SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wired Occupancy Sensors for High-Bay Applications
369606c 1 01.24.2019
Lutron
Sensors
Occupancy Sensors for
High-Bay Applications
Features
•Surface-mountandend-mountmodelsavailable.
•180°and360°coveragelensesavailable.
•Low-voltage,passiveinfrared(PIR)sensor.
•ControlsLutronsystemsinhigh-bayapplications.
•End-mountmodelattachesdirectlytoindustrialT5HO
andT8xturesthroughanextended½in(13mm)
chasenippleorjunctionbox.
•Maximum45ft(14m)mountingheight.
(Seenextpageforcoveragediagrams.)
•Featuresanadjustabletimeoutformaximumenergy
savings.
•Idealforwarehouses,distributioncenters,and
gymnasiums.
Available Models
LUT-WSPSM24V-180 -x x
1
- CPN 6111 Surface-mount,180°coverage
LUT-WSPSM24V-360-xx
1
- CPN 6111 Surface-mount,360°coverage
LUT-WSPEM24V-180-x x
1
- CPN 6112 End-mount,180°coverage
LUT-WSPEM24V-360-xx
1
- CPN 6112 End-mount,360°coverage
Color
WH White
BL Black
GR Gray
End-mount
Surface-mount
180° aisle lens
360° lens
1
"xx"denotesthecolor.Seechoicesabove.
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wired Occupancy Sensors for High-Bay Applications
369606c 2 01.24.2019
Lutron
Sensors
30 ft (9 m) mounting height
45 ft (14 m) mounting height
Coverage Diagrams
Notes
Sensorisdesignedtodetectmajor
motion(i.e.,walkingperson)only
Adelayof1to2secondsfrom
occupancydetectiontoturn-onmay
beexperienced
42 ft (13 m) radius at 30 ft (9 m) mounting height
50 ft (15 m) radius at 45 ft (14 m) mounting height
Specifications
•20–24V-input30mAmax.
•Userinterface:12-pinDIPswitch
•Availabletimeroptions:
-8secondtestmode
-4,8,16,and30minutetimeouts
•Passiveinfrared:Dualelementpyrometerand
sphericalFresnellensdesignedtodetectmajor
motion(i.e.,walkingperson)
•Coverage:360°or180°
SeeCoverage Diagramsfordetails.
Lensratio:
-30ft(9m)mountingheight:1.4:1
-30to45ft(9to14m)mountingheight:1.1:1
•Construction:High-impactinjection-molded
plasticcasing
•Sizeandweight:4in(102mm)diameter
1½in(38mm)height
7oz(198g)
Sensor Placement
•Todetectmotion,thesensorrequiresline-of-sight
ofroomoccupants.Thesensormustalsohave
anunobstructedviewoftheroom.DoNOTmount
behindorneartallcabinets,shelves,hanging
xtures,ceilingfans,etc.Thesensorcannotsee
throughglassobjectssuchaspatioorshower
doors.
•Hotobjectsandmovingaircurrentscanaffect
theperformanceofthesensor.Toensureproper
operation,thesensorshouldbemountedatleast
4ft(1.2m)awayfromHVACventsandlightbulbs
thatarebelowtheceilingline.
•Theperformanceofthesensordependsona
temperaturedifferentialbetweentheambientroom
temperatureandthatoftheroomoccupants.
Warmerroomsmayreducetheabilityofthe
sensortodetectoccupants.
•DevicesemittingRadioFrequency(RF)energy
canaffecttheperformanceofsensors.Toensure
properoperation,sensorsshouldbemountedat
least4ft(1.2m)awayfromdevicesthatemitradio
waves(e.g.,microwaveovens,wirelessroutersor
otherwirelessdevices).
•Foradditionalinformationonplacingsensors,
pleaseseetheOccupancy/VacancySensor
DesignandApplicationGuide(P/N368-3197)
locatedatwww.lutron.com.
42 ft (13 m)
at 30 ft (9 m)
mounting height
50 ft (15 m)
at 45 ft (14 m) mounting height
29 ft
(9 m)
21 ft
(6 m)
360° Lens
Side View
180° Lens
Top View
Operating Environment
•Indooruseonly
•Operatingtemperature:32°F–86°F(0°C–30°C)
•Foruseinclimatecontrolledenvironmentsonly
•Relativehumidity(non-condensing):0–95%
Certifications
•ConformstoULSTD508,ULSTD244A
•CertiedtoCAN/USASTD22.2No.61010-1-04
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wired Occupancy Sensors for High-Bay Applications
369606c 3 01.24.2019
Lutron
Sensors
Surface Mounting
Refertothismountingtemplate(rearviewofsensor)
forpositioningmountingscrewholesandwiring
accesshole.
Mountinghole
Usescrewsprovided
Wiringaccess
Approx.2x1in
(19x6mm)
22in(70mm)
O
N
1 2 3 4 5 6 7 8 9 10 11 12
Mounting:frontviewofsensor
(lensremoved)
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wired Occupancy Sensors for High-Bay Applications
369606c 4 01.24.2019
Lutron
Sensors
Wiring Diagrams
Maximum Wire Lengths
WireSize #Sensors
1 2 3
22AWG
(0.5mm
2
)
750ft
(229m)
375ft
(114m)
250ft
(76m)
20AWG
(0.65mm
2
)
1200ft
(366m)
600ft
(183m)
400ft
(122m)
18AWG
(0.75mm
2
)
2400ft
(732m)
1200ft
(366m)
800ft
(244m)
Wiring to a QS Sensor Module (QSM)
•Maximumfour(4)occupancysensorsperQSM
•RefertoQSMSpecicationSubmittalforadditionaldetails
Note:DoNOTusebluewireforANYinstallation.
Wiring to an EcoSystem Ballast
•Maximumone(1)occupancysensorper
EcoSystemballast
•RefertoEcoSystemballastSpecicationSubmittal
foradditionaldetails
Red(20-24V-)
Gray(Signal)
Black(Common)
EcoSystemballast
ToEcoSystemBus
Occupancy
sensor
Capoff
remaining
wires
Capoff
remaining
wires
Occupancy
sensor
QSsensor
module
Red(20-24V-)
Gray(Signal)
Black(Common)
ToQSLink
COM
OCC
+20V
COM
OCC
+20V
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wired Occupancy Sensors for High-Bay Applications
369606c501.24.2019
Lutron
Sensors
Wiring Diagrams
Maximum Wire Lengths
WireSize #Sensors
1 2 3
22AWG
(0.5mm
2
)
750ft
(229m)
375ft
(114m)
250ft
(76m)
20AWG
(0.65mm
2
)
1200ft
(366m)
600ft
(183m)
400ft
(122m)
18AWG
(0.75mm
2
)
2400ft
(732m)
1200ft
(366m)
800ft
(244m)
Wiring to a PP Series Power Pack
•Maximumthree(3)occupancysensorsperpowerpack
Note:Ifusingapowerpack,theblackwireontheoccupancysensormustbeconnectedtothecommon
terminalonboththeLutronlightingcontrolsystemcomponentandthepowerpack
Note:DoNOTusebluewireforANYinstallation.
Wiring to an Energi Savr Node Unit
•Maximumone(1)occupancysensorperEnergiSavr
Nodeinputgroup
•RefertoEnergiSavrNodeSpecicationSubmittal
foradditionaldetails
Capoff
remaining
wires
Cap
off
Cap
off
Occupancy
sensor
Occupancy
sensor
Occupancy
sensor
Lutronlighting
controlsystem
component
Lutronlighting
controlsystem
component
Lutronlighting
controlsystem
component
Powerpack
Red(20-24V-)
Black(Common)
Black(Common)
Gray(Signal)
Black(Common)
Gray(Signal)
Black(Common)
Gray(Signal)
Black
Black
Black
Blue(capoff)
+20V
OCC
COM
Capoff
remaining
wires
Black
(Common)
Gray
(Signal)
Red(20-24V-)
EnergiSavrNode
InputGroup
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wired Occupancy Sensors for High-Bay Applications
369606c 6 01.24.2019
Lutron
Sensors
DIP Switch Function DIP Switch Setting
1:Mode
5 6
5 6
5 6
5 6
1 1
Off:Normal
5 6
5 6
5 6
5 6
1 1
On:Test
(8second
time-out)
5and6:Timeout 8minutes(default)
5:Off6:Off
4minutes
5:Off6:On
16minutes
5 6
5:On6:Off
30minutes
5 6
5 6
5 6
5 6
1 1
5:On6:On
2through4and
7through12:
MUSTBESETTOOFF
1
2 3 4 5 6 7 8 9 10 11 12
SetalltoOff
O
N
1 2 3 4 5 6 7 8 9 10 11 12
OccupancySensor
withlensremoved
Operation
TheinternalDIPswitchesallowtheusertoselect
NormalorTestmode,andtoselectthetime-out.To
accesstheDIPswitches,rotatethelenscounter-
clockwiseuntilatablinesupwiththesingleline,
thenremovethelens.(Tolockthelensinplace,
rotateitclockwiseuntilatablinesupwiththe
doubleline).
Lenslockedinplace Lensunlocked
DIPswitches
)Lutron,Lutron,andEcoSystemaretrademarksofLutronElectronicsCo.,Inc.,registeredintheU.S.andothercountries.
EnergiSavrNodeisatrademarkofLutronElectronicsCo.,Inc.
6