by
Open Office | New Construction
IECC 2012
Control Functionality
Occupant Enters:
Not more than 50% of the lights automatically turn on when an occupant enters the space. The remaining
lights must be turned on manually.
When Occupied:
Manual: Occupant uses wall switch separately to turn off general lighting and daylight zone.
Occupant Exits:
All lights automatically turn off 15 minutes after all occupants exit.
Add a Vive wireless hub to enable simple setup and re-zoning, system monitoring, timeclock
functionality, and advanced integration.
Symbol Model Number Description Qty
RMJS-5R-DV-B PowPak switching module 2
LRF2-OCR2B-P-WH
Radio Powr Savr wireless ceiling-mount
occupancy sensor
4
PJ2-2B-GWH-L01 Pico wireless 2-button control 2
PICO-WBX-ADAPT Pico wallbox adapter 2
Line-voltage
wiring
Clear Connect
RF Communication
2 2 2 2
2 2 2 2
1 1 1 1
1 1 1 1
2
1
Code Notes: For non-daylight open offices, all general lighting can be connected to a single switching module.
Want to add a Vive wireless hub for more features? Go to lutron.com/vive for complete compatibility and design details.
© 06/2017 Lutron Electronics Co., Inc.
I
P/N 368-4576 REV B
Fixture
Insert Model Number
Insert Description
Insert
Qty