Where the main breaker of the electrical panel that the PV system will interconnect to is located at either the
top or bottom of the panel distribution bus bars and the PV interconnect breaker is located at the opposite
end, the code permits the sum of the ratings of the main breaker and the PV breaker to exceed the rating of the
panel bus bars. Per
Section 705.12 (D)(2)
, the sum of the electrical panel main breaker and the
microinverter PV interconnect breaker shall not add up to more than 120% of the rating of the panel bus
bars. For a 100 amp rated bus this means that both breakers together shall not add up to more than
120
amps.
For a 200 amp rated bus, not more than
240 amps
and for 225 amps, not more than
270 amps.
In
order to qualify for this additional allowance, the PV breaker
must
be located at the opposite end of the
breaker panel from the main breaker and shall have the warning label installed next to it per
Section 705.12
(D)(7)
.
“WARNING INVERTER OUTPUT CONNECTION. DO NOT RELOCATE THIS OVERCURRENT
DEVICE”.
Note:
Certain “All-in-One” service panels have the factory installed main breaker in the center of the di stribution
section. Because of the possibility of overloading the bus bars, this type of service is not able to take
advantage of the 120% overage permitted for top or bottom fed bussing. For this type of installation the sum
of the main circuit breaker and the PV breaker may not exceed 100% of the rating of the factory bussing.
For example, if the service panel label states that the bus bars are rated for 200 amps you cannot exceed
that figure. In some cases it may be possible to reduce the size of the main circuit breaker to accommodate
the addition of a PV breaker and still not exceed the bus bar rating. This requires that a “load calculation” of
the house electrical power consumption be made in order to see if this is an acceptable solution. Where it
is necessary to install the PV interconnection as a “Line Side Tap” and where the electrical service panel at
the dwelling is an “All-in-One” type, the service shall be provided with factory installed terminals designed
specifically to accommodate this type of connection. Where these terminals are not provided there shall be
NO
PV connection between the load side of the meter and the line side of the main circuit breaker.
J) Grounding the photovoltaic system:
A
Grounding Electrode Conductor
sized per the manufacturer’s installation instructions, (minimum #8
AWG solid copper), shall be run
UNSPLICED
from the factory identified grounding terminal of each
microinverter to the grounding electrode system of the house, (i.e. ground rod, Ufer ground, or metallic
water pipe with a minimum of 10 feet in the ground).
Note:
The Grounding Electrode Conductor is permitted to be spliced per
Section 250.64 (C)
using an
irreversible means or by the installation of a “Ground Plate”. (A Ground Plate is defined as a copper bus bar
1/4” thick by 2” wide by whatever length is needed to terminate the conductors). This conductor may also be
used as the required equipment grounding conductor for the modules and the frame rails of the array.
(Equipment grounding conductors may be connected to the Grounding Electrode Conductor by non-
irreversible means such as listed split bolts).
K) Disconnection of photovoltaic equipment:
Section 690.15 requires that means are provided to disconnect equipment from all ungrounded conductors of all
sources. Such disconnecting means shall comply with Sections 690.16 and 690.17.
Note: Section 690.17 contains an exception which states "A connector shall be permitted to be used as an ac
or a dc disconnecting means, provided that it complies with the requirements of 690.33 and is listed and
identified for the use."
L) Signage:
Per Section 690.54
, a permanent label for the microinverter AC power source shall be installed at the
point of interconnection at an accessible location. This label shall show that it is a PV source and additionally,
the rated AC output current and the nominal operating AC voltage.