45'-10"
27'-6"
11'-3"
E E E
G G
Customer Name -
Address and Phone
Number
PATIO
POOL
RESIDENCE
UTILITIES
ELECTRIC PLUMBING
LENGTH
50' 134'
TYPE
RIGID PVC RIGID PVC
DEPTH
-18" -18"
SIZE
#8 2
1
2
"
TRACER WIRE
CONDUCTOR PURPLE
CONDUIT SIZE
1"
BREAKER SIZE
30 AMPS
FLA
15 AMPS
UNDER GROUND
SCH #40
ABOVE GROUND
SCH #80
GAS LINES (1) [TOTAL LENGTH - 25 LF]
SOURCE
METER
DESTINATION
POOL EQUIP
DEMANDS
400K BTU
LENGTH
25 LF
SIZE
1"
TYPE
POLYETHYLENE PIPE
DEPTH
-18"
TRACER
YELLOW
TOTAL LENGTH
25 LF TOTAL
TOTAL BTU
400K BTU
SPA
G
E
40 LF
45 LF
Pool Company
Name - Address
- Phone
Number
DESIGNER: ??
DWG BY: ??
DATE: ??
SCALE: ??
ROC # ??
N
POOL & SPA DATA
525
49
574
SHALLOW
3.5
5.0
8.0
POOL AREA FT2
SPA AREA FT2
TOTAL FT2
POOL DEPTHS
MIDDLE
DEEP
"WITH THE FIRST INSPECTION THERE
SHALL BE A PRE-CONSTRUCTION MEETING
ON THE JOB SITE WITH THE PROPERTY
OWNER, THE POOL CONTRACTOR, AND A
TOWN OF SAHUARITA BUILDING
INSPECTOR. CALL TED RODRIQUEZ, CHIEF
BUILDING INSPECTOR AT (520) 275-3354 TO
SCHEDULE"
ALL WORK SHALL COMPLY WITH THE 2018
ICC SUITE OF CODES AND THE 2017 NEC
OUTDOOR HEATED POOLS AND OUTDOOR
PERMANENT SPAS SHALL BE PROVIDED
WITH A VAPOR-RETARDANT COVER OR
OTHER APPROVED VAPOR-RETARDANT
MEANS IN ACCORDANCE WITH SECTION
104.11. 2018 ISPSC 303.1.3. (HAVE COVER
ON SITE AT FINAL INSPECTION)
"A 3RD PARTY VERIFICATION REPORT FOR
THE BACKFLOW WILL BE REQUIRED AT
FINAL INSPECTION" COMPLETED BY AN
APPROVED BY THE TOWN OF SAHUARITA
COMPANY AND INDIVIDUAL IRC SECTION
102.7.1.
WHERE INSTALLED IN WET LOCATIONS, 15
AND 20 AMP, 125 – AND 250-VOLT
RECEPTACLES SHALL HAVE AN
ENCLOSURE THAT IS WEATHERPROOF
WITH AN OUTLET BOX HOOD LISTED AND
IDENTIFIED AS "EXTRA-DUTY" THESE
RECEPTACLES SHALL ALSO BE LISTED
AND IDENTIFIED AS THE WEATHER-
RESISTANT TYPE (WR) AND TAMPER
RESISTANT (TR). IRC SECTION E4002.9.
OVERCURRENT PROTECTION REQUIRED.
BRANCH-CIRCUIT CONDUCTORS AND
EQUIPMENT SHALL BE PROTECTED BY
OVERCURRENT PROTECTIVE DEVICES
HAVING A RATING OR SETTING NOT
EXCEEDING THE ALLOWABLE AMPACITY
AND BE GFCI PROTECTED. IRC SECTION
E3705.1. E4203.1.4
ALL RECEPTACLES LOCATED WITHIN 20
FEET OF WATERS EDGE OF POOLS AND
OUTDOOR SPAS AND HOT TUBS SHALL BE
PROTECTED BY GFCI WR/TR IRC SECTION
E4002.9.
INDICATE ON PLAN THE CONVENIENCE
RECEPTACLE NO CLOSER THAN 6' AND NO
FARTHER THAN 20' FROM WATERS EDGE
OF POOL IRC SECTION E4203.1.3.
NONMETALLIC RACEWAYS LISTED FOR
DIRECT BURIAL SHALL BE 18 INCHES DEEP
IRC SECTION E3803.1.
ALL METAL WITHIN 5' OF THE POOL/SPA IS
REQUIRED TO BE BONDED. IRC SECTION
E4204 (7).
INDICATE ON PLANS THE EQUIPOTENTIAL
BONDING. IRC SECTION E4204.1. E4204.2.
MAIN PANEL SIZE SUB PANEL SIZE
IRC SECTION E3602, E3606.4, AND
E3701.2, E3706.1 E3602.2.
DOORS WITH ACCESS TO THE POOL AND
WIDOWS WITH LATCHES LESS THAN 54"
SHALL BE ALARMED WITH UL 2017
ALARMS IPSC SECTION 305.4.
ALL ACCESS GATES SHALL HAVE SELF-
CLOSING, SELF-LATCHING DEVICES AT A
HEIGHT OF 54"LOCATED ON THE POOL
SIDE OF THE GATE. THE TOP OF THE GATE
AT A MIMIMUM OF 60 INCHES IN HEIGHT
FROM GRADE AND A MAXIMUM OF 2”
CLEARANCE FROM THE BOTTOM OF THE
GATE TO GRADE. THE GATE SHALL OPEN
OUTWARD AWAY FROM THE POOL AREA.
ISPSC SECTION 305.3 TOS AMENDMENTS
SECTION AG305.2 (1)
INDICATE ON THE PLAN THE REQUIRED
TYPE AND HEIGHT OF BARRIER A MINIMUM
OF 60”. TOS AMENDMENTS SECTION
AG305.2 (1).
PET DOORS WITH DIRECT ACCESS TO THE
POOL WILL NOT BE PERMITTED. ISPSC
SECTION 305.5.5