SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
369147g 4 06.25.2018
Wallbox Controls0–10 V ControlsDiva
Specifications (continued)
DVTV- and DVSCTV- Models
Power
Operating Voltage
24V-100mA
Output Ratings
•Powerpackrequiredforloadswitching.Powerpackis
ratedfor16A.
•30mAmaximumoutput(sinkonly).
0–10 V Control Link
•0–10VcontrolisClass2.
•Controlsupto15ballastsordrivers(IEC60929Annex
E.2requirestheballast/drivertolimitthecurrentdraw
to2.0mAmaximum).
Performance
•For120–277V~installationsswitchingmorethan
8A,useDVTV-withLutronpowerpack(PP-DV).See
LutronP/N369544atwww.lutron.com.
•For347V~installations,useDVTV-withLutronpower
pack(PP-347H)SeeLutronP/N369544at
www.lutron.com.
•Workswithallballastsanddriversthatprovidea
currentsourcecomplianttoIEC60629AnnexE.2.
•Adjustablehigh-endandlow-endtrimforoptimal
dimmingperformance.
•Powerfailurememory:shouldpowerbeinterrupted,
the0–10V-signalwillreturntoitspreviouslysetlevel
priortotheinterruptionwhenpowerisrestored.
•Captivelinearslider.
•Precisecolormatching.
Environment
•Forindooruseonly.
• Ambientoperatingtemperature:32°Fto104°F
(0°Cto40°C),0%to90%humidity,
non-condensing.
Application Requirements
•Noderatingrequiredifganged.
•Nightlightnotavailable.
•Alwaysconsultlocalwiringcodes.
Warranty
•www.lutron.com/TechnicalDocumentLibrary/