SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
369147f 4 10.03.2017
Wallbox Controls0–10 V ControlsDiva
Specifications (continued)
DVTV- and DVSCTV- Models
Power
Operating Voltage
24 V- 100 mA
Output Ratings
• Power pack required for load switching. Power pack is
rated for 16 A.
• 30 mA maximum output (sink only).
0–10 V Control Link
• 0–10 V control is Class 2.
• Controls up to 15 ballasts or drivers (IEC 60929 Annex
E.2 requires the ballast / driver to limit the current draw
to 2.0 mA maximum).
Performance
• For 120-277 V~ installations switching more than
8A, use DVTV- with Lutron power pack (PP-DV). See
Lutron P/N 369544.
• For 347 V~ installations, use DVTV- with Lutron power
pack (PP-347H) See Lutron P/N 369544.
• Works with all ballasts and drivers that provide a
current source compliant to IEC 60629 Annex E.2.
• Adjustable high-end and low-end trim for optimal
dimming performance.
• Power failure memory: should power be interrupted,
the 0–10 V- signal will return to its previously set level
prior to the interruption when power is restored.
• Captive linear slider.
• Precise color matching.
Environment
• For indoor use only.
• Ambient operating temperature: 32 °F to 104 °F
(0 °C to 40 °C), 0% to 90% humidity, non-
condensing.
Application Requirements
• No derating required if ganged.
• Night light not available.
• Always consult local wiring codes.
Warranty
• www.lutron.com/TechnicalDocumentLibrary/
369-119_Wallbox_Warranty.pdf