Level One Planning Document
May 2014
Laramie County Community College
Physical Education Building Renovation
POTENTIAL RENOVATION DESIGN
DESCRIPTION 04
Project Description
Project Need and Opportunities
BACKGROUND 05
Ownership
Permits
Environmental Considerations
Utilities
SPACE & DESIGN 06
Quantitative Requirements
Qualitative Requirements
Current Function
Proposed Renovation
PUBLIC 11
Description of Public Forum
Public Response
SPACE USE CODES 12
Dispersion of Space Use Codes
Analysis of Space Use Code Change
APPENDICES
-Space Use Code Analysis
-Open House Sign in Sheet
-DEQ Notication of Demolition and Renovation
-Laramie County Commercial Building Permit Application
TABLE OF CONTENTS
LCCC Physical Education Building Renovation Level One Study Page 4
P D
This project includes the partial
renovation of the LCCC Physical
Education Building (PEB). The project
would make better use of existing space
within the building, and enhance the
user experience.
The major component of the project
would be the transition of a portion of
the existing large multi purpose room
into spaces accommodating cardio
equipment, weights, and a new second
oor of oices.
Other work will consist primarily
of replacing nishes and minor
rearrangement of existing spaces.
The work will be contained entirely
within the existing structure, however
it is proposed that to increase daylight
access, portions of the west wall be
removed and replaced with glazing.
Site
The PEB is located at the north west
corner of the LCCC campus, and the
majority of the proposed improvements
are located in the north west corner of
the PEB. The building is a prominent
feature when entering campus from the
west. Parking is provided directly to
the east of the building, and various
pedestrian approaches are present.
P N 
O
Currently deciencies and unfullled
potential exist in the PEB. The
following items are of particular
concern, and present signicant
opportunity for improving the
functionality and experience of this
building.
Cardio
Currently in the PEB, cardio
equipment shares space with a studio.
The space is undersized, under
utilized, uninspiring, and separation
of the spaces would benet both user
groups. A new cardio space where all
equipment and weights are collocated
could provide a more comfortable
eicient, and inviting space, more
closely aligned with facilities at other
public and collegiate institutions.
Conferencing
The large multi purpose room in the
facility is currently utilized for large
gatherings and functions.
As modications are made to this large
space to accommodate a new cardio
space, features could be incorporated
to maximize the eectiveness of
the larger multi purpose space as
a conference center. Features could
include: upgrades to and integration of
audio visual equipment in a dedicated
PROJECT LOCATION (SHADED IN YELLOW)
LCCC S
C
Pete Cautilli
Director of Athletics and Campus
Recreation
Tim Macnamara
Director, Physical Plant
Cynthia Henning
Instructor, Program Director for
Exercise Science
Don Erickson
LCCC Board of Trustees
Tucker Stover
Director, Corporate Development &
Major Gifts
Lucy McVeigh
Instructor
Brooke Schaer
Community Relations
Scott Noble
Director of Athletic, South High
School
Jessie Johnson
Student
C
01 Physical Education Building
(PEB)
02 Residence Halls
03 Cafeteria
04 Parking for PEB
01
02
03
04
north
LCCC Physical Education Building Renovation Level One Study Page 5
presentation wall, chair and table
storage, and a new wall designed as a
backdrop for presentations.
Locker Rooms
Locker rooms are currently shared
between, public, student body, and
athletics.
Providing dedicated athletics locker
rooms will provide a more collegiate
atmosphere for users of both the
athletic and recreational locker rooms.
Team and Class Rooms
The building currently has no space
dedicated as team rooms for athletics,
and general classrooms are limited.
Athletic team rooms could be included
to provide this space, as well as
potentially functioning as classrooms
when needed for P.E. classes.
Offices
The building does not currently oer
adequate oice space for athletics and
P.E. faculty and sta.
A second oor addition in the remodel
of the multi purpose room could
provide space for athletic oices.
Freeing rst oor oice for other uses.
Studio
The current studio space is shared with
cardio equipment, and is more suited
for dance classes than yoga or other
small group activities.
There is space available above the
current mat room where a new studio
could be built. This space is above
adjacent roofs, and would therefore
provide the opportunity for day
lighting.
O
The land on which the Physical
Education Building sits was donated
by the Arp-Hammond family when the
college was founded.
E
C
The proposed project is a renovation
of an existing building, and therefore
poses minimal environmental impacts.
The proposed changes to the building
will not alter site drainage, impact
the building site, or introduce
hazardous materials into the building.
Asbestos
A primary concern in renovation
projects is the presence of asbestos,
lead paint, or other harmful or
hazardous materials in the existing
construction. A campus wide survey
and testing was performed in 1983,
however the results of the survey
are no longer available. Therefore
it may be prudent to engage an
environmental consultant to inspect
the areas identied for renovation,
and include any required abatement
in the project, or perform the
abatement prior to the execution of
this project.
Other Regulated Materials
Any investigation eorts undertaken
for asbestos should also consider
other regulated materials such
as lead, pcbs, and others as
recommended by an environmental
consultant.
U
Existing building services include:
domestic water, re suppression water,
sanitary sewer, storm sewer, hydronic
heating water (there is currently no
cooling in the building), gas, and
electricity.
Electrical
The electrical service is reportedly at
maximum capacity and this project may
require a service upgrade to the building
or portions of the building.
HVAC
The capacity of the existing heating
systems will need to be reviewed by an
engineer for adequacy and expandability
if required.
Water
Currently only one 4” water line serves
the building (for domestic and re
suppression). A second line will be
required for re suppression water, and
the sizing will need to be reviewed for
adequacy.
Fire Suppression & Detection
The building is currently supplied with
an automatic re sprinkler system in the
large Multi Purpose Room only. Riser
equipment is located in the storage room
adjacent to the multi purpose room.
Service sizing is currently 4”, and will
need to be evaluated for the renovation.
The building is equipped throughout with
a re alarm system.
P
The following permits will be
required (see appendix for copies of the
forms):
Laramie County
Building Permit and Plan Review
Cost: $9,500.00 (est.)
Contact: Rauchelle Meredith
307-633-4512
City of Cheyenne
not required
State of Wyoming Fire Marshal
not required
Additionally the project will require
coordination with the
Wyoming Department of
Environmental Quality
Notication of Demolition and Renovation
Cost: No Cost
Contact: Linda Dewitt
307-777-7394
Information regarding the results of asbestos
and other hazardous materials testing will be
required for these forms.
LCCC Physical Education Building Renovation Level One Study Page 6
space name qty. area each total area notes
Cardio/Aerobic Equipment 1 1,500 1,500 Daylight and views, volume
Weight Room 1 1,500 1,500 Relocation of current weight room, area based on current.
Climbing Wall 1 250 250 Existing to remain, include area for belay and gathering.
Misc. Rec 1 350 350 Misc. activities related to cardio and weights
Lockers/cubbies 1 100 100
A/V/ Chair storage 1 300 300 For large multi prupose room
Men's Soccer Locker Room 1 500 500 Includes showers and toilet(s)
Men's Basket Ball Locker Room 1 500 500 Includes toilets, but not showers.
Women's Soccer Locker Rm 1 350 350 Could be adjacent to exiting women's locker to use existing showes, etc.
Women's Volleyball Locker Rm 1 350 350 Could be adjacent to exiting women's locker to use existing showes, etc.
P.E. Classroom + Team Room, Lg. 1 800 800 Tiered Seating
P.E. Classroom + Team Room, Sm. 1 500 500
Lounge 1 500 500 Combine with circulation, include snack/juice bar.
Concesssions + Ticketing 1 200 200
Information + Check-In 1 100 100
Studio 1 300 300 Yoga, Pilates, etc.
Office, Athletic Director 1 250 250
Office AD Assistant 1 100 100
Office, Coach 6 150 900
Office, Asst. Coach 6 100 600
Athlete Study 1 200 200
Coach's Conference 1 250 250
Break/Kitchenette 1 100 100
Storage 1 100 100
Athletics Entry/Waiting 1 100 100
10,700
Gross Area, assuming an efficiency of
75%
14,267
Total Net Area
A S
Rather than a proposal for new
construction, this project proposes to
remodel under-utilized portions of an
existing building. It could be argued
that this is the alternate space option.
P S
D
While portions of the remodel work
relocated existing space into a more
functional arrangement, other portions
will include introducing needed
spaces into the building which are
not currently provided. These spaces
include: athletic locker rooms, coach
oices, athletic student study, as
well as concessions and ticketing for
basketball games.
Q D R
To achieve the intent of this project and remedy current facility issues, the spatial needs of the building must be identied.
The spaces described below have been established as those required to meet the needs of the College and accommodate
current and expected functions.
S L
In addition to remodeling existing
space, the proposed plan also capitalizes
on spaces within the current building
which are tall enough to accommodate
a second level. In these spaces the
addition of a second oor within the
current building shell provides additional
opportunity for space.
Accessibility to Second Levels
Depending on the function of spaces
located on the second level handicapped
accessibility may be a necessary
consideration. If a person with mobility
impairment would be precluded from
participating in activities on a second
level, an elevator may be required.
S P
S P
The space program included below
outlines the spaces required for
this project. This table is dierent
from those typically developed for
architectural projects in that it has
been somewhat reverse engineered.
Many of the spaces included are
simply being moved from one location
to another, and with the exception
of spaces located on the new second
oors, these functions must t within
the current area of the building.
Additionally, demolition of interior
walls is being mostly avoided, so many
spaces are simply the same square
footage as they have always been, they
will however be re-nished to suit new
functions.
note: see pages 12 through 14 for an
analysis of the changes in Space Use
Codes for the full Physical Education
Building.
LCCC Physical Education Building Renovation Level One Study Page 7
C
A
Goal Description
The current facility does not poses
the inviting character that many
modern recreational centers on college
campuses do. In order to better
compete this facility should feel more
like a collegiate rec center.
Strategies
Upgrading nishes and instilling a
focus on life long wellness along with
creating a more unied and active
environment can help to achieve this
goal. Providing a stronger core and
incorporating usable space within
circulation space can help to activate
the building. Where possible providing
views into adjacent spaces can also
unify and activate circulation spaces
and thereby the building as a whole.
D & V
Goal Description
Daylight and view to the outdoors
signicantly improve the interior
environment of a building, however
almost all spaces in the current
building are dark and do not provide
views to the exterior. Introducing these
features into the building will make
spaces more inviting and enhance the
user experience.
Strategies
The west wall of the multi purpose
room, which is proposed to be
remodeled as cardio space, is built of
pre-cast double tee units. Removing
some of these units and replacing with
curtain wall glazing would dramatically
change the interior environment by
ooding the space with daylight and
providing expansive views to the
adjacent green space.
D D
Q D G & S
The previous page outlines the quantitative spatial needs of the project. As design progresses and the functional areas are
placed within the existing building shell, thought should be given to how these spaces will be rendered and the eect that
will have on the function and experience of the spaces. Some of these primary qualitative goals are listed below along with
possible strategies for achieving these goals.
Remodeling located in spaces
above adjacent roofs may provide
opportunity to cut openings in the
existing exterior walls and introduce
daylight and views into those spaces.
L W
Goal Description
An important component of this
facility is to provide students to
develop habits that support lifelong
wellness. The design of the remodel
should bear this in mind and consider
ways that the building could reinforce
this idea.
Organization, above
This diagram shows the general
idea that spaces should be
organized around the check-in
desk, and certain functions could
exist in some shared or connected
way to the check-in area and
circulation.
Circulation, right
One of the best ways to improve
the experience of a building is to
activate the circulation space by
including related functions within
the space, and visually connecting
it to adjacent functions and/or
the outdoors.
Strategies
Including nutritional food options, a
variety of exercise, social, and educational
opportunities in a bright, active, and
organized environment will provide
students with a place on campus
dedicated to the maintenance of their
wholistic physical wellness.
The interior design of this facility will
be important in that the space must
be inviting, and must attract students
and be a place they want to spend time.
The use of materials such as glass and
wood where practical as opposed to solid
masonry and wall board could make
strides in achieving this goal.
LCCC Physical Education Building Renovation Level One Study Page 8
E
The plan below on this page indicates
in gray the portion of the existing
building which is proposed for
remodeling. The current function of
those spaces include:
• The current weight room.
• Storage
• One of four indoor tennis courts.
• Existing mat classroom, currently
used for studio style classes.
• Original building entry, which is
currently seldom used.
R
The plan on the follow page indicates
the proposed changes to the building.
They include:
• Omitting one of four tennis courts
to accommodate aerobic equipment,
weights, climbing wall (existing to
remain), and second oor athletics
oices.
• Consolidate and relocate storage,
and replace with athletic locker
rooms.
• Relocate existing weight room (see
rst bullet above) and replace with
team room / P.E. classroom.
• Replace existing mat classroom with
new basketball locker room with
pilates type studio above.
• Finish upgrade and improved access
control and waynding in main
entry corridor.
• Areas in grey on the plan below are
not aected by this project.
• Re-develop the original building
entry.
• Expand training areas, including a
new private exam room.
• Incorporation of lounge/food
service function into circulation
areas to activate the building.
• Addition of a second level spaces
for athletic coaches’ oices and a
studio space. (see page 10 for plan)
E P
Multi-Purpose Room
Proposed Cardio Area
Climbing Wall
Fire Riser
Pool
Basketball
Court
Mat
Room
Current
Dance
&
Cardio
Storage
Weight
Room
Original
Main Entry
Current
Main Entry
north
LCCC Physical Education Building Renovation Level One Study Page 9
UP
UP
R P, 1 F
Multi-Purpose Room
Proposed Cardio/Weights Area
Pool
Concessions
Basketball
Lockers (Studio above)
Basketball
Court
Trainer’s oice, exam, & storage
Re-Establish main entry,
and activate circulation/lounge
Expanded
Training
Room
Team
Lockr.
Lockr.
Lockr.
Solid wall replaced with glazing.
Dance
north
I D
This image shows a possible
renovation option. In this view
large portions of the existing
exterior wall have been removed
and replaced with glazing, allowing
ample daylighting and views of the
adjacent elds.
Light colors on walls and ceilings
keep the space bright, and the use
of natural materials such as wood,
bring a warmth into the building
that is currently absent.
LCCC Physical Education Building Renovation Level One Study Page 10
DN
DN
R P, 2 F
Athletic Coaches
Studio
2 F
It is proposed that a second level be
added to the building in select areas.
The multi-purpose room as well as
the mat room have suicient roof
height to accommodate a second level.
This would provide additional usable
square foot age without expanding the
footprint of the building.
As previously mentioned access may
be one of the primary considerations
regarding a second level. Especially for
the athletic coaches’ area an elevator
may be required.
The second oor plan below indicates
the arrangement of new second oor
spaces.
north
LCCC Physical Education Building Renovation Level One Study Page 11
P F
An open house style forum was held
on April 16, 2014. Two session were
provided, one over the lunch hour, and
one from 5:00 until 6:00 in the evening.
I  P H
P I
The public forum provided an opportunity
for many valuable discussions with
students, faculty, sta, and the general
public. Some of the repeated concerns are
listed below:
• While space may be limited for locker rooms, as much should be done as possible to create collegiate level
athletic locker rooms with regard especially to aesthetic and function.
• Evaluate sizing of weight room. Consider eicient layout options as well as better dene the balance between
cardio equipment, circuit equipment, and fee weights.
• Critically evaluate the climbing wall. There were widely varying opinions regarding the wall. Some suggestions
urge the removal of the wall, while others urge the development of the wall into a more accessible and attractive
element.
• Consideration the possibility of additional sports in the future, such as women’s basketball, and ensure the ability
to provide the required facilities for those sports (such as locker rooms).
• Consider connection from cardio/weight area directly into the multipurpose room.
• Evaluate the location of locker rooms with consideration for their proximity to the teams typical practice and
game spaces.
• Attempt to provide storage for volleyball equipment directly into the gym.
• Consider additional pool entry at the north wall of the pool area.
• Consider the ramications of reducing storage and develop a plan for consolidation and relocation.
• Consider locating the training oice and exam room within the training room to allow monitoring of the space.
• Provide a door from the main corridor into the training room.
• Consider a second whirlpool to allow simultaneous hot and cold pools.
• Consider exibility of team room.
• Evaluate sizing of one large team room vs. two or more smaller rooms to minimize scheduling conicts.
• Consider the assembly uses of the MPR, and provide adequate accommodations.
LCCC Physical Education Building Renovation Level One Study Page 12
C  S U C D
The tables on these pages reect the dispersion of Space Use Codes (as dened in the Institute of Educational Sciences’
Postsecondary Educational Facilities Inventory and Classication Manual, 2006) in the existing building as well as the
proposed addition. It must be noted that there are minor discrepancies between past documentation of room sizes and
those ascertained from the current drawings. This is likely attributed to the common variations in room size calculations.
Note: These table are also provided in the appendix with larger print.
The pie charts below provide a feel for the dominate Space Use Codes, as well as demonstrate the increased variety in the
building after the proposed renovation. This variety reinforces the project goal to provide renovated space for as many
dierent users as possible.
EXISTING BUILDING BY CATEGORY RENOVATION FIRST FLOOR
RENOVATION FULL BUILDING
110 Classroom
115 Classroom Service
310 Office
315 Office Service
350 Conference
355 Conference Service
410 Study Room
520 Athletics/Physical Education
660 Merchandising
650 Lounge
WWW Circulation
XXX Building Service
YYY Mechanical
110 Classroom
115 Classroom Service
310 Office
315 Office Service
350 Conference
355 Conference Service
410 Study Room
520 Athletics/Physical Education
525 Athletics/Physical Education Service
660 Merchandising
650 Lounge
WWW Circulation
XXX Building Service
YYY Mechanical
110 Classroom
115 Classroom Service
310 Office
315 Office Service
350 Conference
355 Conference Service
410 Study Room
520 Athletics/Physical Education
525 Athletics/Physical Education Service
660 Merchandising
650 Lounge
WWW Circulation
XXX Building Service
YYY Mechanical
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
1 HW Hallways 6939
1 103 Multi Purpose Room 1500 22515
1 104 Fan Room 100
1 105 Fan Room 100
1 106 Fan Room 100
1 107 Weight Room 1519
1 108 PE Storage 1793
1 110 Custodial 81
1 112 Lockers, Women's Coach 155
1 114 PE Storage/Electrical Service 185
1 114A Office 1 80
1 114B Office 1 80
1 114C Office 1 80
1 115 Locker Room/Restroom, Women's 690
1 116 Restroom, Women's 219
1 117 Shower, Women's 386
1 118 Training Room 544
1 120 Locker Room/Restroom, Men's 736
1 121 Restroom, Men's 72
1 122 Shower, Men's 381
1 123 Lockers, Men's Coach 155
1 127 Mechanical Room 739
1 128 Mechanical Room 158
1 129 Office 1 120
1 130 Office 2 124
1 133 Aerobic Center 49 2850
1 133A Storage, Aerobic Center 750
1 134 Office 1 132
1 139 Racquetball Court 4 842
1 140 Racquetball Court 4 846
1 141 Racquetball Court 4 846
1 142 Office 163
1 143 Classroom 20 505
1 505 Gym 654 9657
1 506 Storage, Athletic 306
1 507 Storage, Athletic 64
1 508 Office 1 107
1 509 Electrical Room 216
1 510 Mat Room 10 885
1 511 Pool 6956
1 512 Shower, Men's 203
1 513 Locker Room, Men's 511
1 516 Locker Room, Women's 409
1 517 Shower, Women's 184
1 519 Restroom, Women's 100
1 521 Restroom, Men's 108
1 522 Custodial 32
1 523 Mechanical Room 201
1 524 Office 1 150
1 525 Office 106
1 526 Mechanical Room 268
1 527 Storage, Acid Room 14
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
505 0 1142 0 0 0 0 46916 7965 0 0 6939 113 1882
% of Total Building Area 0.77% 0.00% 1.74% 0.00% 0.00% 0.00% 0.00% 71.67% 12.17% 0.00% 0.00% 10.60% 0.17% 2.87%
Total Building Area 65462.00
Total Sta. 2254.00
Laramie County Community College
Area by Category Code
Totals by Category Code
Room Name/Description
Room #
Floor
MULTIPURPOSE BUILDING, EXITING AREAS
Sta.
Existing Building
EXISTING BUILDING BY CATEGORY RENOVATION FIRST FLOOR
RENOVATION FULL BUILDING
110 Classroom
115 Classroom Service
310 Office
315 Office Service
350 Conference
355 Conference Service
410 Study Room
520 Athletics/Physical Education
525 Athletics/Physical Education Service
660 Merchandising
650 Lounge
WWW Circulation
XXX Building Service
YYY Mechanical
110 Classroom
115 Classroom Service
310 Office
315 Office Service
350 Conference
355 Conference Service
410 Study Room
520 Athletics/Physical Education
525 Athletics/Physical Education Service
660 Merchandising
650 Lounge
WWW Circulation
XXX Building Service
YYY Mechanical
110 Classroom
115 Classroom Service
310 Office
315 Office Service
350 Conference
355 Conference Service
410 Study Room
520 Athletics/Physical Education
525 Athletics/Physical Education Service
660 Merchandising
650 Lounge
WWW Circulation
XXX Building Service
YYY Mechanical
Proposed Renovation
Space Use Code Dispersion in Existing Building
LCCC Physical Education Building Renovation Level One Study Page 13
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
1 V1 Vestibule 207
1 V2 Vestibule 82
1 100A Hall/Lobby 1254
1 100B Hall/Lounge 1022
1 100C Hall 2368
1 100D Hall 260
1 100E Hall 615
1 100F Hall 1727
1 103A Multi Purpose Room 1500 16871
1 103B MP AV 162
1 103C MP Storage 296
1 103D Stair 268
1 103E Aerobic/Climbing Wall/Other 3392
1 103F Weight Room 1305
1 103G Stair 217
1 104 Fan Room 100
1 105 Fan Room 100
1 106 Fan Room 100
1 107A Classroom/Team Room 761
1 107A2 AV Closet 35
1 107B Volleyball Locker Room 345
1 107B2 Vestibule, Privacy 47
1 108A W. Soccer Lockers 346
1 108A2 Vestibule, Privacy 53
1 108B M. Soccer Lockers 534
1 108B2 Vestibule, Privacy 46
1 110 Custodial 41
1 112 Lockers, Women's Coach 174
1 114 Incorporated into 118
1 115 Locker Room/Restroom, Women's 498
1 116 Restroom, Women's 226
1 117 Shower, Women's 200
1 118 Training Room 1720
1 119 Field Storage 313
1 120 Locker Room/Restroom, Men's 464
1 121 Restroom, Men's 210
1 122 Shower, Men's 199
1 123 Lockers, Men's Coach 152
1 127 Mechanical Room 739
1 128 Mechanical Room 158
1 129 Exam 1 120 69
1 130 Office, Trainer 1 124 115
1 133 Active Instruction 49 3093
1 133A Storage, Aerobic Center 532
1 134 Storage, training 1 233
1 139 Racquetball Court 4 842
1 140 Racquetball Court 4 846
1 141 Racquetball Court 4 846
1 142 Office 163
1 143 Classroom 20 505
1 505 Gym 654 9657
1 506 Storage, Athletic 306
1 507 Storage, Athletic 64
1 508 Office 1 107
1 509 Electrical Room 216
1 510A Basketball Lockers 500
1 510B Stair 148
1 510C Concessions/Ticketing 130
1 510D Concessions storage 26
1 511 Pool 6956
1 512 Shower, Men's 203
1 513 Locker Room, Men's 511
1 516 Locker Room, Women's 409
1 517 Shower, Women's 184
1 519 Restroom, Women's 100
1 521 Restroom, Men's 108
1 522 Custodial 32
1 523 Mechanical Room 201
1 524 Office 1 150
1 525 Office 106
1 526 Mechanical Room 268
1 527 Storage, Acid Room 14
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
1266 35 770 0 0 0 0 44266 8875 156 2276 5892 73 1882
% of Total Floor Area 1.93% 0.05% 1.18% 0.00% 0.00% 0.00% 0.00% 67.59% 13.55% 0.24% 3.48% 9.00% 0.11% 2.87%
Total Floor Area 65491.00
Total Sta. 2240.00
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
1 701 Waiting/Lobby 759
1 702 A-D Assistant 203
1 703 Athletic Director 264
1 704 Hall 480
705 Coach's Office 139
706 Coach's Office 139
707 Coach's Office 139
708 Coach's Office 139
709 Conference 157
710 Coach's Office 107
711 Coach's Office 106
712 Coach's Office 107
713 Conference 254
714 Student Study 191
715 Coach's Office 107
716 Coach's Office 106
717 Coach's Office 107
718 Break Room 753
719 Storage 148
720 Stair (included in 1st floor)
801 Studio 781
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
Totals by Category Code 0 0 1663 1660 411 0 191 781 0 0 0 480 0 0
% of Total Floor Area 0.00% 0.00% 32.07% 32.01% 7.93% 0.00% 3.68% 15.06% 0.00% 0.00% 0.00% 9.26% 0.00% 0.00%
Total Floor Area 5186.00
Total Sta. 0.00
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
1266.00 35.00 2433.00 1660.00 411.00 0.00 191.00 45047.00 8875.00 156.00 2276.00 6372.00 73.00 1882.00
1.79% 0.05% 3.44% 2.35% 0.58% 0.00% 0.27% 63.74% 12.56% 0.22% 3.22% 9.02% 0.10% 2.66%
Laramie County Community College
MULTIPURPOSE BUILDING, RENOVATION AREAS - FIRST FLOOR
Floor
Room #
Room Name/Description
Sta.
Area by Category Code
MULTIPURPOSE BUILDING, RENOVATION AREAS - BUILDING SUMMARY
Area by Category Code
Totals by Category Code
MULTIPURPOSE BUILDING, RENOVATION AREAS - SECOND FLOOR
Floor
Room #
Room Name/Description
Sta.
Area by Category Code
Total Area by Category Code
Total Building Area
% of Total Building
70677.00
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
1 V1 Vestibule 207
1 V2 Vestibule 82
1 100A Hall/Lobby 1254
1 100B Hall/Lounge 1022
1 100C Hall 2368
1 100D Hall 260
1 100E Hall 615
1 100F Hall 1727
1 103A Multi Purpose Room 1500 16871
1 103B MP AV 162
1 103C MP Storage 296
1 103D Stair 268
1 103E Aerobic/Climbing Wall/Other 3392
1 103F Weight Room 1305
1 103G Stair 217
1 104 Fan Room 100
1 105 Fan Room 100
1 106 Fan Room 100
1 107A Classroom/Team Room 761
1 107A2 AV Closet 35
1 107B Volleyball Locker Room 345
1 107B2 Vestibule, Privacy 47
1 108A W. Soccer Lockers 346
1 108A2 Vestibule, Privacy 53
1 108B M. Soccer Lockers 534
1 108B2 Vestibule, Privacy 46
1 110 Custodial 41
1 112 Lockers, Women's Coach 174
1 114 Incorporated into 118
1 115 Locker Room/Restroom, Women's 498
1 116 Restroom, Women's 226
1 117 Shower, Women's 200
1 118 Training Room 1720
1 119 Field Storage 313
1 120 Locker Room/Restroom, Men's 464
1 121 Restroom, Men's 210
1 122 Shower, Men's 199
1 123 Lockers, Men's Coach 152
1 127 Mechanical Room 739
1 128 Mechanical Room 158
1 129 Exam 1 120 69
1 130 Office, Trainer 1 124 115
1 133 Active Instruction 49 3093
1 133A Storage, Aerobic Center 532
1 134 Storage, training 1 233
1 139 Racquetball Court 4 842
1 140 Racquetball Court 4 846
1 141 Racquetball Court 4 846
1 142 Office 163
1 143 Classroom 20 505
1 505 Gym 654 9657
1 506 Storage, Athletic 306
1 507 Storage, Athletic 64
1 508 Office 1 107
1 509 Electrical Room 216
1 510A Basketball Lockers 500
1 510B Stair 148
1 510C Concessions/Ticketing 130
1 510D Concessions storage 26
1 511 Pool 6956
1 512 Shower, Men's 203
1 513 Locker Room, Men's 511
1 516 Locker Room, Women's 409
1 517 Shower, Women's 184
1 519 Restroom, Women's 100
1 521 Restroom, Men's 108
1 522 Custodial 32
1 523 Mechanical Room 201
1 524 Office 1 150
1 525 Office 106
1 526 Mechanical Room 268
1 527 Storage, Acid Room 14
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
1266 35 770 0 0 0 0 44266 8875 156 2276 5892 73 1882
% of Total Floor Area 1.93% 0.05% 1.18% 0.00% 0.00% 0.00% 0.00% 67.59% 13.55% 0.24% 3.48% 9.00% 0.11% 2.87%
Total Floor Area 65491.00
Total Sta. 2240.00
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
1 701 Waiting/Lobby 759
1 702 A-D Assistant 203
1 703 Athletic Director 264
1 704 Hall 480
705 Coach's Office 139
706 Coach's Office 139
707 Coach's Office 139
708 Coach's Office 139
709 Conference 157
710 Coach's Office 107
711 Coach's Office 106
712 Coach's Office 107
713 Conference 254
714 Student Study 191
715 Coach's Office 107
716 Coach's Office 106
717 Coach's Office 107
718 Break Room 753
719 Storage 148
720 Stair (included in 1st floor)
801 Studio 781
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
Totals by Category Code 0 0 1663 1660 411 0 191 781 0 0 0 480 0 0
% of Total Floor Area 0.00% 0.00% 32.07% 32.01% 7.93% 0.00% 3.68% 15.06% 0.00% 0.00% 0.00% 9.26% 0.00% 0.00%
Total Floor Area 5186.00
Total Sta. 0.00
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
1266.00 35.00 2433.00 1660.00 411.00 0.00 191.00 45047.00 8875.00 156.00 2276.00 6372.00 73.00 1882.00
1.79% 0.05% 3.44% 2.35% 0.58% 0.00% 0.27% 63.74% 12.56% 0.22% 3.22% 9.02% 0.10% 2.66%
Laramie County Community College
MULTIPURPOSE BUILDING, RENOVATION AREAS - FIRST FLOOR
Floor
Room #
Room Name/Description
Sta.
Area by Category Code
MULTIPURPOSE BUILDING, RENOVATION AREAS - BUILDING SUMMARY
Area by Category Code
Totals by Category Code
MULTIPURPOSE BUILDING, RENOVATION AREAS - SECOND FLOOR
Floor
Room #
Room Name/Description
Sta.
Area by Category Code
Total Area by Category Code
Total Building Area
% of Total Building
70677.00
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
1 V1 Vestibule 207
1 V2 Vestibule 82
1 100A Hall/Lobby 1254
1 100B Hall/Lounge 1022
1 100C Hall 2368
1 100D Hall 260
1 100E Hall 615
1 100F Hall 1727
1 103A Multi Purpose Room 1500 16871
1 103B MP AV 162
1 103C MP Storage 296
1 103D Stair 268
1 103E Aerobic/Climbing Wall/Other 3392
1 103F Weight Room 1305
1 103G Stair 217
1 104 Fan Room 100
1 105 Fan Room 100
1 106 Fan Room 100
1 107A Classroom/Team Room 761
1 107A2 AV Closet 35
1 107B Volleyball Locker Room 345
1 107B2 Vestibule, Privacy 47
1 108A W. Soccer Lockers 346
1 108A2 Vestibule, Privacy 53
1 108B M. Soccer Lockers 534
1 108B2 Vestibule, Privacy 46
1 110 Custodial 41
1 112 Lockers, Women's Coach 174
1 114 Incorporated into 118
1 115 Locker Room/Restroom, Women's 498
1 116 Restroom, Women's 226
1 117 Shower, Women's 200
1 118 Training Room 1720
1 119 Field Storage 313
1 120 Locker Room/Restroom, Men's 464
1 121 Restroom, Men's 210
1 122 Shower, Men's 199
1 123 Lockers, Men's Coach 152
1 127 Mechanical Room 739
1 128 Mechanical Room 158
1 129 Exam 1 120 69
1 130 Office, Trainer 1 124 115
1 133 Active Instruction 49 3093
1 133A Storage, Aerobic Center 532
1 134 Storage, training 1 233
1 139 Racquetball Court 4 842
1 140 Racquetball Court 4 846
1 141 Racquetball Court 4 846
1 142 Office 163
1 143 Classroom 20 505
1 505 Gym 654 9657
1 506 Storage, Athletic 306
1 507 Storage, Athletic 64
1 508 Office 1 107
1 509 Electrical Room 216
1 510A Basketball Lockers 500
1 510B Stair 148
1 510C Concessions/Ticketing 130
1 510D Concessions storage 26
1 511 Pool 6956
1 512 Shower, Men's 203
1 513 Locker Room, Men's 511
1 516 Locker Room, Women's 409
1 517 Shower, Women's 184
1 519 Restroom, Women's 100
1 521 Restroom, Men's 108
1 522 Custodial 32
1 523 Mechanical Room 201
1 524 Office 1 150
1 525 Office 106
1 526 Mechanical Room 268
1 527 Storage, Acid Room 14
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
1266 35 770 0 0 0 0 44266 8875 156 2276 5892 73 1882
% of Total Floor Area 1.93% 0.05% 1.18% 0.00% 0.00% 0.00% 0.00% 67.59% 13.55% 0.24% 3.48% 9.00% 0.11% 2.87%
Total Floor Area 65491.00
Total Sta. 2240.00
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
1 701 Waiting/Lobby 759
1 702 A-D Assistant 203
1 703 Athletic Director 264
1 704 Hall 480
705 Coach's Office 139
706 Coach's Office 139
707 Coach's Office 139
708 Coach's Office 139
709 Conference 157
710 Coach's Office 107
711 Coach's Office 106
712 Coach's Office 107
713 Conference 254
714 Student Study 191
715 Coach's Office 107
716 Coach's Office 106
717 Coach's Office 107
718 Break Room 753
719 Storage 148
720 Stair (included in 1st floor)
801 Studio 781
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
Totals by Category Code 0 0 1663 1660 411 0 191 781 0 0 0 480 0 0
% of Total Floor Area 0.00% 0.00% 32.07% 32.01% 7.93% 0.00% 3.68% 15.06% 0.00% 0.00% 0.00% 9.26% 0.00% 0.00%
Total Floor Area 5186.00
Total Sta. 0.00
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
1266.00 35.00 2433.00 1660.00 411.00 0.00 191.00 45047.00 8875.00 156.00 2276.00 6372.00 73.00 1882.00
1.79% 0.05% 3.44% 2.35% 0.58% 0.00% 0.27% 63.74% 12.56% 0.22% 3.22% 9.02% 0.10% 2.66%
Laramie County Community College
MULTIPURPOSE BUILDING, RENOVATION AREAS - FIRST FLOOR
Floor
Room #
Room Name/Description
Sta.
Area by Category Code
MULTIPURPOSE BUILDING, RENOVATION AREAS - BUILDING SUMMARY
Area by Category Code
Totals by Category Code
MULTIPURPOSE BUILDING, RENOVATION AREAS - SECOND FLOOR
Floor
Room #
Room Name/Description
Sta.
Area by Category Code
Total Area by Category Code
Total Building Area
% of Total Building
70677.00
Space Use Code Dispersion in Proposed Renovation, First Floor
Space Use Code Dispersion in Proposed Renovation, Second Floor
Space Use Code Dispersion in Proposed Renovation, Full Building
LCCC Physical Education Building Renovation Level One Study Page 14
Laramie County Community College
Category Code Category Description Existing First Floor Area Renovation First Floor First Floor Area Change First Floor % Change Renovation Second Floor Renovation Full Building Total Building Area Change
110 Classroom 505 1266 761 151% 0 1266 761
115 Classroom Service 0 0 0 0.00 0 0
310 Office 1142 770 -372 -33% 1663.00 2433 1291
315 Office Service 0 0 0 1660.00 1660 1660
350 Conference 0 0 0 411.00 411 411
355 Conference Service 0 0 0 0.00 0 0
410 Study Room 0 0 0 191.00 191 191
520 Athletics/Physical Education 46916 44266 -2650 -6% 781.00 45047 -1869
525 Athletics/Physical Education Service 7965 8875 910 11% 0.00 8875 910
660 Merchandising 0 156 156 0.00 156 156
650 Lounge 0 2276 2276 0.00 2276 2276
WWW Circulation 6939 5892 -1047 -15% 480.00 6372 -567
XXX Building Service 113 73 -40 -35% 0 73 -40
YYY Mechanical 1882 1882 0 0% 0 1882 0
65462 65456 -6 5186 70642
Laramie County Community College
Category Code Category Description Existing First Floor by % Renovation First Floor Renovation Second Floor Renovation Full Building
110 Classroom 0.77% 1.93% 0.00% 1.79%
115 Classroom Service 0.00% 0.05% 0.00% 0.05%
310 Office 1.74% 1.18% 32.07% 3.44%
315 Office Service 0.00% 0.00% 32.01% 2.35%
350 Conference 0.00% 0.00% 7.93% 0.58%
355 Conference Service 0.00% 0.00% 0.00% 0.00%
410 Study Room 0.00% 0.00% 3.68% 0.27%
520 Athletics/Physical Education 71.67% 67.59% 15.06% 63.74%
525 Athletics/Physical Education Service 12.17% 13.55% 0.00% 12.56%
660 Merchandising 0.00% 0.24% 0.00% 0.22%
650 Lounge 0.00% 3.48% 0.00% 3.22%
WWW Circulation 10.60% 9.00% 9.26% 9.02%
XXX Building Service 0.17% 0.11% 0.00% 0.10%
YYY Mechanical 2.87% 2.87% 0.00% 2.66%
Building Area Totals
MULTIPURPOSE BUILDING - CATEGORY CODE AREA ANALYSIS
MULTIPURPOSE BUILDING - CATEGORY CODES PERCENTAGE ANALYSIS
S U C A
The tables below compare the existing building with the proposed renovation with regard to the dispersion of Space Use
Codes.
Laramie County Community College
Category Code Category Description Existing First Floor Area Renovation First Floor First Floor Area Change First Floor % Change Renovation Second Floor Renovation Full Building Total Building Area Change
110 Classroom 505 1266 761 151% 0 1266 761
115 Classroom Service 0 0 0 0.00 0 0
310 Office 1142 770 -372 -33% 1663.00 2433 1291
315 Office Service 0 0 0 1660.00 1660 1660
350 Conference 0 0 0 411.00 411 411
355 Conference Service 0 0 0 0.00 0 0
410 Study Room 0 0 0 191.00 191 191
520 Athletics/Physical Education 46916 44266 -2650 -6% 781.00 45047 -1869
525 Athletics/Physical Education Service 7965 8875 910 11% 0.00 8875 910
660 Merchandising 0 156 156 0.00 156 156
650 Lounge 0 2276 2276 0.00 2276 2276
WWW Circulation 6939 5892 -1047 -15% 480.00 6372 -567
XXX Building Service 113 73 -40 -35% 0 73 -40
YYY Mechanical 1882 1882 0 0% 0 1882 0
65462 65456 -6 5186 70642
Laramie County Community College
Category Code Category Description Existing First Floor by % Renovation First Floor Renovation Second Floor Renovation Full Building
110 Classroom 0.77% 1.93% 0.00% 1.79%
115 Classroom Service 0.00% 0.05% 0.00% 0.05%
310 Office 1.74% 1.18% 32.07% 3.44%
315 Office Service 0.00% 0.00% 32.01% 2.35%
350 Conference 0.00% 0.00% 7.93% 0.58%
355 Conference Service 0.00% 0.00% 0.00% 0.00%
410 Study Room 0.00% 0.00% 3.68% 0.27%
520 Athletics/Physical Education 71.67% 67.59% 15.06% 63.74%
525 Athletics/Physical Education Service 12.17% 13.55% 0.00% 12.56%
660 Merchandising 0.00% 0.24% 0.00% 0.22%
650 Lounge 0.00% 3.48% 0.00% 3.22%
WWW Circulation 10.60% 9.00% 9.26% 9.02%
XXX Building Service 0.17% 0.11% 0.00% 0.10%
YYY Mechanical 2.87% 2.87% 0.00% 2.66%
Building Area Totals
MULTIPURPOSE BUILDING - CATEGORY CODE AREA ANALYSIS
MULTIPURPOSE BUILDING - CATEGORY CODES PERCENTAGE ANALYSIS
Space Use Code Comparison by Area
Space Use Code Comparison by Percentage
APPENDIX
SPACE USE CODE ANALYSIS
project LCCC PE Building Renovation
client Laramie County Community College
date modified Friday, April 25, 2014
Category Code Category Description Existing First Floor Area Renovation First Floor First Floor Area Change First Floor % Change Renovation Second Floor Renovation Full Building Total Building Area Change
110 Classroom 505 1266 761 151% 0 1266 761
115 Classroom Service 0 0 0 0.00 0 0
310 Office 1142 770 -372 -33% 1663.00 2433 1291
315 Office Service 0 0 0 1660.00 1660 1660
350 Conference 0 0 0 411.00 411 411
355 Conference Service 0 0 0 0.00 0 0
410 Study Room 0 0 0 191.00 191 191
520 Athletics/Physical Education 46916 44266 -2650 -6% 781.00 45047 -1869
525 Athletics/Physical Education Service 7965 8875 910 11% 0.00 8875 910
660 Merchandising 0 156 156 0.00 156 156
650
Lounge 0 2276 2276 0.00 2276 2276
WWW Circulation 6939 5892 -1047 -15% 480.00 6372 -567
XXX Building Service 113 73 -40 -35% 0 73 -40
YYY Mechanical 1882 1882 0 0% 0 1882 0
65462 65456 -6 5186 70642
Laramie County Community College
Category Code Category Description Existing First Floor by % Renovation First Floor Renovation Second Floor Renovation Full Building
110 Classroom 0.77% 1.93% 0.00% 1.79%
115 Classroom Service 0.00% 0.05% 0.00% 0.05%
310 Office 1.74% 1.18% 32.07% 3.44%
315 Office Service 0.00% 0.00% 32.01% 2.35%
350 Conference 0.00% 0.00% 7.93% 0.58%
355 Conference Service 0.00% 0.00% 0.00% 0.00%
410 Study Room 0.00% 0.00% 3.68% 0.27%
520 Athletics/Physical Education 71.67% 67.59% 15.06% 63.74%
525 Athletics/Physical Education Service 12.17% 13.55% 0.00% 12.56%
660 Merchandising 0.00% 0.24% 0.00% 0.22%
650 Lounge 0.00% 3.48% 0.00% 3.22%
WWW Circulation 10.60% 9.00% 9.26% 9.02%
XXX Building Service 0.17% 0.11% 0.00% 0.10%
YYY Mechanical 2.87% 2.87% 0.00% 2.66%
Building Area Totals
PHYSICAL EDUCATION BUILDING - CATEGORY CODE AREA ANALYSIS
MULTIPURPOSE BUILDING - CATEGORY CODES PERCENTAGE ANALYSIS
SPACE USE CODE ANALYSIS
project LCCC PE Building Renovation
client Laramie County Community College
date modified
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
1 HW Hallways 6939
1 103 Multi Purpose Room 1500 22515
1 104 Fan Room 100
1 105 Fan Room 100
1 106 Fan Room 100
1 107 Weight Room 1519
1 108 PE Storage 1793
1 110 Custodial 81
1 112 Lockers, Women's Coach 155
1 114 PE Storage/Electrical Service 185
1 114A Office 1 80
1 114B Office 1 80
1 114C Office 1 80
1 115 Locker Room/Restroom, Women's 690
1
116 Restroom, Women's 219
1
117 Shower, Women's 386
1
118 Training Room 544
1 120 Locker Room/Restroom, Men's 736
1 121 Restroom, Men's 72
1 122 Shower, Men's 381
1 123 Lockers, Men's Coach 155
1 127 Mechanical Room 739
1 128 Mechanical Room 158
1 129 Office 1 120
1 130 Office 2 124
1 133 Aerobic Center 49 2850
1 133A Storage, Aerobic Center 750
1 134 Office 1 132
1 139 Racquetball Court 4 842
1 140 Racquetball Court 4 846
1 141 Racquetball Court 4 846
1 142 Office 163
1 143 Classroom 20 505
1 505 Gym 654 9657
1 506 Storage, Athletic 306
1 507 Storage, Athletic 64
1 508 Office 1 107
1 509 Electrical Room 216
1 510 Mat Room 10 885
1 511 Pool 6956
1 512 Shower, Men's 203
1 513 Locker Room, Men's 511
1 516 Locker Room, Women's 409
1 517 Shower, Women's 184
1 519 Restroom, Women's 100
1 521 Restroom, Men's 108
1 522 Custodial 32
1 523 Mechanical Room 201
1 524 Office 1 150
1 525 Office 106
1 526 Mechanical Room 268
1 527 Storage, Acid Room 14
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
505 0 1142 0 0 0 0 46916 7965 0 0 6939 113 1882
% of Total Building Area 0.77% 0.00% 1.74% 0.00% 0.00% 0.00% 0.00% 71.67% 12.17% 0.00% 0.00% 10.60% 0.17% 2.87%
Total Building Area 65462.00
Total Sta. 2254.00
Friday, April 25, 2014
Area by Category Code
Totals by Category Code
Room Name/Description
Room #
Floor
PHYSICAL EDUCATION BUILDING, EXITING AREAS
Sta.
SPACE USE CODE ANALYSIS
project LCCC PE Building Renovation
client Laramie County Community College
date modified
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
1 V1 Vestibule 207
1 V2 Vestibule 82
1 100A Hall/Lobby 1254
1 100B Hall/Lounge 1022
1 100C Hall 2368
1 100D Hall 260
1 100E Hall 615
1 100F Hall 1727
1 103A Multi Purpose Room 1500 16871
1 103B MP AV 162
1 103C MP Storage 296
1 103D Stair 268
1 103E Aerobic/Climbing Wall/Other 3392
1 103F Weight Room 1305
1 103G Stair 217
1 104 Fan Room 100
1 105 Fan Room 100
1 106 Fan Room 100
1 107A Classroom/Team Room 761
1 107A2 AV Closet 35
1
107B Volleyball Locker Room 345
1 107B2
Vestibule, Privacy 47
1 108A W. Soccer Lockers 346
1 108A2 Vestibule, Privacy 53
1 108B M. Soccer Lockers 534
1 108B2 Vestibule, Privacy 46
1 110 Custodial 41
1 112 Lockers, Women's Coach 174
1 114 Incorporated into 118
1 115 Locker Room/Restroom, Women's 498
1 116 Restroom, Women's 226
1 117 Shower, Women's 200
1 118 Training Room 1720
1 119 Field Storage 313
1 120 Locker Room/Restroom, Men's 464
1 121 Restroom, Men's 210
1 122 Shower, Men's 199
1 123 Lockers, Men's Coach 152
1 127 Mechanical Room 739
1 128 Mechanical Room 158
1 129 Exam 1 120 69
1 130 Office, Trainer 1 124 115
1 133 Active Instruction 49 3093
1 133A Storage, Aerobic Center 532
1 134 Storage, training 1 233
1 139 Racquetball Court 4 842
1 140 Racquetball Court 4 846
1 141 Racquetball Court 4 846
1 142 Office 163
1 143 Classroom 20 505
1 505 Gym 654 9657
1 506 Storage, Athletic 306
1 507 Storage, Athletic 64
1 508 Office 1 107
1 509 Electrical Room 216
1 510A Basketball Lockers 500
1 510B Stair 148
1 510C Concessions/Ticketing 130
1 510D Concessions storage 26
1 511 Pool 6956
1 512 Shower, Men's 203
1 513 Locker Room, Men's 511
1 516 Locker Room, Women's 409
1 517 Shower, Women's 184
1 519 Restroom, Women's 100
1 521 Restroom, Men's 108
1 522 Custodial 32
1 523 Mechanical Room 201
1 524 Office 1 150
1 525 Office 106
1 526 Mechanical Room 268
1 527 Storage, Acid Room 14
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
1266 35 770 0 0 0 0 44266 8875 156 2276 5892 73 1882
% of Total Floor Area 1.93% 0.05% 1.18% 0.00% 0.00% 0.00% 0.00% 67.59% 13.55% 0.24% 3.48% 9.00% 0.11% 2.87%
Total Floor Area 65491.00
Total Sta. 2240.00
Friday, April 25, 2014
PHYSICAL EDUCATION BUILDING, RENOVATION AREAS - FIRST FLOOR
Floor
Room #
Room Name/Description
Sta.
Area by Category Code
Totals by Category Code
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
2 701 Waiting/Lobby 759
2 702 A-D Assistant 203
2 703 Athletic Director 264
2 704 Hall 480
2 705 Coach's Office 139
2 706 Coach's Office 139
2 707 Coach's Office 139
2 708 Coach's Office 139
2 709 Conference 157
2 710 Coach's Office 107
2 711 Coach's Office 106
2 712 Coach's Office 107
2 713 Conference 254
2 714 Student Study 191
2 715 Coach's Office 107
2 716 Coach's Office 106
2 717 Coach's Office 107
2 718 Break Room 753
2 719 Storage 148
2 720 Stair (included in 1st floor)
2 801 Studio 781
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
Totals by Category Code 0 0 1663 1660 411 0 191 781 0 0 0 480 0 0
% of Total Floor Area 0.00% 0.00% 32.07% 32.01% 7.93% 0.00% 3.68% 15.06% 0.00% 0.00% 0.00% 9.26% 0.00% 0.00%
Total Floor Area 5186.00
Total Sta. 0.00
110 115 310 315 350 355 410 520 525 660 650 WWW XXX YYY
Classroom Classroom Service Office Office Service Conference Conference Service Study Room Athletic/P.E. Athletic/P.E. Service Merchandising Lounge
Circulation Building Service Mechanical
1266.00 35.00 2433.00 1660.00 411.00 0.00 191.00 45047.00 8875.00 156.00 2276.00 6372.00 73.00 1882.00
1.79% 0.05% 3.44% 2.35% 0.58% 0.00% 0.27% 63.74% 12.56% 0.22% 3.22% 9.02% 0.10% 2.66%
PHYSICAL EDUCATION BUILDING, RENOVATION AREAS - BUILDING SUMMARY
Area by Category Code
PHYSICAL EDUCATION BUILDING, RENOVATION AREAS - SECOND FLOOR
Floor
Room #
Room Name/Description
Sta.
Area by Category Code
Total Area by Category Code
Total Building Area
% of Total Building
70677.00
Figure 3
STATE OF WYOMING
NOTIFICATION OF DEMOLITION AND RENOVATION
Form 5
Revised 9/2007
(WY DEQ Form
)
I. Facility Description (Include Building Name, Number, And Floor Or Room Number)
BLDG NAME:
ADDRESS:
CITY: STATE” ZIP: CONTACT:
SITE DESCRIPTION (type of material being removed)
II.
Facility Information (Identify Owner, Removal Contractor, And Other Operator)
OWNER NAME:
ADDRESS:
CITY: STATE: ZIP:
CONTACT PERSON: TEL:
REMOVAL CONTRACTOR:
ADDRESS:
CITY: STATE: ZIP:
CONTACT PERSON: TEL:
OTHER OPERATOR:
ADDRESS:
CITY: STATE: ZIP:
CONTACT PERSON: TEL:
BUILDING SIZE: NUM OF FLOORS: AGE IN YEARS:
PRESENT USE: PRIOR USE:
III. Type Of Operation: D=Demo O=Ordered Demo R=Renovation E=Emergency Renovation
IV. Is Asbestos Present?
YES NO Explain:
V. Procedure, Including Analytical Method, If Appropriate, Used To Detect The Presence Of Asbestos Material:
VI. Scheduled Dates Asbestos Removal (MM/DD/YY) START:
COMPLETE:
VII. Scheduled Dates Demo/Renovation (MM/DD/YY) START:
COMPLETE:
VIII. Scheduled Work Hours: START:
COMPLETE:
IX. Approximate Amount Of Asbestos,
Including
:
1. Regulated ACM To Be Removed
2. Category I ACM Not Removed
3. Category II ACM Not Removed
RACM
To Be
Removed
Nonfriable Asbestos
Material To Be
Removed
Nonfriable Asbestos
Material Not To Be
Removed
CAT I CAT II CAT I CAT II
PIPES
SURFACE AREA
VOL. RACM OFF FACILITY COMPONENT
X. Description Of Planned Demolition Or Renovation Work And Method(S) To Be Used:
XI.
Description Of Work Practiced And Engineering Controls To Be Used To Prevent Emissions Of Asbestos At The
Demolition And Renovation Site
:
XII.
Type Of Notification: O=Original R=Revised C=Cancelled
Figure 3
STATE OF WYOMING
NOTIFICATION OF DEMOLITION AND RENOVATION
Form 5
Revised 9/2007
(WY DEQ Form
)
WPR Notice? Yes No
XIII.
Waste Transporter #1
ADDRESS:
CITY: STATE: ZIP:
CONTACT PERSON: TEL:
WASTE TRANSPORTER #2:
ADDRESS:
CITY: STATE: ZIP:
CONTACT PERSON: TEL:
XIV. WASTE DISPOSAL SITE
NAME:
LOCATION:
CITY: STATE: ZIP:
CONTACT PERSON: TEL:
XV.
If demolition ordered by a government agency, please identify the agency below:
NAME: TITLE:
AUTHORITY:
DATE OF ORDER (MM/DD/YY):
DATE ORDERED TO BEGIN (MM/DD/YY):
XVI.
For Emergency Renovations
DATE AND HOUR OF EMERGENCY (MM/DD/YY):
DESCRIPTION OF THE SUDDEN, UNEXPECTED EVENT:
EXPLANATION OF HOW THE EVENT CAUSED UNSAFE CONDITIONS OR WOULD CAUSE EQUIPMENT DAMAGE OR AN
UNREASONABLE FINANCIAL; BURDEN:
XVII. Description of procedures to be followed in the event that unexpected asbestos is found or previously nonfriable
asbestos material becomes crumbled, pulverized or reduced to powder:
XVIII. I certify that an individual trained in the provision of this regulation (40 CFR Part 61, Subpart M) will be on site
during the demolition or renovation and evidence that the required training has been accomplished b y this person
will be available for inspection during normal business hours (required 1 year after promulgation).
_______________________________________________ Date: (Signature of Owner/Operator)
XIX. I certify that the above information is correct.
_______________________________________________ Date: (Signature of Owner/Operator)
Laramie County Planning and Development Office
Building Division
3861 Archer Pkwy Cheyenne, WY 82009
Phone: 307-633-4512 Fax: 307-633-4519
planning@laramiecounty.com
www.laramiecountyplanning.com
Page1
COMMERCIAL SUBMITTAL REQUIREMENTS
INCOMPLETE APPLICATIONS CAN NOT BE ACCEPTED
Please visit our new and improved Laramie County Parcel Viewer for information on the property
and aerials: http://arcims.laramiecounty.com/
All Building Permit Applications must include the following:
1. Completed Application Form
2. Recorded deed for proof of property ownership (for new Residential construction)
3. Certificate of Review from the Planning Division
4. One plot plan
5. One set of building plans
6. One set of engineered foundation plans stamped by a registered Wyoming Engineer
7. Proof of Health Department Approval (additions only)
8. Proof of Driveway Access Approval. Please contact Leo Pando at (307) 633-4302 to discuss requirements
9. Fire District Approval may be required
NOTE: AN OPEN HOLE INSPECTION REPORT OR SOILS REPORT (from a register Wyoming Engineer is required
prior to requesting footer/foundation inspection.)
WE ARE GOING GREENER! Please note that we require one full set of plans as well as an electronic set
whenever possible. If electronic copies are not submitted, we will require 2 full sets of plans. Please contact us if
you have questions.
Please refer to attached for complete instructions and information.
NOTICE:
The Applicant, his Agents and Employees shall comply with all the rules, restrictions and requirements of Laramie
County Zoning Regulations and Laramie County Building Codes governing location, construction and erection of
the above proposed work for which the permit is granted. The Building Official or his agents are authorized to
order the immediate cessation of construction at any time a violation of the codes or regulations appears to have
occurred. Violation of any of the codes or regulations applicable may result in the revocation of this permit.
Buildings must conform with plans as submitted to the Laramie County Planning & Development Office. Any
change of plans or layout must be approved prior to the changes being made. Any change in the use or
occupancy of a building or structure must be approved prior to proceeding with construction.
The Applicant is required to call for inspections at various stages of the construction, and in accordance with the
aforesaid rule, the applicant shall give the Building Inspector not less than one day’s notice to perform such
activities.
Laramie County Planning and Development Office
Building Division
3861 Archer Pkwy Cheyenne, WY 82009
Phone: 307-633-4512 Fax: 307-633-4519
planning@laramiecounty.com
www.laramiecountyplanning.com
Page2
The Applicant must comply with current Planning & Development office expiration policy. Laramie County is not
liable for workmanship. Permits are not transferable.
The following items expand on the submittal requirements. Not all projects require all items listed below, please
contact us if you have any questions.
1. Application Form: can be obtained at the Laramie County Planning & Development Office or on-line at the
Laramie County website at www.laramiecountyplanning.com
2. Proof of Ownership: A copy of the recorded deed will be required to verify ownership of the property.
3. Plot Plans: (sample available upon request) They are to be drawn on 8 ½” x 11” size paper, and must
show:
1. North arrow
2. Location of proposed building
3. Distances between each property line to proposed building (the minimum is from 2 property lines)
4. Distances between proposed building and any existing structures
5. Identify the street or county/state road being accessed from
6. Driveway location with driveway width and surface type (and distance to the closest property line)
7. Location of well and septic system (if applicable)
4. Building Plans: Two identical sets (only one set is required if submitted on paper that is 11”x17” or smaller)
of Building Plans are required for all residential buildings. Plans should include all of the items listed below
which apply to your particular project. Plans and specifications must be drawn to scale on substantial paper,
unless the plans are being submitted electronically, and must indicate locations, nature and extent of the
work proposed, and should show in detail that it will conform to the adopted Laramie County Building Code,
and shall state the design standards meet or exceed wind and snow loads for the area. The recommended
scale for plans is 1/4" = 1'. Plan Review fees are calculated at 65% of the building permit fee based on
provided valuation. Fee adjustments may be made if needed.
If the project is an addition or remodel, be sure to clearly label all existing and all proposed construction.
The following information is required for full plan submittal:
A. Foundation and Floor- Framing Plan: All foundations shall be designed and wet-stamped by an architect
or engineer licensed by the State of Wyoming. Additionally, if a site-specific soils report is not provided, an
"open hole" inspection shall be conducted by an architect or engineer licensed by the State of Wyoming.
Contact the Planning & Development Office for exceptions for an addition to an existing residence.
Foundation and floor framing plans must include the following information:
1. Location of continuous foundations and pier footings
2. Size and depth of footings
3. Thickness of concrete slabs
4. Size and spacing of girders
5. Size and spacing of floor joists
6. Location of crawl holes and vents
7. Size of stem walls
8. Location and size of re-enforcing steel to be installed
Laramie County Planning and Development Office
Building Division
3861 Archer Pkwy Cheyenne, WY 82009
Phone: 307-633-4512 Fax: 307-633-4519
planning@laramiecounty.com
www.laramiecountyplanning.com
Page3
9. Elevation of foundation in relation to grade
B. Floor Plan: Floor plans must show the following:
1. Exterior dimensions
2. Interior dimensions
3. Use of all rooms
4. Size of all windows and doors
5. Size of supporting headers above wall openings
6. Direction of joists and rafters
7. Location of all plumbing fixtures
8. Location and type of heating and air conditioning facilities
9. Location of smoke detectors
10. Drawings shall be to scale
C. Elevation Views: This is a drawing or exterior view of each new wall. The drawing must include:
1. Doors, windows and other openings
2. Vertical dimensions
3. Exterior finishes
4. Wall bracing or shear panel location or means of obtaining required lateral bracing
D. Cross Section Views: The cross section views must include:
1. Interior and exterior finishes
2. Size, spacing and type of materials used
3. Insulation, type, location and “R” value
4. Typical connections
5. Complete roofing specifications
E. Roof Plan: the roof plans should include drawings of the following:
1. Hips, valleys, ridges
2. Any special framing at roof area
3. For additions to existing buildings, locations of bearing walls and slope of roof in existing buildings;
and
4. Shall include a copy of the truss certifications (truss specs shall be available at the job site for the
inspector.)
5. Foundation Plans: Two identical sets (only one set is required if submitted on paper that is 11”x17” or
smaller) of Foundation Plans that are engineered by a Wyoming Licensed Engineer are required for all
residential buildings. All drawings must be stamped.
Laramie County Planning and Development Office
Building Division
3861 Archer Pkwy Cheyenne, WY 82009
Phone: 307-633-4512 Fax: 307-633-4519
planning@laramiecounty.com
www.laramiecountyplanning.com
Page4
6. Permit for access driveway: If access is from a county road, the application is available from the Laramie
County Planning & Development Office, or on-line at the Laramie County website at
www.laramiecountyplanning.com. The fee for the county access permit is $25.00.
If access is from a state highway, please contact the WyDOT District Engineer in Laramie at (307) 745-2100.
7. Open Hole Report: Please see #4A - If a site-specific soils report is not provided, an “Open Hole Inspection
Report” shall be conducted by an architect or engineer licensed by the State of Wyoming. This is to be
submitted prior to requesting a footer/foundation inspection. Please note that our inspectors must verify the
footer/rebar/caissons prior to any concrete being poured.
For other related permit information, please contact:
(307) 635-5608 South Cheyenne Water & Sewer District
(307) 633-4090 City/County Environmental Health Department (Septic permits)
(307) 777-6163 State Engineer’s Office (Well permits)
Rcvd By Rcvd Date PR # BP #
New Address?
yes no
Name Phone
Address City
Email State Zip
Name Phone
Address City
Email State Zip
Phone
Electrician Phone
Zone District Township Range Section
Prior Use
New Addition Renovation
Other Demolish Move
20 yrs old
slab on grade crawl space
1st floor 2nd floor
Date
Approved
Fees BP Fee PR Fee MP Fee
Check # Cash Receipt # Total Fees
Primary Contact Person
block / pier / caisson
Description of Work: Complete description of the work done including any plumbing, mechanical (Heating, ventilaiton or air conditioning),
electrical, fire sprinkler or alarm. (Work is not included in the permit unless description in this scope of work.)
Foundation Type
Bldg area square footage
Design Occupancy Load
basement
other
Structure Use
Check all that apply and fill in square footage areas specific to this project
Fire Sprinklers
Manufactured Bldg Structurally Altered
Purpose of Permit
Project Information
Legal Description (Subdivision, Block and Lot or Tract)
Map Page
INCOMPLETE APPLICATIONS CAN NOT BE ACCEPTED
Property Information
Land Owner Information
Contractor Information
Address of Project
If there are additional owners (such as a Business Owner), please list on separate sheet and attach
Name of Business
Signature of Owner / Agent
Printed Name
Valuation (cost of project) $
Phone: 307-633-4512
Fax: 307-633-4519
planning@laramiecounty.com
www.laramiecountyplanning.com
Laramie County Planning and Development Office
Building Division
3861 Archer Pkwy Cheyenne, WY 82009
Commerical Building Permit Application
Bymysignatureandunderpenaltyofperjury,IherebycertifythatIamtheownerofthereferencedproperty,ortheowner’s authorizedagent.Ihavereadandexamined
thisapplicationandknowthesametobetrueandcorrect.Allprovisionsorlawsandordinancesgoverningthistypeofwork
willbecompliedwith,whether specified
hereinornot.Theissuanceofapermitdoesnotpresumetogiveauthoritytoviolateorcanceltheprovisionsofanystateorlocallawregulating construction,orguarantee
issuanceofawellorsepticpermit,thispermitbecomesnullandvoidif
workorconstructionauthorizedisnotcommencedwithin180days,unlesspriorauthorizationhas
beenissuedbythisoffice.Thispermitexpires1yearfromthedateofissuanceprovidingthe1stinspectionhasoccurredwithintheinitial180dayperiod.Iunderstand that
occupyingthisstructurepriortoobtaininga
CertificateofOccupancyisagainstthelaw.Failuretocomplymayresultina $750finewitheachdayofoccupancybeinga