Egress Stairwell | New Construction
IECC 2012
Symbol Model Number Description Qty
FXSWLX4H Lutron 4 ft. stairwell LED fixture
2
(per floor)
LRF2-OKLB-P-WH
Radio Powr Savr wireless corner-mount
occupancy sensor
1
(per floor)
Control Functionality
Occupant Enters:
All lights automatically turn on to maximum light level. Maximum light level is set to 80%.
Occupant Exits:
All lights dim to minimum light level 15 minutes after all occupants exit. Minimum light level is set to 10%.
Emergency Mode:
Lighting connected to emergency power turns on to full output.
Line-voltage
wiring
Clear Connect
RF Communication
A section of the floor is shown
A floor cross-section is shown. One fixture per landing is suggested.
To
emergency
power
To
emergency
power
Code Notes: Verify that the egress fixtures go to full output upon loss of control signal. For projects that require UL 924 compliance, provide an
automatic load control relay (ALCR) per load controller connected to emergency fixtures. Add a daylight sensor for stairwells with daylight zones.
Lutron Stairwell Fixture (FXSWLX44) is not currently compatible with Vive wireless hub. A new model number is coming soon that will include
Vive compatibility.