-3
– Immunity: IEC/EN 61547,
IEC/EN 61000-4-2, -4-3, -4-4, -4-6, -4-11
– Performance: IEC/EN 62384
• RoHS 2006 Compliant
• IEC 60529, IP20 Rating
• Lutron Quality Systems registered to ISO9001.2015
Driver Wiring & Mounting
• Wiring Means: Daisy chain capable terminals
for input
– Input Screw Terminals:
· 1 or 2 cables, 2 core 0,5mm
2
to 2,5mm
2
· Daisy Chain Maximum: 8units
· Recommended Wire Types: H03VV-F,
H03VVH2-F, H05VV-F, and H05VVH2-F
– EcoSystem Terminals:
· 1 or 2 cables, 2 core 0,5mm
2
to 1,5mm
2
(Solid copper wire only)
· Recommended Wire Types: H03VV-U,
H03VVH2-U, H05VV-U, and H05VVH2-U
– Output Screw Terminals:
· 1 cable, 2 core 0,5mm
2
to 2,5mm
2
· Recommended Wire Types: H03VV-F,
H03VVH2-F, H05VV-F, and H05VVH2-F
Note: Ground termination not provided. Terminate
ground in compliance with local electric codes