SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247d 4 07.07.14
Wiring Diagrams
• Each terminal can accept up to two 12 AWG
(2.5 mm
2
) conductors.
• L1 / H1 is the Line / Hot feed to power the load.
• L2 / H2 (on the control circuit terminals) supplies
operating power for the Ten Volt Interface.
• Wiring Diagrams A, C, E, G, I, and M show a
GRX-TVI wired from one distribution panel. If the
power requirement of the complete system is less
than an MCB / circuit breaker rating and L1 / H1
and L2 / H2 are both coming from the same phase,
one feed can be jumpered inside the enclosure (as
shown).
• Wiring Diagrams B, D, F, H, J, L, and N show a
GRX-TVI wired from two separate distribution panels
that may be different phases or voltages.
• Wiring Diagram O shows a GRX-TVI wired from one
distribution panel with 2 separate feeds.
• Make sure L2 / H2 and DL2 / DH2 (Dimmed
Line / Dimmed Hot) are fed from the same breaker
that powers the control unit.
• Run separate neutrals for load circuit and control
circuit- no common neutrals.
• NEC® Class 2 / IEC PELV, 0—10 V- wiring from a
ballast / driver to the GRX-TVI must be separated
from the power wiring. Enter the Class 2 / PELV
wires through the knockout adjacent to the
0—10 V- terminal blocks. The barrier ensures
separation and is flexible to allow access to the
terminals. The barrier must be in place when
installation is complete.
Wiring Diagram A: HomeWorks® Wallbox Power Module / GRAFIK Eye® Control Unit
— 1 Distribution Panel / 1 Feed
V-
100-
127 V~
220-
240 V~
L
2
/H
2
100-277 V~
LUTRON
LUTRON
GRX-TVI
HomeWorksR Wallbox
Power Module
1
(HWI-WPM-6D)
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage
in the range of 100—277 V~. Refer to
the Note on the first page of the
GRX-TVI Specification Submittal.
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
OR
Dimmed Line /
Dimmed Hot, DL / DH
Switched Line / Hot
Line / Hot
Line / Hot
0—10 V-
Ballast / Driver
1
0—10 V-
Ballast / Driver
1
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
LutronR is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
Neutral
Distribution
Panel
Neutral
Earth / Ground
Note: Ballast / driver must
provide a 0—10 V- source
only!
L1 / H1 is the Line / Hot feed that powers
the Switched Line / Hot output to the
load. Shown in picture as the same
voltage as L2 / H2.
Neutral
Line / Mains Voltage:
100—240 V~
GRAFIK EyeR
Control Unit
1
1
Control units and ballasts / drivers must be rated for the specific Line / Mains
voltage utilized.