DIP Switches
• Set DIP switches 1-4 to give the Wallstation a
unique system address from 1 to 16.
• Set additional DIP switches (if any) to specify
function as shown on the first page of the
Wallstation’s Specification Submittal.
• DIP switch 10 controls the button backlight.
Low-voltage Class 2 (PELV) Wiring
• Use low-voltage Class 2 (PELV) wiring to daisy-chain
Wallstations to Control Units and other components.
• Make connections inside the wallbox or in a
switch/junction box with a maximum wire length of 8
feet (2.5m) from the link to the Wallstation.
When used with GRAFIK Eye 3000 Control Units
• Two #18 AWG (1.0mm
2
) conductors for common
(terminal 1) and 12VDC (terminal 2). Ensure that the
terminal 2 connection is wired correctly. Refer to
GRAFIK Eye 3000 Series Specification Submittal.
• One shielded, twisted pair #18 AWG (1.0mm
2
) for
data link (terminals 3 and 4).
When used with GRAFIK Eye 4000 Control Units
• Two #12 AWG (2.5mm
2
) conductors for common
(terminal 1) and 24VFW (terminal 2). These won’t fit
in terminals. Connect as shown.
• One shielded, twisted pair #18 AWG (1.0mm
2
) for
data link (terminals 3 and 4).
• Connect Drain/Shield as shown. Do not connect to
Ground (Earth) or Wallstation. Connect the bare drain
wires and cut off the outside shield.
Note: Use appropriate wire connecting devices as
specified by local codes.