SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wired Occupancy Sensors for High-Bay Applications
369606c 2 01.24.2019
Lutron
Sensors
30 ft (9 m) mounting height
45 ft (14 m) mounting height
Coverage Diagrams
Notes
Sensorisdesignedtodetectmajor
motion(i.e.,walkingperson)only
Adelayof1to2secondsfrom
occupancydetectiontoturn-onmay
beexperienced
42 ft (13 m) radius at 30 ft (9 m) mounting height
50 ft (15 m) radius at 45 ft (14 m) mounting height
Specifications
•20–24V-input30mAmax.
•Userinterface:12-pinDIPswitch
•Availabletimeroptions:
-8secondtestmode
-4,8,16,and30minutetimeouts
•Passiveinfrared:Dualelementpyrometerand
sphericalFresnellensdesignedtodetectmajor
motion(i.e.,walkingperson)
•Coverage:360°or180°
SeeCoverage Diagramsfordetails.
Lensratio:
-30ft(9m)mountingheight:1.4:1
-30to45ft(9to14m)mountingheight:1.1:1
•Construction:High-impactinjection-molded
plasticcasing
•Sizeandweight:4in(102mm)diameter
1½in(38mm)height
7oz(198g)
Sensor Placement
•Todetectmotion,thesensorrequiresline-of-sight
ofroomoccupants.Thesensormustalsohave
anunobstructedviewoftheroom.DoNOTmount
behindorneartallcabinets,shelves,hanging
xtures,ceilingfans,etc.Thesensorcannotsee
throughglassobjectssuchaspatioorshower
doors.
•Hotobjectsandmovingaircurrentscanaffect
theperformanceofthesensor.Toensureproper
operation,thesensorshouldbemountedatleast
4ft(1.2m)awayfromHVACventsandlightbulbs
thatarebelowtheceilingline.
•Theperformanceofthesensordependsona
temperaturedifferentialbetweentheambientroom
temperatureandthatoftheroomoccupants.
Warmerroomsmayreducetheabilityofthe
sensortodetectoccupants.
•DevicesemittingRadioFrequency(RF)energy
canaffecttheperformanceofsensors.Toensure
properoperation,sensorsshouldbemountedat
least4ft(1.2m)awayfromdevicesthatemitradio
waves(e.g.,microwaveovens,wirelessroutersor
otherwirelessdevices).
•Foradditionalinformationonplacingsensors,
pleaseseetheOccupancy/VacancySensor
DesignandApplicationGuide(P/N368-3197)
locatedatwww.lutron.com.
42 ft (13 m)
at 30 ft (9 m)
mounting height
50 ft (15 m)
at 45 ft (14 m) mounting height
29 ft
(9 m)
21 ft
(6 m)
360° Lens
Side View
180° Lens
Top View
Operating Environment
•Indooruseonly
•Operatingtemperature:32°F–86°F(0°C–30°C)
•Foruseinclimatecontrolledenvironmentsonly
•Relativehumidity(non-condensing):0–95%
Certifications
•ConformstoULSTD508,ULSTD244A
•CertiedtoCAN/USASTD22.2No.61010-1-04