40% of lot shall be maintained permeable surface (grass area). Show calculaons on drawings.
770 Sq Ft is the total amount of all accessory structures combined.
If new driveway is installed indicate on plat of survey the direcon water will flow. (Water shall not drain towards adjoining properes).
No materials shall be stored in the street or parkway at any me.
All excavated soil/materials and building materials must be removed from the site immediately following construcon.
Water from garage roof shall not drain towards adjoining properes.
The owner or contractor MUST contact J.U.L.I.E. at least 48 hours before construcon.
All jobsite dumpsters must be from GROOT 800‐244‐1977
Please fill in the following and include all informaon from below on drawings:
Total Height _______ feet from exisng grade to the peak (maximum 15’)
Depth: ________ Width: ________ (maximum 770 sq. .)
Setbacks: from side lot line ________ (minimum 3’) (Not permied to encroach vacated alley or easement)
from rear lot line __________ (minimum 5’) (Not permied to encroach vacated alley or easement)
from principle structure _______ (minimum 10’)
Type of Construcon: _____________________________________________
Type of Siding: Aluminum Wood Masonry Other ________________
Studs: 2 x _____ @ 16” O.C. Raer’s 2 x ____ @ 16” O.C.
Type of Sheathing: Plywood OSB Other _______________
Cross Ties: 2” x _______ @ 4’ O.C Eaves: ____ _ protruding from finished exterior wall.
Overhead garage door header: 2‐ 1 3/4 x 11 7/8 microlam 2‐ 2 x 14
Pitch: NO LESS THAN A 3 INCH IN 12 INCH ROOF SLOPE IS ALLOWED.
Electric: Exterior light is required outside each door and receptacle is required for garage door opener. All ready accessible outlets shall be GFI protected. Underground electric
shall be buried 6” below grade in rigid galvanized conduit or 18” in non‐metallic rigid.
Show on site/survey Com Ed service to house.
Grade:
When adjacent to an alley, slab SHALL NOT exceed 6” above alley unless approved by the Engineering Department.
Garage Slab shall be 4” concrete on top of 4” crushed stone with 6 x 6 x # 10 wire mesh. Perimeter shall be 12” wide 14” deep and 6” above grade.
Garages 600 square feet or greater, masonry, and brick veneer garages shall have a foundaon around the perimeter a minimum of 12” wide and 42” below grade.
Anchor Bolts shall be 6’ O.C. 12” from each corner, minimum 2 per plate.
Spoed survey showing all setbacks and elevaon is required to be approved prior to any framing.
As‐built civil drawings are required for final inspecon.
If you have any quesons concerning a detached garage please contact the building department.
John Montejo (847) 588‐8067 Building Inspector jpm@vniles.com
Dennis O’Donovan (847) 588‐8064 Building Inspector dpo@vniles.com
REQUIRED INSPECTIONS: Pre‐Pour Underground Electric Final (Building & Electric)
DETACHED GARAGE PERMIT CONDITIONS
THIS FORM MUST BE SUBMITTED ALONG WITH A COMPLETED PERMIT APPLICATION